Plan Review Notes
Plan Review Notes For Permit 16070049
Permit Number 16070049
Review Stop E
Sequence Number 2
Notes
Date Text
2016-10-18 19:25:572ND ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 JOB ADDRESS: 335 KENILWORTH BLVD.
 DESCRIPTION: INTERIOR REPAIRS TO INCLUDE NEW ELECTRICAL
 AND HVAC
 MASTER PERMIT: 16070049
  
 THIS WAS REVIEWED ONCE BEFORE. THE BELOW COMMENTS ARE
 NUMBERED IN ACCORDANCE WITH THE PREVIOUS COMMENTS. ANY
 GREATER NUMBER REPRESENTS NEW OBSERVATIONS. ADDITIONAL
 CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF SUBMITTED
 CORRECTIONS.
 1. RESPONSE ACCEPTED
 2. RESPONSE ACCEPTED
 3. YOU SHALL CORRECTLY LABEL ALL PANELS ON THE RISER
 DIAGRAM TO MATCH THE PANEL SCHEDULES AND UNIT NUMBERS.
 YOU SHALL CORRECT THE LOAD CALCS AND OCPD FOR EACH UNIT
 AND MULTI DWELLING SERVICE INCLUDING THE LAUNDRY
 CIRCUIT LOADS. KEEP IN MIND THAT THE WATER HEATERS,
 RANGE, LIGHTING AND HVAC ARE CONTINUOUS LOADS. YOU
 SHALL INCLUDE CONDUCTOR SIZING AND PROPOSED INSULATION
 TYPE. THE GROUNDING SHALL COMPLY WITH NEC 250.53. BLDG.
 A RISER IS MISSING THE INTER-SYSTEM BONDING REQUIRED BY
 NEC 250.94.
 4. ADDITIONAL CO (CARBON MONOXIDE) DETECTORS ARE
 REQUIRED FOR BEDROOMS 1 OF BLDG. A.
 5. FBC-ER3905.8: A BLOCK NOTE STATING COMPLIANCE WITH
 THIS SHALL BE PLACED ON THE DRAWINGS.
 6. RESPONSE ACCEPTED
 7. FBC-ER3903.4: YOU INDICATE THAT THERE IS NO ATTIC,
 YET THE DRAWINGS FOR BLDG. A SUGGEST OTHERWISE. MAY I
 SUGGEST THAT THIS BE SWITCHED OUTSIDE THE ATTIC AND
 CONTROLLED WITH A SWITCH THAT HAS A PILOT SO AS TO
 INDICATE IF THE LIGHT IS ACCIDENTLY LEFT ON.
 7. RESPONSE ACCEPTED
 8. RESPONSE ACCEPTED
 9. RESPONSE ACCEPTED
 10. RESPONSE ACCEPTED
 11. PER FBC BLDG. "A" UNITS 1 & 2 BATHROOMS REQUIRE
 MECHANICAL VENTILATION WHENEVER THE ROOM IS OCCUPIED.
 THEREFORE THE EXHAUST FAN SHALL BE CONNECTED TO THE
 LIGHT TO COME ON SIMULTANEOUSLY.
 12. APT. 2 KITCHEN IS MISSING THE REQUIRED OUTLETS.
 13. RECEPTACLES INSTALLED IN DAMP OR WET LOCATIONS
 SHALL IN ADDITION TO HAVING AND IN-USE TYPE COVER, BE
 LISTED WEATHER-RESISTANT. A BLOCK NOTE TO THIS SHALL BE
 INCLUDED ON THE DRAWINGS.
 14. FBC-RE3901.7: BLDG. "B" IS MISSING THE EXTERIOR
 OUTLET REQUIRED BY CODE.
 15. FBC-ER3903.4: A LIGHT CONTROLLED BY A WALL SWITCH
 IS REQUIRED IN THE WATER HEATER CLOSET.
 16. FBC-ER404.1: A MINIMUM OF 75% OF THE PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL BE OF THE
 HIGH-EFFICACY TYPE OR HAVE A MINIMUM OF 75% OF THE
 FIXTURES SHALL CONTAIN HIGH-EFFICACY LAMPS.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  