2016-10-18 19:25:57 | 2ND ELECTRICAL REVIEW NOTES |
| REVIEWED FOR COMPLIANCE WITH: |
| 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| |
| JOB ADDRESS: 335 KENILWORTH BLVD. |
| DESCRIPTION: INTERIOR REPAIRS TO INCLUDE NEW ELECTRICAL |
| AND HVAC |
| MASTER PERMIT: 16070049 |
| |
| THIS WAS REVIEWED ONCE BEFORE. THE BELOW COMMENTS ARE |
| NUMBERED IN ACCORDANCE WITH THE PREVIOUS COMMENTS. ANY |
| GREATER NUMBER REPRESENTS NEW OBSERVATIONS. ADDITIONAL |
| CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF SUBMITTED |
| CORRECTIONS. |
| 1. RESPONSE ACCEPTED |
| 2. RESPONSE ACCEPTED |
| 3. YOU SHALL CORRECTLY LABEL ALL PANELS ON THE RISER |
| DIAGRAM TO MATCH THE PANEL SCHEDULES AND UNIT NUMBERS. |
| YOU SHALL CORRECT THE LOAD CALCS AND OCPD FOR EACH UNIT |
| AND MULTI DWELLING SERVICE INCLUDING THE LAUNDRY |
| CIRCUIT LOADS. KEEP IN MIND THAT THE WATER HEATERS, |
| RANGE, LIGHTING AND HVAC ARE CONTINUOUS LOADS. YOU |
| SHALL INCLUDE CONDUCTOR SIZING AND PROPOSED INSULATION |
| TYPE. THE GROUNDING SHALL COMPLY WITH NEC 250.53. BLDG. |
| A RISER IS MISSING THE INTER-SYSTEM BONDING REQUIRED BY |
| NEC 250.94. |
| 4. ADDITIONAL CO (CARBON MONOXIDE) DETECTORS ARE |
| REQUIRED FOR BEDROOMS 1 OF BLDG. A. |
| 5. FBC-ER3905.8: A BLOCK NOTE STATING COMPLIANCE WITH |
| THIS SHALL BE PLACED ON THE DRAWINGS. |
| 6. RESPONSE ACCEPTED |
| 7. FBC-ER3903.4: YOU INDICATE THAT THERE IS NO ATTIC, |
| YET THE DRAWINGS FOR BLDG. A SUGGEST OTHERWISE. MAY I |
| SUGGEST THAT THIS BE SWITCHED OUTSIDE THE ATTIC AND |
| CONTROLLED WITH A SWITCH THAT HAS A PILOT SO AS TO |
| INDICATE IF THE LIGHT IS ACCIDENTLY LEFT ON. |
| 7. RESPONSE ACCEPTED |
| 8. RESPONSE ACCEPTED |
| 9. RESPONSE ACCEPTED |
| 10. RESPONSE ACCEPTED |
| 11. PER FBC BLDG. "A" UNITS 1 & 2 BATHROOMS REQUIRE |
| MECHANICAL VENTILATION WHENEVER THE ROOM IS OCCUPIED. |
| THEREFORE THE EXHAUST FAN SHALL BE CONNECTED TO THE |
| LIGHT TO COME ON SIMULTANEOUSLY. |
| 12. APT. 2 KITCHEN IS MISSING THE REQUIRED OUTLETS. |
| 13. RECEPTACLES INSTALLED IN DAMP OR WET LOCATIONS |
| SHALL IN ADDITION TO HAVING AND IN-USE TYPE COVER, BE |
| LISTED WEATHER-RESISTANT. A BLOCK NOTE TO THIS SHALL BE |
| INCLUDED ON THE DRAWINGS. |
| 14. FBC-RE3901.7: BLDG. "B" IS MISSING THE EXTERIOR |
| OUTLET REQUIRED BY CODE. |
| 15. FBC-ER3903.4: A LIGHT CONTROLLED BY A WALL SWITCH |
| IS REQUIRED IN THE WATER HEATER CLOSET. |
| 16. FBC-ER404.1: A MINIMUM OF 75% OF THE PERMANENTLY |
| INSTALLED LIGHTING FIXTURES SHALL BE OF THE |
| HIGH-EFFICACY TYPE OR HAVE A MINIMUM OF 75% OF THE |
| FIXTURES SHALL CONTAIN HIGH-EFFICACY LAMPS. |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |