2016-08-11 03:14:04 | BUILDING "A". |
| 1) SUBMIT AN EXISTING FLOOR PLAN THAT SHOWS THE CURRENT |
| LOCATION OF ALL THE PLUMBING FIXTURES. THE PLANS ARE |
| VAGUE AS TO THE SCOPE OF PLUMBING WORK THAT IS TO BE |
| DONE. ARE THE NEW FIXTURES BEING REPLACED IN THE SAME |
| EXACT LOCATIONS? CLARIFY THIS ON THE PLANS AND BE |
| SPECIFIC. WPB AMEND. TO FBC SEC.107.2.1. |
| 2) SHOW THE FIXTURE CLEARANCES FOR THE PLUMBING |
| FIXTURES IN ACCORDANCE WITH 2014 FBCR-P2705.1. |
| 3) SHOW THE LENGTH AND WIDTH DIMENSIONS OF ALL THE |
| SHOWERS.COMPLY WITH 2014 FBCR- P2708.1. |
| 4) THE WATER HEATERS ARE SHOWN ON THE EXTERIOR OF THE |
| STRUCTURE. INDDICATE IF THEY ARE LOCATED IN AN |
| ENCLOSURE OR NOT. THE PLANS SHOW THE WATER HEATERS AS |
| "EGH". I AM ASSUMING THIS MEANS "EXISTING GAS HEATER." |
| CLARIFY. |
| 5) THE SUBMITTED SANITARY RISER DOES NOT COMPLY WITH |
| THE PLUMBING CODE. COMPLY WITH 2014 FBCR-SEC. P3108.1 |
| FOR FIXTURES PERMITTED ON A WET VENT. ALSO, REFER TO |
| 2014 FBCR-SEC. R202 FOR THE DEFINITION OF A BATHROOM |
| GROUP. |
| 6) CLEANOUTS ARE REQUIRED IN THE BASE OF WASTE STACKS |
| PER 2104 FBCR SEC.P3005.2.6. |
| |
| BUILDING "B" |
| 1) SUBMIT AN EXISTING FLOOR PLAN THAT SHOWS THE CURRENT |
| LOCATION OF ALL THE PLUMBING FIXTURES. THE PLANS ARE |
| VAGUE AS TO THE SCOPE OF PLUMBING WORK THAT IS TO BE |
| DONE. ARE THE NEW FIXTURES BEING REPLACED IN THE SAME |
| EXACT LOCATIONS? CLARIFY THIS ON THE PLANS AND BE |
| SPECIFIC. WPB AMEND. TO FBC SEC.107.2.1. |
| 2) SHOW THE FIXTURE CLEARANCES FOR THE PLUMBING |
| FIXTURES IN ACCORDANCE WITH 2014 FBCR-P2705.1. |
| 3) SHOW THE LENGTH AND WIDTH DIMENSIONS OF THE |
| SHOWER.COMPLY WITH 2014 FBCR- P2708.1. |
| 4) SUBMIT A SANITARY RISER FOR REVIEW. WPB AMEND. TO |
| FBC SEC. 107.3.5.3.. |
| 6) CLEANOUTS ARE REQUIRED IN THE BASE OF WASTE STACKS |
| PER 2104 FBCR SEC.P3005.2.6. |
| |