2016-07-12 16:11:38 | 1ST ELECTRICAL REVIEW NOTES |
| REVIEWED FOR COMPLIANCE WITH: |
| 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| |
| 1. FBC-107.2.5 A SITE PLAN SHOWING THE LOCATION OF ALL |
| STRUCTURES ON THE SITE SHALL BE PROVIDED. THIS PLAN |
| SHALL INCLUDE THE LOCATION OF EVERY ELECTRICAL SERVICE, |
| ELECTRICAL METER & ELECTRICAL SERVICE DISCONNECT. SHOW |
| ON THE PLANS THE LOCATION OF THE FPL POLE SERVING THE |
| PROPERTY. |
| 2. NEC 230.2 AS WELL AS FPL?S SERVICE STANDARDS LIMITS |
| A SINGLE DROP PER PROPERTY. |
| 3. THE SUBMITTED DRAWING HAS CONFLICTING INFORMATION. |
| THERE ARE TWO BLDGS. BOTH OF WHICH ARE LABELED BLDG. B |
| EACH OF WHICH ACCORDING TO THE RISER DIAGRAMS IS |
| SUPPOSED TO HAVE TWO APARTMENTS. THE PLAN ONLY SHOWS |
| THREE APARTMENTS AND THREE ELECTRICAL PANELS. CORRECT |
| ACCORDINGLY. |
| 4. FBC-R315 YOU SHALL INSTALL CARBON MONOXIDE DETECTORS |
| WITHIN 10? OF THE DOOR TO EACH SLEEPING AREA. |
| 5. FBC-RE3905.8 BOXES FOR CEILING/PADDLE FANS SHALL BE |
| LISTED FOR THE APPLICATION |
| 6. FBC-RE3901.12 A 125V 1 PHASE 15/20 AMP OUTLET IS |
| REQUIRED WITHIN 25? OF CONDENSING UNITS OR HVAC |
| EQUIPMENT INSIDE AN ATTIC. |
| 7. FBC-RE3903.4 AT LEAST ONE LIGHTING OUTLET CONTROLLED |
| BY A WALL SWITCH CLOSE TO THE USUAL POINT OF ENTRY |
| SHALL BE INSTALLED IN ATTICS WHERE EQUIPMENT REQUIRING |
| SERVICE IS INSTALLED. |
| 8. FBC-RE3703.3/NEC210.11/FBC-RE3901.58 A 20 |
| AMPERE-RATED OUTLET SHALL BE PROVIDED TO SERVE THE |
| LAUNDRY AREA. |
| 9. FBC-RE4101.5/NEC422.33 YOU SHALL HAVE A DISCONNECT |
| FOR THE WATER HEATER. |
| 10. FBC-ER A LEAST 75% OF PERMANENTLY INSTALLED LAMPS |
| SHALL BE OF THE HIGH EFFICIENCY TYPE. |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |