Plan Review Notes
Plan Review Notes For Permit 16070049
Permit Number 16070049
Review Stop E
Sequence Number 1
Notes
Date Text
2016-07-12 16:11:381ST ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 1. FBC-107.2.5 A SITE PLAN SHOWING THE LOCATION OF ALL
 STRUCTURES ON THE SITE SHALL BE PROVIDED. THIS PLAN
 SHALL INCLUDE THE LOCATION OF EVERY ELECTRICAL SERVICE,
 ELECTRICAL METER & ELECTRICAL SERVICE DISCONNECT. SHOW
 ON THE PLANS THE LOCATION OF THE FPL POLE SERVING THE
 PROPERTY.
 2. NEC 230.2 AS WELL AS FPL?S SERVICE STANDARDS LIMITS
 A SINGLE DROP PER PROPERTY.
 3. THE SUBMITTED DRAWING HAS CONFLICTING INFORMATION.
 THERE ARE TWO BLDGS. BOTH OF WHICH ARE LABELED BLDG. B
 EACH OF WHICH ACCORDING TO THE RISER DIAGRAMS IS
 SUPPOSED TO HAVE TWO APARTMENTS. THE PLAN ONLY SHOWS
 THREE APARTMENTS AND THREE ELECTRICAL PANELS. CORRECT
 ACCORDINGLY.
 4. FBC-R315 YOU SHALL INSTALL CARBON MONOXIDE DETECTORS
 WITHIN 10? OF THE DOOR TO EACH SLEEPING AREA.
 5. FBC-RE3905.8 BOXES FOR CEILING/PADDLE FANS SHALL BE
 LISTED FOR THE APPLICATION
 6. FBC-RE3901.12 A 125V 1 PHASE 15/20 AMP OUTLET IS
 REQUIRED WITHIN 25? OF CONDENSING UNITS OR HVAC
 EQUIPMENT INSIDE AN ATTIC.
 7. FBC-RE3903.4 AT LEAST ONE LIGHTING OUTLET CONTROLLED
 BY A WALL SWITCH CLOSE TO THE USUAL POINT OF ENTRY
 SHALL BE INSTALLED IN ATTICS WHERE EQUIPMENT REQUIRING
 SERVICE IS INSTALLED.
 8. FBC-RE3703.3/NEC210.11/FBC-RE3901.58 A 20
 AMPERE-RATED OUTLET SHALL BE PROVIDED TO SERVE THE
 LAUNDRY AREA.
 9. FBC-RE4101.5/NEC422.33 YOU SHALL HAVE A DISCONNECT
 FOR THE WATER HEATER.
 10. FBC-ER A LEAST 75% OF PERMANENTLY INSTALLED LAMPS
 SHALL BE OF THE HIGH EFFICIENCY TYPE.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  