2016-07-22 13:06:12 | BUILDING PLAN REVIEW |
| 2014 FLORIDA BUILDING CODE |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| BUILDING PLANS EXAMINER ? PX3169 |
| CONSTRUCTION SERVICES DIVISION |
| DEVELOPMENT SERVICES DEPARTMENT |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| DATE: 7/22/16 |
| |
| 1. PLANS TO BE SIGNED AND SEALED BY DESIGNER OF RECORD. |
| 2. PALM BEACH COUNTY IMPACT FEES MAY APPLY. |
| 3. ROOFING PERMIT REQUIRED. |
| 4. PROVIDE ENERGY CALCULATIONS. |
| 5. SEPERATE PERMIT REQUIRED FOR SECOND DWELLING UNIT. |
| PERMITS MAY RUN CONCURRENTLY AND SHARE PLANS. |
| 6. PROVIDE PRODUCT APPROVALS FOR NEW WINDOWS. |
| 7. PROVIDE DETAIL FOR 1 HR RATED WALL. WALL TO RUN FROM |
| FOUNDATION TO UNDERSIDE OF ROOF ASSEMBLY PER FBC |
| R302.3. |
| 8. PROVIDE SITE PLAN SHOWING LOCATION OF BUILDINGS AND |
| SETBACKS. |
| |
| FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| CONSTRUCTION DOCUMENTS SHALL BE |
| DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. |
| CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL |
| CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH |
| INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES |
| SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE |
| TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE |
| FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS, |
| SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE |
| NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE |
| DESIGN. (SEE ALSO SECTION 107.3.5). |
| |
| BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES |
| MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE |
| SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM |
| BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH |
| THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT |
| MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE |
| THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL |
| PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025. |
| |
| FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE. |
| AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402 |
| SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO |
| DEMONSTRATE CODE COMPLIANCE BY THIS METHOD. |
| |
| FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. |
| AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 |
| (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE |
| SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE |
| COMPLIANCE BY SECTION 405. |
| |
| R401.3 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD |
| (MANDATORY). |
| THE BUILDING OFFICIAL SHALL REQUIRE THAT AN ENERGY |
| PERFORMANCE LEVEL (EPL) DISPLAY CARD BE COMPLETED AND |
| CERTIFIED BY THE BUILDER TO BE ACCURATE AND CORRECT |
| BEFORE FINAL APPROVAL OF THE BUILDING FOR OCCUPANCY. |
| FLORIDA LAW [SECTION 553.9085, FLORIDA STATUTES)] |
| REQUIRES THE EPL DISPLAY CARD TO BE INCLUDED AS AN |
| ADDENDUM TO EACH SALES CONTRACT FOR BOTH PRESOLD AND |
| NONPRESOLD RESIDENTIAL BUILDINGS. THE EPL DISPLAY CARD |
| CONTAINS INFORMATION INDICATING THE ENERGY PERFORMANCE |
| LEVEL AND EFFICIENCIES OF COMPONENTS INSTALLED IN A |
| DWELLING UNIT. THE BUILDING OFFICIAL SHALL VERIFY THAT |
| THE EPL DISPLAY CARD COMPLETED AND SIGNED BY THE |
| BUILDER ACCURATELY REFLECTS THE PLANS AND |
| SPECIFICATIONS SUBMITTED TO DEMONSTRATE CODE COMPLIANCE |
| FOR THE BUILDING. A COPY OF THE EPL DISPLAY CARD CAN BE |
| FOUND IN APPENDIX C. |
| |
| FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE |
| PRODUCTS WHICH ARE REGULATED BY |
| FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD. SPECIFICALLY, PROVIDE ROOFING, |
| WINDOW AND DOOR SUBMITTALS. |
| |
| R302.3 TWO-FAMILY DWELLINGS. |
| DWELLING UNITS IN TWO-FAMILY DWELLINGS SHALL BE |
| SEPARATED FROM EACH OTHER BY WALL AND/OR FLOOR |
| ASSEMBLIES HAVING NOT LESS THAN A 1-HOUR |
| FIRE-RESISTANCE RATING WHEN TESTED IN ACCORDANCE WITH |
| ASTM E 119 OR UL 263. FIRE-RESISTANCE-RATED |
| FLOOR/CEILING AND WALL ASSEMBLIES SHALL EXTEND TO AND |
| BE TIGHT AGAINST THE EXTERIOR WALL, AND WALL ASSEMBLIES |
| SHALL EXTEND FROM THE FOUNDATION TO THE UNDERSIDE OF |
| THE ROOF SHEATHING. |
| |
| |
| |