2016-07-05 18:40:23RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS.
 CODE: FBC, 5TH EDITION (2014).
  
 1- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS (2
 COPIES) FOR THE ROOF REPAIRS AND GENERAL REPAIRS
 SPECIFIED ON THE PERMIT APPLICATION. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 2- FLAT ROOF NOA 14-0529.02 SUBMITTED:
 A) CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO
 BE INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301 FBC-RESIDENTIAL, 5TH EDITION
 (2014).
  
 B) IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES OF SEC. R301, THEN SIGNED AND SEALED RAS 117
 CALCULATIONS ARE REQUIRED BY GENERAL LIMITATION #7 ON
 LAST PAGE ON NOA SUBMITTED.
 NOTE: ASSEMBLIES WITH GENERAL LIMITATION #9 CAN NOT BE
 USED IF THE DESIGN PRESSURES SHOWN ON THE ASSEMBLY
 DON'T MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES.
  
  
 NOA APPROVED:
 SHINGLES NOA 14-1022.20