| PLUMBING COMMENTS: |
| |
| 1. PE PIPE UNDER HOUSE TO COOK TOP IS NOT APPROVED. PER |
| FBC FUEL GAS 404.17.1 LIMITATIONS. PLASTIC PIPE SHALL |
| BE INSTALLED OUTDOORS UNDERGROUND ONLY. PLASTIC PIPE |
| SHALL NOT BE USED WITHIN OR UNDER ANY BUILDING OR SLAB |
| OR BE OPERATED AT PRESSURES GREATER THAN 100 PSIG (689 |
| KPA) FOR NATURAL GAS OR 30 PSIG (207 KPA) FOR LP-GAS |
| |
| 2. DRIP OR SEDIMENT TRAPS CAN NOT BE INSTALLED IN-THE |
| RUN THEY SHALL BE AT THE 90. PER FBC FUEL GAS 408.4 |
| SEDIMENT TRAP. |
| WHERE A SEDIMENT TRAP IS NOT INCORPORATED AS PART OF |
| THE APPLIANCE, A SEDIMENT TRAP SHALL BE INSTALLED |
| DOWNSTREAM OF THE APPLIANCE SHUTOFF VALVE AS CLOSE TO |
| THE INLET OF THE APPLIANCE AS PRACTICAL. THE SEDIMENT |
| TRAP SHALL BE EITHER A TEE FITTING HAVING A CAPPED |
| NIPPLE OF ANY LENGTH INSTALLED VERTICALLY IN THE |
| BOTTOMMOST OPENING OF THE TEE AS ILLUSTRATED IN FIGURE |
| 408.4 OR OTHER DEVICE APPROVED AS AN EFFECTIVE SEDIMENT |
| TRAP. ILLUMINATING APPLIANCES, RANGES, CLOTHES DRYERS, |
| DECORATIVE VENTED APPLIANCES FOR INSTALLATION IN VENTED |
| FIREPLACES, GAS FIREPLACES, AND OUTDOOR GRILLS NEED NOT |
| BE SO EQUIPPED. |
| |
| 3. THE PE PIPE UP TO THE TEE FOR THE POOL HEATER AND |
| TANKLESS SHALL BE 3/4 . PER FBC FUEL GAS TABLE |
| 402.4(36) |
| |
| 4.SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE |
| FBC-2014 FUEL GAS CODE SEC. 304 |
| |
| 5.SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL |
| GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA |
| 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 |
| |
| 6. THE GALV. PIPE COMING OF METER TO THE PE RISER SHALL |
| BE !1/4IN. FBC-2014 FUEL GAS CODE TABLE 402.4(5) |