Plan Review Notes For Permit 16061690 |
Permit Number |
16061690 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-07-05 08:05:27 | 1)THE METER SHOWS A .5 INCH WATER COLUMN PRESSURE BUT | | THE PLAN NOTES A 2 PSI SYSTEM. CLARIFY. | | 2) SIZE THE SHORT SECTION OF PIPE COMING FROM THE GAS | | METER. | | 3) I HAVE ADDED THE THE LENGTHS OF PIPE SHOWN ON THE | | GAS DRAWING AND NOTHING ADDS UP TO THE 260 FT. TOTAL | | LENGTH SHOWN ON THE PLANS. CLARIFY. | | 4) SHOW THE TYPE OF PIPING FOR THE EXISTING SYSTEM. | | 5) SHOW THE TYPE OF PIPING FROM THE METER TO THE POOL | | HEATER AND THE FIRE FEATURE. | | 6) SIZE THE PIPE TO THE EXISTING RANGE. | | 7) SHOW THE LENGTH OF THE SECTION OF PIPE FROM THE | | METER TO THE POOL HEATER. | | 8) TABLE 402.4 (5) IS REFERENCED ON THE PLAN WHICH IS | | THE TABLE FOR 2 PSI BUT THE METER NOTES ".5 INCH W.C." | | CLARIFY. | | 9) THE PLAN NOTES 2 PSI REGULATORS BUT 3 REGULATORS ARE | | SHOWN. CLARIFY. | | 10) CLEARLY SHOW ALL LENGTHS OF PIPE SECTION. | | 11) THE PLAN SHOWS THE TOTAL BTU LOAD AS 600K AND ALSO | | AS 790K. CLARIFY. | | 12) SUBMIT AN EXPANDED GAS DIAGRAM THAT CLEARLY SHOWS | | ALL REQUIRED INFORMATION. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|