Plan Review Notes
Plan Review Notes For Permit 16061598
Permit Number 16061598
Review Stop E
Sequence Number 1
Notes
Date Text
2016-07-13 18:27:29I HAD THIS FILE ON MY DESK WAITING TO HEAR BACK FROM
 THE EC. BY 7/13/16 I HAD NOT HEARD FROM HIM SO I ROUTED
 TO SMALL DENIED DRAWER A. MA
2016-06-29 16:00:21I PLACED A CALL TO THE EC TO INQUIRE ON THE LOCATION OF
 THE SERVICE DISCONNECTS TO ASCERTAIN COMPLIANCE W/NEC
 230.70(A)(1). THE DRAWING IS ALSO LACKING THE
 INTER-SYSTEM BONDING TERMINAL REQUIRED IN NEC 250.94.