Plan Review Notes
Plan Review Notes For Permit 16061589
Permit Number 16061589
Review Stop B
Sequence Number 1
Notes
Date Text
2016-07-06 13:26:10BUILDING PLAN REVIEW
 REVISION: 16061589
 PERMIT:14071105
 ADD: 1517 CAMERON SAMUEL LN.
 CONT: KAST
 TEL: (561)346-4994
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: WED. JULY 2016
 ACTION: DENIED
  
 1) THE DESIGNER OF RECORD (ARCHITECT) HAS NOT REVIEWED
 THE INTERIOR DESIGNERS DRAWING FOR THE OVERALL CONCEPT
 IS IN COMPLIANCE WITH THE ARCHITECTS DESIGN.
  
 1A) IN THE LAST REVISION 15031217 THE ARCHITECTURAL
 PLAN A-1.0 SHOWS THE RISER GOING ACROSS THE THEATER IN
 A STRAIGHT LINE 90 DEGREES TO THE SIDE WALLS. WHILE THE
 INTERIOR DESIGNER HAS A STRAIGHT LINE DOTTED AND A
 CURVED SOLID LINE, SHEET ID-11 DOES NOT HAVE A LEGEND
 INDICATING WHAT THESE LINES REPRESENT. DOES THE DOTTED
 LINE REPRESENT THE RISERS AND THE CURVED SOLID LINE
 INDICATE A DROPPED CEILING? THERE ARE NO CUT SECTIONS
 THROUGH THE CEILING SHOWING A DROPPED CEILING OR
 CONSTRUCTION OTHER THAN A FLAT CEILING. 107.2.1.3. NOT
 ENOUGH DETAIL IN THE PLANS TO INDICATE CODE COMPLIANCE.
  
 1B) BOTH SHEETS ID-03 AND ID-11 SHOW THE STAGE GOING
 ALL THE WAY ACROSS THE FRONT OF THE THEATER. WHERE AS
 THE ARCHITECTURAL SHEET A-1.0 REVISION 15031217 SHOWS
 ON THE ONE SIDE OF THE STAGE AN AREA WHERE A PLATFORM
 LIFT IS TO BE INSTALLED AND ON THE OPPOSITE SIDE OF THE
 STAGE A DOOR THAT LEADS INTO THE CONCESSION AREA. AGAIN
 THE PLANS DO NOT CONFORM TO THE DESIGNER OF RECORDS
 PLANS ON FILE WITH THE CITY. THESE SHEETS NEED TO BE
 REVISED.
  
 1C) SHEET ID-11 DOES NOT INDICATE THE LAYOUT OF THE
 SEATING NOR THE AISLES FOR EGRESS. THE OTHER ISSUE THE
 PLANS DO NOT PROVIDE A HANDRAILS ON EITHER SIDE OF THE
 EGRESS AISLES. PLEASE PROVIDE CODE COMPLIANCE WITH:
 2010 FBC-B 1028.9.1 MINIMUM AISLE WIDTH.
 THE MINIMUM CLEAR WIDTH FOR AISLES SHALL BE AS SHOWN:
 1. FORTY-EIGHT INCHES (1219 MM) FOR AISLE STAIRS HAVING
 SEATING ON EACH SIDE.
 EXCEPTION: THIRTY-SIX INCHES (914 MM) WHERE THE AISLE
 SERVES LESS
 THAN 50 SEATS.
 2. THIRTY-SIX INCHES (914 MM) FOR AISLE STAIRS HAVING
 SEATING ON ONLY ONE SIDE.
 EXCEPTION: TWENTY-THREE INCHES (584 MM) BETWEEN AN
 AISLE STAIR HANDRAIL AND SEATING WHERE AN AISLE DOES
 NOT SERVE MORE THAN FIVE ROWS ON ONE SIDE.
 3. TWENTY-THREE INCHES (584 MM) BETWEEN AN AISLE STAIR
 HANDRAIL OR GUARD AND SEATING WHERE THE AISLE IS
 SUBDIVIDED BY A HANDRAIL.
 4. FORTY-TWO INCHES (1067 MM) FOR LEVEL OR RAMPED
 AISLES HAVING SEATING ON BOTH SIDES.
  
 1D) SHEET ID-11, THE WALLS & CEILING APPEAR TO BE SET
 OUT TYPE OF CONSTRUCTION WITH FOAM AND FABRIC FINISHES
 PLEASE PROVIDE WHAT TYPE OF FRAME WORK AND BACKING
 MATERIAL CREATES THE BACKING FOR THE WALL PANELS, THIS
 HOLDS TRUE FOR THE FORMICA PANEL ASSEMBLY AS WELL. SHOW
 COMPLIANCE WITH: 2010 FBC-B 803.11.2 SET-OUT
 CONSTRUCTION. WHERE WALLS AND CEILINGS ARE REQUIRED TO
 BE OF FIRE-RESISTANCE-RATED OR NONCOMBUSTIBLE
 CONSTRUCTION AND WALLS ARE SET OUT OR CEILINGS ARE
 DROPPED DISTANCES GREATER THAN SPECIFIED IN SECTION
 803.11.1, CLASS A FINISH MATERIALS( FLAME SPREAD INDEX
 0-25; SMOKE DEVELOPMENT INDEX 0-450, ASTM E 84 OR UL
 723), IN ACCORDANCE WITH SECTION 803.1.1 OR 803.1.2,
 SHALL BE USED.
 EXCEPTIONS:
 1. WHERE INTERIOR FINISH MATERIALS ARE PROTECTED ON
 BOTH SIDES BY AN AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH SECTION 903.3.1.1 OR 903.3.1.2.
 2. WHERE INTERIOR FINISH MATERIALS ARE ATTACHED TO
 NONCOMBUSTIBLE BACKING OR FURRING STRIPS INSTALLED AS
 SPECIFIED IN SECTION 803.11.1.1.
  
 THE POLYURETHANE FOAM SUBMITTED WAS NOT TESTED TO THE
 CORRECT STANDARD.
  
 1E) 803.5 TEXTILE WALL COVERINGS. WHERE USED AS
 INTERIOR WALL FINISH MATERIALS, TEXTILE WALL COVERINGS,
 INCLUDING MATERIALS HAVING WOVEN OR NONWOVEN, NAPPED,
 TUFTED, LOOPED OR SIMILAR SURFACE AND CARPET AND
 SIMILAR TEXTILE MATERIALS, SHALL BE TESTED IN THE
 MANNER INTENDED FOR USE, USING THE PRODUCT MOUNTING
 SYSTEM, INCLUDING ADHESIVE, AND SHALL COMPLY WITH THE
 REQUIREMENTS OF SECTION 803.1.2, 803.1.3 OR 803.1.4.
 803.1.2 ROOM CORNER TEST FOR INTERIOR WALL OR CEILING
 FINISH MATERIALS.
 INTERIOR WALL OR CEILING FINISH MATERIALS SHALL BE
 PERMITTED TO BE TESTED IN ACCORDANCE WITH NFPA 286.
 INTERIOR WALL OR CEILING FINISH MATERIALS TESTED IN
 ACCORDANCE WITH NFPA 286 SHALL COMPLY WITH SECTION
 803.1.2.1.
 803.1.3 ROOM CORNER TEST FOR TEXTILE WALL COVERINGS AND
 EXPANDED VINYL WALL COVERINGS.
 TEXTILE WALL COVERINGS AND EXPANDED VINYL WALL
 COVERINGS SHALL MEET THE CRITERIA OF SECTION 803.1.3.1
 WHEN TESTED IN THE MANNER INTENDED FOR USE IN
 ACCORDANCE WITH THE METHOD B PROTOCOL OF NFPA 265 USING
 THE PRODUCT-MOUNTING SYSTEM, INCLUDING ADHESIVE.
 803.1.4 ACCEPTANCE CRITERIA FOR TEXTILE AND EXPANDED
 VINYL WALL OR CEILING COVERINGS TESTED TO ASTM E 84 OR
 UL 723.
 TEXTILE WALL AND CEILING COVERINGS AND EXPANDED VINYL
 WALL AND CEILING COVERINGS SHALL HAVE A CLASS A FLAME
 SPREAD INDEX IN ACCORDANCE WITH ASTM E 84 OR UL 723 AND
 BE PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM INSTALLED
 IN ACCORDANCE WITH SECTION 903.3.1.1 OR 903.3.1.2. TEST
 SPECIMEN PREPARATION AND MOUNTING SHALL BE IN
 ACCORDANCE WITH ASTM E 2404.
  
 1F) 803.6 TEXTILE CEILING COVERINGS. WHERE USED AS
 INTERIOR CEILING FINISH MATERIALS, TEXTILE CEILING
 COVERINGS, INCLUDING MATERIALS HAVING WOVEN OR
 NONWOVEN, NAPPED, TUFTED, LOOPED OR SIMILAR SURFACE AND
 CARPET AND SIMILAR TEXTILE MATERIALS, SHALL BE TESTED
 IN THE MANNER INTENDED FOR USE, USING THE PRODUCT
 MOUNTING SYSTEM, INCLUDING ADHESIVE, AND SHALL COMPLY
 WITH THE REQUIREMENTS OF SECTION 803.1.2 OR 803.1.4.
  
 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676