2016-07-06 13:26:10 | BUILDING PLAN REVIEW |
| REVISION: 16061589 |
| PERMIT:14071105 |
| ADD: 1517 CAMERON SAMUEL LN. |
| CONT: KAST |
| TEL: (561)346-4994 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 1ST REVIEW |
| DATE: WED. JULY 2016 |
| ACTION: DENIED |
| |
| 1) THE DESIGNER OF RECORD (ARCHITECT) HAS NOT REVIEWED |
| THE INTERIOR DESIGNERS DRAWING FOR THE OVERALL CONCEPT |
| IS IN COMPLIANCE WITH THE ARCHITECTS DESIGN. |
| |
| 1A) IN THE LAST REVISION 15031217 THE ARCHITECTURAL |
| PLAN A-1.0 SHOWS THE RISER GOING ACROSS THE THEATER IN |
| A STRAIGHT LINE 90 DEGREES TO THE SIDE WALLS. WHILE THE |
| INTERIOR DESIGNER HAS A STRAIGHT LINE DOTTED AND A |
| CURVED SOLID LINE, SHEET ID-11 DOES NOT HAVE A LEGEND |
| INDICATING WHAT THESE LINES REPRESENT. DOES THE DOTTED |
| LINE REPRESENT THE RISERS AND THE CURVED SOLID LINE |
| INDICATE A DROPPED CEILING? THERE ARE NO CUT SECTIONS |
| THROUGH THE CEILING SHOWING A DROPPED CEILING OR |
| CONSTRUCTION OTHER THAN A FLAT CEILING. 107.2.1.3. NOT |
| ENOUGH DETAIL IN THE PLANS TO INDICATE CODE COMPLIANCE. |
| |
| 1B) BOTH SHEETS ID-03 AND ID-11 SHOW THE STAGE GOING |
| ALL THE WAY ACROSS THE FRONT OF THE THEATER. WHERE AS |
| THE ARCHITECTURAL SHEET A-1.0 REVISION 15031217 SHOWS |
| ON THE ONE SIDE OF THE STAGE AN AREA WHERE A PLATFORM |
| LIFT IS TO BE INSTALLED AND ON THE OPPOSITE SIDE OF THE |
| STAGE A DOOR THAT LEADS INTO THE CONCESSION AREA. AGAIN |
| THE PLANS DO NOT CONFORM TO THE DESIGNER OF RECORDS |
| PLANS ON FILE WITH THE CITY. THESE SHEETS NEED TO BE |
| REVISED. |
| |
| 1C) SHEET ID-11 DOES NOT INDICATE THE LAYOUT OF THE |
| SEATING NOR THE AISLES FOR EGRESS. THE OTHER ISSUE THE |
| PLANS DO NOT PROVIDE A HANDRAILS ON EITHER SIDE OF THE |
| EGRESS AISLES. PLEASE PROVIDE CODE COMPLIANCE WITH: |
| 2010 FBC-B 1028.9.1 MINIMUM AISLE WIDTH. |
| THE MINIMUM CLEAR WIDTH FOR AISLES SHALL BE AS SHOWN: |
| 1. FORTY-EIGHT INCHES (1219 MM) FOR AISLE STAIRS HAVING |
| SEATING ON EACH SIDE. |
| EXCEPTION: THIRTY-SIX INCHES (914 MM) WHERE THE AISLE |
| SERVES LESS |
| THAN 50 SEATS. |
| 2. THIRTY-SIX INCHES (914 MM) FOR AISLE STAIRS HAVING |
| SEATING ON ONLY ONE SIDE. |
| EXCEPTION: TWENTY-THREE INCHES (584 MM) BETWEEN AN |
| AISLE STAIR HANDRAIL AND SEATING WHERE AN AISLE DOES |
| NOT SERVE MORE THAN FIVE ROWS ON ONE SIDE. |
| 3. TWENTY-THREE INCHES (584 MM) BETWEEN AN AISLE STAIR |
| HANDRAIL OR GUARD AND SEATING WHERE THE AISLE IS |
| SUBDIVIDED BY A HANDRAIL. |
| 4. FORTY-TWO INCHES (1067 MM) FOR LEVEL OR RAMPED |
| AISLES HAVING SEATING ON BOTH SIDES. |
| |
| 1D) SHEET ID-11, THE WALLS & CEILING APPEAR TO BE SET |
| OUT TYPE OF CONSTRUCTION WITH FOAM AND FABRIC FINISHES |
| PLEASE PROVIDE WHAT TYPE OF FRAME WORK AND BACKING |
| MATERIAL CREATES THE BACKING FOR THE WALL PANELS, THIS |
| HOLDS TRUE FOR THE FORMICA PANEL ASSEMBLY AS WELL. SHOW |
| COMPLIANCE WITH: 2010 FBC-B 803.11.2 SET-OUT |
| CONSTRUCTION. WHERE WALLS AND CEILINGS ARE REQUIRED TO |
| BE OF FIRE-RESISTANCE-RATED OR NONCOMBUSTIBLE |
| CONSTRUCTION AND WALLS ARE SET OUT OR CEILINGS ARE |
| DROPPED DISTANCES GREATER THAN SPECIFIED IN SECTION |
| 803.11.1, CLASS A FINISH MATERIALS( FLAME SPREAD INDEX |
| 0-25; SMOKE DEVELOPMENT INDEX 0-450, ASTM E 84 OR UL |
| 723), IN ACCORDANCE WITH SECTION 803.1.1 OR 803.1.2, |
| SHALL BE USED. |
| EXCEPTIONS: |
| 1. WHERE INTERIOR FINISH MATERIALS ARE PROTECTED ON |
| BOTH SIDES BY AN AUTOMATIC SPRINKLER SYSTEM IN |
| ACCORDANCE WITH SECTION 903.3.1.1 OR 903.3.1.2. |
| 2. WHERE INTERIOR FINISH MATERIALS ARE ATTACHED TO |
| NONCOMBUSTIBLE BACKING OR FURRING STRIPS INSTALLED AS |
| SPECIFIED IN SECTION 803.11.1.1. |
| |
| THE POLYURETHANE FOAM SUBMITTED WAS NOT TESTED TO THE |
| CORRECT STANDARD. |
| |
| 1E) 803.5 TEXTILE WALL COVERINGS. WHERE USED AS |
| INTERIOR WALL FINISH MATERIALS, TEXTILE WALL COVERINGS, |
| INCLUDING MATERIALS HAVING WOVEN OR NONWOVEN, NAPPED, |
| TUFTED, LOOPED OR SIMILAR SURFACE AND CARPET AND |
| SIMILAR TEXTILE MATERIALS, SHALL BE TESTED IN THE |
| MANNER INTENDED FOR USE, USING THE PRODUCT MOUNTING |
| SYSTEM, INCLUDING ADHESIVE, AND SHALL COMPLY WITH THE |
| REQUIREMENTS OF SECTION 803.1.2, 803.1.3 OR 803.1.4. |
| 803.1.2 ROOM CORNER TEST FOR INTERIOR WALL OR CEILING |
| FINISH MATERIALS. |
| INTERIOR WALL OR CEILING FINISH MATERIALS SHALL BE |
| PERMITTED TO BE TESTED IN ACCORDANCE WITH NFPA 286. |
| INTERIOR WALL OR CEILING FINISH MATERIALS TESTED IN |
| ACCORDANCE WITH NFPA 286 SHALL COMPLY WITH SECTION |
| 803.1.2.1. |
| 803.1.3 ROOM CORNER TEST FOR TEXTILE WALL COVERINGS AND |
| EXPANDED VINYL WALL COVERINGS. |
| TEXTILE WALL COVERINGS AND EXPANDED VINYL WALL |
| COVERINGS SHALL MEET THE CRITERIA OF SECTION 803.1.3.1 |
| WHEN TESTED IN THE MANNER INTENDED FOR USE IN |
| ACCORDANCE WITH THE METHOD B PROTOCOL OF NFPA 265 USING |
| THE PRODUCT-MOUNTING SYSTEM, INCLUDING ADHESIVE. |
| 803.1.4 ACCEPTANCE CRITERIA FOR TEXTILE AND EXPANDED |
| VINYL WALL OR CEILING COVERINGS TESTED TO ASTM E 84 OR |
| UL 723. |
| TEXTILE WALL AND CEILING COVERINGS AND EXPANDED VINYL |
| WALL AND CEILING COVERINGS SHALL HAVE A CLASS A FLAME |
| SPREAD INDEX IN ACCORDANCE WITH ASTM E 84 OR UL 723 AND |
| BE PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM INSTALLED |
| IN ACCORDANCE WITH SECTION 903.3.1.1 OR 903.3.1.2. TEST |
| SPECIMEN PREPARATION AND MOUNTING SHALL BE IN |
| ACCORDANCE WITH ASTM E 2404. |
| |
| 1F) 803.6 TEXTILE CEILING COVERINGS. WHERE USED AS |
| INTERIOR CEILING FINISH MATERIALS, TEXTILE CEILING |
| COVERINGS, INCLUDING MATERIALS HAVING WOVEN OR |
| NONWOVEN, NAPPED, TUFTED, LOOPED OR SIMILAR SURFACE AND |
| CARPET AND SIMILAR TEXTILE MATERIALS, SHALL BE TESTED |
| IN THE MANNER INTENDED FOR USE, USING THE PRODUCT |
| MOUNTING SYSTEM, INCLUDING ADHESIVE, AND SHALL COMPLY |
| WITH THE REQUIREMENTS OF SECTION 803.1.2 OR 803.1.4. |
| |
| 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |