Plan Review Notes
Plan Review Notes For Permit 16061576
Permit Number 16061576
Review Stop E
Sequence Number 1
Notes
Date Text
2016-06-30 17:48:03REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 - SINCE THE SERVICE IS BEING CHANGED SHOW AMPERE RATING
 OF METER ENCLOSURE, GROUNDING DETAIL TO INCLUDE
 ELECTRODE SIZING, CONDUIT AND SERVICE ENTRANCE
 CONDUCTOR SIZES. FBC 107 MINIMUM PLAN CRITEREA.
  
 - NEC 250.94 BONDING FOR OTHER SYSTEMS. THE
 INTER-SYSTEM BONDING TERMINAL PRESCRIBED SHALL BE
 INSTALLED
  
 - THE GENERATOR SHALL HAVE A DISSCONNECT WITHIN SIGHT
 OR INTERGRATED. IF NOT THE GENERATOR DISCONNECTING
 MEANS SHALL BE LOCKABLE IN THE OPEN POSITION. NEC
 445.18