Plan Review Notes For Permit 16061576 |
Permit Number |
16061576 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-06-30 17:48:03 | REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6713 | | [email protected] | | | | - SINCE THE SERVICE IS BEING CHANGED SHOW AMPERE RATING | | OF METER ENCLOSURE, GROUNDING DETAIL TO INCLUDE | | ELECTRODE SIZING, CONDUIT AND SERVICE ENTRANCE | | CONDUCTOR SIZES. FBC 107 MINIMUM PLAN CRITEREA. | | | | - NEC 250.94 BONDING FOR OTHER SYSTEMS. THE | | INTER-SYSTEM BONDING TERMINAL PRESCRIBED SHALL BE | | INSTALLED | | | | - THE GENERATOR SHALL HAVE A DISSCONNECT WITHIN SIGHT | | OR INTERGRATED. IF NOT THE GENERATOR DISCONNECTING | | MEANS SHALL BE LOCKABLE IN THE OPEN POSITION. NEC | | 445.18 |
|