Plan Review Notes For Permit 16061557 |
Permit Number |
16061557 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-06-30 11:57:01 | 1ST REVIEW: FBC 2014 MECHANICAL | | PERMIT #16061557 | | 6/20/16 | | | | 1) PLEASE IDENTIFY ALL ROOMS ON THE PLANS. | | | | 2) THERE APPEARS TO BE DUCT DROPS MISSING IN SOME OF | | THE FIRST FLOOR ROOMS. | | | | 3) THE TRANSFER GRILLS ON THE SECOND FLOOR PLAN ARE | | UNDERSIZED PER SECTION M1602.4 FBC-14 RESIDENTIAL | | EXCEPTION (2): TRANSFER GRILLES SHALL USE 50 SQUARE | | INCHES (32 258 MM2) (OF GRILLE AREA) TO 100 CFM (OF | | SUPPLY AIR) FOR SIZING THROUGH-THE-WALL TRANSFER | | GRILLES AND USING AN UNRESTRICTED 1-INCH (25 MM) | | UNDERCUTTING OF DOORS TO ACHIEVE PROPER RETURN AIR | | BALANCE. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|