2016-06-30 11:57:011ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16061557
 6/20/16
  
 1) PLEASE IDENTIFY ALL ROOMS ON THE PLANS.
  
 2) THERE APPEARS TO BE DUCT DROPS MISSING IN SOME OF
 THE FIRST FLOOR ROOMS.
  
 3) THE TRANSFER GRILLS ON THE SECOND FLOOR PLAN ARE
 UNDERSIZED PER SECTION M1602.4 FBC-14 RESIDENTIAL
 EXCEPTION (2): TRANSFER GRILLES SHALL USE 50 SQUARE
 INCHES (32 258 MM2) (OF GRILLE AREA) TO 100 CFM (OF
 SUPPLY AIR) FOR SIZING THROUGH-THE-WALL TRANSFER
 GRILLES AND USING AN UNRESTRICTED 1-INCH (25 MM)
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER RETURN AIR
 BALANCE.
  