Plan Review Notes
Plan Review Notes For Permit 16061460
Permit Number 16061460
Review Stop E
Sequence Number 1
Notes
Date Text
2016-06-29 17:39:06REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 - PROVIDE A SITE SPECIFIC PLAN TO INCLUDE THE LOCATION
 OF THE POWER SOURCE IN RELATION TO THE ELECTRICAL
 EQUIPMENT OF THE BOATLIFT. FBC 107 MINIMUM PLAN
 CRITEREA
  
 - THE RISER DIAGRAM SHALL INCLUDE COUNDUIT SIZE AND
 ROUTING, HOT-NUETRAL-GROUND WIRE SIZE, AND OVERCURRENT
 PROTECTION SIZE. NEC 215.5. PLEASE KEEP IN MIND GFCI
 PROTECTION FOR BOATHOUSES NEC 210.8(A)(8)