2017-10-03 13:04:46 | ****PROVISOS**** |
| ****ISSUED AT APPLICANT'S RISK**** |
| ****REVISION REQUIRED (SEE ITEM 19) |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| 1. PROVISO: 110.3.7.4.3 ALL SHORING AND RESHORING |
| PROCEDURES, PLANS AND DETAILS SHALL BE SUBMITTED TO THE |
| ENFORCEMENT AGENCY FOR RECORDKEEPING. EACH SHORING AND |
| RESHORING INSTALLATION SHALL BE SUPERVISED, INSPECTED |
| AND CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING |
| DOCUMENTS BY THE CONTRACTOR. |
| |
| 2. PLEASE CALL THE CITY OF WEST PALM BEACHS AUTOMATED |
| TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL |
| BUILDING INSPECTIONS FOR AUDITING OF JOBSITE |
| INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6 |
| MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. |
| |
| 3. INFORMATIONAL NO ACTION REQUIRED. 109.3.6 THRESHOLD |
| BUILDINGS, OPERATING GUIDELINES FOR THRESHOLD |
| INSPECTORS #26. ASSURE THAT THE DESIGNER HAS REQUIRED |
| ON THE PLANS OR SPECIFICATIONS ONE MATERIAL, APPROVED |
| FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND CEILINGS. |
| |
| 4. PROVISO: UNDER A SEPARATE PERMIT. PERIMETER FENCING |
| UNDER A SEPARATE PERMIT. PLEASE PROVIDE COMPLIANCE |
| WITH: 2014 FBC-B 3306.5 BARRIERS. BARRIERS SHALL BE A |
| MINIMUM OF 8 FEET (2438 MM) IN HEIGHT AND SHALL BE |
| PLACED ON THE SIDE OF THE WALKWAY NEAREST THE |
| CONSTRUCTION. BARRIERS SHALL EXTEND THE ENTIRE LENGTH |
| OF THE CONSTRUCTION SITE. |
| |
| 5. PROVISO: UNDER A SEPARATE PERMIT. 2014 FBC0B 3306.2 |
| WALKWAYS. A WALKWAY SHALL BE PROVIDED FOR PEDESTRIAN |
| TRAVEL IN FRONT OF EVERY CONSTRUCTION AND DEMOLITION |
| SITE UNLESS THE APPLICABLE GOVERNING AUTHORITY |
| AUTHORIZES THE SIDEWALK TO BE FENCED OR CLOSED. |
| WALKWAYS SHALL BE OF SUFFICIENT WIDTH TO ACCOMMODATE |
| THE PEDESTRIAN TRAFFIC, BUT IN NO CASE SHALL THEY BE |
| LESS THAN 4 FEET (1219 MM) IN WIDTH. WALKWAYS SHALL BE |
| PROVIDED WITH A DURABLE WALKING SURFACE. WALKWAYS SHALL |
| BE ACCESSIBLE IN ACCORDANCE WITH CHAPTER 11 AND SHALL |
| BE DESIGNED TO SUPPORT ALL IMPOSED LOADS AND IN NO CASE |
| SHALL THE DESIGN LIVE LOAD BE LESS THAN 150 POUNDS PER |
| SQUARE FOOT (PSF). |
| |
| 6. PROVISO: UNDER A SEPARATE PERMIT. 2014 FBC-B 3306.7 |
| COVERED WALKWAYS. COVERED WALKWAYS SHALL HAVE A CLEAR |
| HEIGHT OF NOT LESS THAN 8 FEET (2438 MM) AS MEASURED |
| FROM THE FLOOR SURFACE TO THE CANOPY OVERHEAD. ADEQUATE |
| LIGHTING SHALL BE PROVIDED AT ALL TIMES. COVERED |
| WALKWAYS SHALL BE DESIGNED TO SUPPORT ALL IMPOSED |
| LOADS. IN NO CASE SHALL THE DESIGN LIVE LOAD BE LESS |
| THAN 150 PSF FOR THE ENTIRE STRUCTURE. |
| |
| 7. BUILDING PROVISO: PRODUCT APPROVALS LISTED BELOW CAN |
| BE DEFERRED SUBMITTALS WITH THE APPROVAL OF EITHER THE |
| DESIGNER OF RECORD OR CONTRACTOR ONCE THE WIND DESIGN |
| CRITERIA IS REVIEWED AND APPROVED THEN THE SUBMITTALS |
| CAN BE SUBMITTED AFTER PERMIT ISSUANCE. 107.3.4.2 |
| DEFERRED SUBMITTALS. |
| 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| OF COMMUNITY AFFAIRS RULE 61G20-3, SUB-CATEGORY OF |
| PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (B) WINDOWS, MULLIONS |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, EFIS SYSTEMS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS, |
| INTAKE AND EXHAUST FANS |
| (E) SHUTTERS |
| (F) SKYLIGHTS |
| (G PRE-ENGINEERED A/C STANDS |
| FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH |
| ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR |
| TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL |
| 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 8. BUILDING PROVISO, DEFERRED SUBMITTALS PRODUCT |
| APPROVALS & SHOP DRAWINGS. |
| IDENTIFY GLAZING/ MULLIONS. FOR ALL PRODUCTS WITH |
| GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, |
| TYPE OF GLAZING, MULLION INFORMATION IF REQUIRED, |
| ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING |
| SIZE. 107.2.1 CONSTRUCTION DOCUMENTS SHALL BE OF |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| DETERMINED BY THE BUILDING OFFICIAL. |
| |
| 9. BUILDING PROVISO/ DEFERRED SUBMITTAL: OPEN AIR |
| TERRACE WATERPROOFING MATERIAL AND DETAILS. SHEET 5.11. |
| ADMINISTRATION 107.3.4 DESIGN PROFESSIONAL IN |
| RESPONSIBLE CHARGE. THE REGISTERED DESIGN |
| PROFESSIONAL IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE |
| FOR REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS |
| PREPARED BY OTHERS, INCLUDING PHASED AND DEFERRED |
| SUBMITTAL ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF |
| THE BUILDING. PRODUCTS SHALL BE REVIEWED AND APPROVED |
| IN WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL. |
| |
| 10. BUILDING PROVISO/ DEFERRED SUBMITTALS: OPEN AIR |
| TERRACE VIVA BLADE GUARD RAIL SYSTEM. SHEET 5.11. |
| ADMINISTRATION 107.3.4 DESIGN PROFESSIONAL IN |
| RESPONSIBLE CHARGE. THE REGISTERED DESIGN |
| PROFESSIONAL IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE |
| FOR REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS |
| PREPARED BY OTHERS, INCLUDING PHASED AND DEFERRED |
| SUBMITTAL ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF |
| THE BUILDING. PRODUCTS SHALL BE REVIEWED AND APPROVED |
| IN WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL. |
| |
| 11. BUILDING PROVISO: POOL AND JACUZZI ARE NOT PART OF |
| THIS PERMIT, WILL REQUIRE A SEPARATE PERMIT, REVIEW AND |
| ASSOCIATED FEES. FENCING AND GATES AROUND THE POOL WILL |
| REQUIRE A SEPARATE PERMIT, REVIEW AND ASSOCIATED FEES. |
| |
| 12. SEPARATE PERMITS (APPLICATION, PLANS, REVIEWS, AND |
| FEES) REQUIRED FOR ALL ITEMS OTHER THAN MECHANICAL, |
| ELECTRICAL, AND PLUMBING FOR THE BUILDING AS SHOWN ON |
| THE PLANS. THIS INCLUDES SIGNS, FIRE ALARM, FIRE |
| SPRINKLERS, LANDSCAPING. |
| |
| 13. BUILDING PROVISO/ DEFERRED SUBMITTAL: |
| AN APPROVED BUILDING INFORMATION CARD THAT CONTAINS, |
| BUT IS NOT LIMITED TO, THE FOLLOWING INFORMATION, |
| 13.1-13.7: |
| |
| 13.1. GENERAL BUILDING INFORMATION THAT INCLUDES: |
| PROPERTY NAME, ADDRESS, THE NUMBER OF FLOORS IN THE |
| BUILDING (ABOVE AND BELOW GRADE), USE AND OCCUPANCY |
| CLASSIFICATION (FOR MIXED USES, IDENTIFY THE DIFFERENT |
| TYPES OF OCCUPANCIES ON EACH FLOOR), ESTIMATED BUILDING |
| POPULATION (I.E., DAY, NIGHT, WEEKEND); |
| |
| 13.2. BUILDING EMERGENCY CONTACT INFORMATION THAT |
| INCLUDES: A LIST OF THE BUILDING?S EMERGENCY CONTACTS |
| (E.G., BUILDING MANAGER, BUILDING ENGINEER, ETC.) AND |
| THEIR RESPECTIVE WORK PHONE NUMBER, CELL PHONE NUMBER, |
| EMAIL ADDRESS; |
| |
| 13.3. BUILDING CONSTRUCTION INFORMATION THAT INCLUDES: |
| THE TYPE OF BUILDING CONSTRUCTION (E.G., FLOORS, WALLS, |
| COLUMNS, AND ROOF ASSEMBLY); |
| |
| 13.4. EXIT STAIR INFORMATION THAT INCLUDES: NUMBER OF |
| EXIT STAIRS IN BUILDING, EACH EXIT STAIR DESIGNATION |
| AND FLOORS SERVED, LOCATION WHERE EACH EXIT STAIR |
| DISCHARGES, EXIT STAIRS THAT ARE PRESSURIZED, EXIT |
| STAIRS PROVIDED WITH EMERGENCY LIGHTING, EACH EXIT |
| STAIR THAT ALLOWS REENTRY, EXIT STAIRS PROVIDING ROOF |
| ACCESS; ELEVATOR INFORMATION THAT INCLUDES: NUMBER OF |
| ELEVATOR BANKS, ELEVATOR BANK DESIGNATION, ELEVATOR CAR |
| NUMBERS AND RESPECTIVE FLOORS THAT THEY SERVE, LOCATION |
| OF ELEVATOR MACHINE ROOMS, LOCATION OF SKY LOBBY, |
| LOCATION OF FREIGHT ELEVATOR BANKS; |
| |
| 13.5. BUILDING SERVICES AND SYSTEM INFORMATION THAT |
| INCLUDES: LOCATION OF MECHANICAL ROOMS, LOCATION OF |
| BUILDING MANAGEMENT SYSTEM, LOCATION AND CAPACITY OF |
| ALL FUEL OIL TANKS, LOCATION OF EMERGENCY GENERATOR, |
| LOCATION OF NATURAL GAS SERVICE; |
| |
| 13.6. FIRE PROTECTION SYSTEM INFORMATION THAT INCLUDES: |
| LOCATIONS OF STANDPIPES, LOCATION OF FIRE PUMP ROOM, |
| LOCATION OF FIRE DEPARTMENT CONNECTIONS, FLOORS |
| PROTECTED BY AUTOMATIC SPRINKLERS, LOCATION OF |
| DIFFERENT TYPES OF SPRINKLER SYSTEMS INSTALLED (E.G., |
| DRY, WET, PRE-ACTION, ETC.); AND |
| |
| 13.7 HAZARDOUS MATERIAL INFORMATION THAT INCLUDES: |
| LOCATION OF HAZARDOUS MATERIAL, QUANTITY OF HAZARDOUS |
| MATERIAL. |
| |
| 14. BUILDING PROVISO: DEFERRED SUBMITTAL. SHEETS A6.02 |
| & A6.03 STAIR GUARDRAIL/ HANDRAILS . ADMINISTRATION |
| 107.3.4 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE. THE |
| REGISTERED DESIGN |
| PROFESSIONAL IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE |
| FOR REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS |
| PREPARED BY OTHERS, INCLUDING PHASED AND DEFERRED |
| SUBMITTAL ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF |
| THE BUILDING. |
| FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL |
| FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE |
| ENGINEER OF RECORD FOR REVIEW. |
| |
| 15. BUILDING PROVISO/ DEFERRED SUBMITTAL. ON THE TOP OF |
| THE 8 FT. CONCRETE CANOPY WHAT PRODUCT WILL BE USED TO |
| KEEP MOISTURE FROM SEEPING INTO THE CONCRETE SLAB AND |
| REINFORCEMENT? |
| |
| 16. BUILDING PROVISO/ DEFERRED SUBMITTAL. SHEET A4.01 |
| THE NORTH WALL ELEVATION ON THE GARAGE LEVELS 3-5 THE |
| PLANS SHOW PERFORATED ALUMINUM PANEL SYSTEM. PLEASE |
| PROVIDE PRODUCT LITERATURE, AND ENGINEERING ANALYSIS OF |
| THE SYSTEM, WITH THE WIND DESIGN CRITERIA AND ANCHORING |
| SYSTEMS REVIEWED BY THE ENGINEER OF RECORD. FL |
| 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL FORWARD |
| THE DELEGATED ENGINEERING DOCUMENTS TO THE ENGINEER OF |
| RECORD FOR REVIEW. 2014 FBC-B 1503.1 ROOF DECKS SHALL |
| BE COVERED WITH APPROVED ROOF COVERINGS SECURED TO THE |
| BUILDING OR STRUCTURE IN ACCORDANCE WITH THE PROVISIONS |
| OF THIS CHAPTER. ROOF COVERINGS SHALL BE DESIGNED AND |
| INSTALLED IN ACCORDANCE WITH THIS CODE AND THE APPROVED |
| MANUFACTURER?S INSTRUCTIONS SUCH THAT THE ROOF COVERING |
| SHALL SERVE TO PROTECT THE BUILDING OR STRUCTURE. |
| |
| 17. SUB PERMITS (APPLICATION, SUB PERMIT FEE OF $80) |
| ARE REQUIRED FOR MECHANICAL, ELECTRICAL, PLUMBING AND |
| ROOFING PRIOR TO COMMENCEMENT OF WORK. |
| |
| 18. DEFERRED SUBMITTAL: IF ACOUSTIC FLOORING |
| UNDERLAYMENT IS PROPOSED, FBC B 603.1, ALLOWABLE |
| MATERIALS IN NON COMBUSTIBLE BUILDINGS, SEE ITEM 2, |
| EXCEPTION 2, ACOUSTICAL INSULATION INSTALLED BETWEEN A |
| FINISHED FLOOR AND SOLID DECKING WITHOUT INTERVENING |
| AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX |
| OF NOT MORE THAN 200. SEE 803.1.1, PROVIDE TEST DATA IN |
| ACCORDANCE WITH ASTM E 84 OR UL 723. SUBMIT PRIOR TO |
| INSTALLATION. |
| |
| 19. REVISION REQUIRED; PER ARCHITECT, 2 HOUR SHAFT |
| DETAIL ON SHEETS A3.05 AND 3.08A (AND ANY OTHER |
| AFFECTED LOCATIONS NOT LISTED) WILL BE REVISED (FBC |
| BUILDING 703.2.1, NEED HORIZONTAL ASSEMBLY). A REVISION |
| IS REQUIRED PRIOR TO INSTALLATION. |
| |
| 20. WHEN AVAILABLE, PROVIDE THE TEST PILE PROGRAM |
| REPORT. REPORT IS TO BE REVIEWED BY SEOR PRIOR TO |
| SUBMITTAL. |
| |