Plan Review Notes For Permit 16061443 |
Permit Number |
16061443 |
|
Review Stop |
P |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2017-08-02 14:33:28 | 1) THE TRENCH DRAIN DETAIL DOES NOT SHOW THAT THIS | | DRAIN IS EQUIPPED WITH A WATER SEAL TRAP. COMPLY WITH | | 2014 FBC-PLUMBING SEC. 1002.1. | | 2) SUBMIT COMPLETE SPECIFICATIONS / DETAILS FOR THE PCU | | UNIT. WPB AMEND. TO FBC SEC. 107.2.1. | | 3) SHT.P5.06 - THE SAMPLING PORT THAT SHOWS THE DOUBLE | | SANITARY TEE WITH A CAP AT THE BOTTOM IS NOT AN | | ACCEPTED DESIGN BY THE CITY. THE TWO WAY CLEANOUT ON | | THE DISCHARGE SIDE OF THE GREASE INTERCEPTOR CAN BE | | USED AS THE SAMPLING PORT AS LONG AS IT IS A MINIMUM OF | | 4 INCHES IN DIAMETER. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | |
|