Plan Review Notes
Plan Review Notes For Permit 16061443
Permit Number 16061443
Review Stop P
Sequence Number 4
Notes
Date Text
2017-08-02 14:33:281) THE TRENCH DRAIN DETAIL DOES NOT SHOW THAT THIS
 DRAIN IS EQUIPPED WITH A WATER SEAL TRAP. COMPLY WITH
 2014 FBC-PLUMBING SEC. 1002.1.
 2) SUBMIT COMPLETE SPECIFICATIONS / DETAILS FOR THE PCU
 UNIT. WPB AMEND. TO FBC SEC. 107.2.1.
 3) SHT.P5.06 - THE SAMPLING PORT THAT SHOWS THE DOUBLE
 SANITARY TEE WITH A CAP AT THE BOTTOM IS NOT AN
 ACCEPTED DESIGN BY THE CITY. THE TWO WAY CLEANOUT ON
 THE DISCHARGE SIDE OF THE GREASE INTERCEPTOR CAN BE
 USED AS THE SAMPLING PORT AS LONG AS IT IS A MINIMUM OF
 4 INCHES IN DIAMETER.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW