2017-08-11 11:38:091) SHT. M2.09 - POOL EQUIPMENT ROOM COMBUSTION AIR
 CALCULATIONS - A REFERENCE IS MADE TO THE 2014 FUEL GAS
 CODE SEC.304.6.2.THIS SECTION REFERS TO ONE PERMANENT
 OPENING FOR COMBUSTION AIR YET THE PLAN REFERS TO TWO
 OPENINGS. CLARIFY.
 2) SHT. M2.09 - POOL EQUIPMENT ROOM COMBUSTION AIR
 CALCULATIONS - A REFERENCE IS MADE TO THE 2014 FUEL GAS
 CODE SEC.304.6.2.THIS SECTION REQIURES THE COMBUSTION
 AIR OPENING TO HAVE 1 SQUARE INCH PER 3,000 BTU'S YET
 THE PLAN NOTES THE TOTAL BTU LOAD BEING DIVIDED BY
 4,000. CLARIFY.
 3) PLEASE CLARIFY HOW THE 1058 FREE SQ. INCH AREA WAS
 DETERMINED. SEC. 304.10 OF THE 2014 FGC NOTES THAT
 METAL LOUVERSAND GRILLES WILL BE ASSUMED TO HAVE A 75
 PERCENT FREE AREA. THE DIMENSION OF THE LOUVERS ARE
 SHOWN AS 54 X 36= 1944 X.75 = 1458 SQ. INCHES PER
 LOUVER. CLARIFY.
 4) SPECIFICATIONS HAVE BEEN SUBMITTED FOR GAS SUPPLIED
 MID-RANGE IRONERS BUT THIS EQUIPMENT IS NOT SHOWN ON
 THE GAS RISER AND THE BTU LOAD IS NOT INCLUDED IN THE
 TOTAL. CLARIFY.SUBMIT COMBUSTION AIR CALCULATIONS FOR
 THIS PIECE OF EQUIPMENT.
 5) SHT. M2.02 - LAUNDRY APPLIANCE CALCULATIONS REFER TO
 SF-2.1 TWICE. CLARIFY.THE PLAN ALSO NOTES THAT THEY ARE
 THE MAKEUP AIR FANS FOR DBF 2.2 & 2.3. THE FAN SCHEDULE
 ON SHT. M6.01 NOTES THESE UNITS AS "NOT USED." CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW