2017-03-20 06:32:40 | 1) SHT. A7.41 - INDICATE ON THE PLANS THAT THE SHOWER |
| SEAT IN ALTERNATE ROLL-IN SHOWER IS OF THE FOLDING |
| TYPE. 2014 FBC-ACCESSIBILITY SEC.610.3. 2ND REQUEST. |
| 2) A LINT INTERCEPTOR IS REQUIRED FOR THE WASHING |
| MACHINES PER 2014 FBC-PLUMBING SEC.1003.6. SUBMIT A |
| DETAIL AND SIZING CALCULATIONS FOR THE UNIT. THE |
| SUBMITTED RESPONSE NARRATIVE REFERS TO A DETAIL ON SHT. |
| P5.01 BUT THERE IS NO DETAIL ON THIS PLAN AND I COULD |
| NOT FIND A DETAIL ANYWHERE IN THE PLANS. 2ND REQUEST. |
| 3) SHT. P4.03 - SANITARY RISER # S/14 - 13TH FLOOR |
| TOILET ROOM #1305 BY STAIR # 2 - THE SANITARY RISER |
| DOEES NOT COMPLY WITH FBC 2014-PLUMBING SECS. 912 OR |
| 914 FOR A HORIZONTAL WET VET OR A CIRCUIT VENT. PLACING |
| A VENT ON THE FIRST WATER CLOSET CONNECTED TO THE |
| HORIZONTAL DRAIN WILLL CORRECT THIS ISSUE. 2ND REQUEST. |
| 4) SHT. P4.03 - SANITARY RISER S/14 - 7TH FLOOR KING |
| SUITE AND FLOORS 8 - 11 - A MAXIMUM OF 4 FIXTURE UNITS |
| ARE PERMITTED ON A 2 INCH WET VENT PER 2014 |
| FBC-PLUMBING SEC.912.3 & TABLE 912.3. THE RISER SHOWS 6 |
| FIXTURE UNITS ON A WET VENT. |
| 5) SHTS. P4.04 & P4.05 - WATER RISERS -WATER FILTERS, |
| BEVERAGE DISPENSERS, COFFEE MACHINES AND NONCARBONATED |
| BEVERAGE DISPENSERS SHALL BE PROTECTED AGAINST BACKFLOW |
| PERR 2014 FBC-PLUMBING SECS.608.16.1 & 608.16.10. THESE |
| APPLIANCES ARE USUALLY UNDER CONTINUOUS PRESSURE AND A |
| ATMOSPHERIC VACUUM BREAKER AS CALLED OUT ON THE PLANS |
| DOES NOT MEET COMPLIANCE WITH THE NOTED CODE SECTIONS. |
| NONCARBONATED & CARBONATED BEVERAGE DISPENSERS, COFFEE |
| MACHINES, ETC. SHALL BE PROTECTED AGAINST BACKFLOW BY A |
| BACKFLOW PREVENTER CONFORMING TO ASSE 1022. |
| 6) SHT. P2.01 - # 25 SHOWS A 2 INCH DRAIN FROM A |
| "SCRUBBER" TO THE GREASE WASTE AND SHT. P4.01 SHOWS A 1 |
| INCH DRAIN FROM THE "SCRUBBER"". CLARIFY. SUBMIT |
| DETAILS / INFORMATION FOR THE SCRUBBER. |
| 7) SUBMIT FACTORY SIZING CALCULATIONS FOR THE GREASE |
| INTERCEPTOR. 2014 FBC - PLUMBING SEC.1003.2. |
| |