Plan Review Notes
Plan Review Notes For Permit 16061443
Permit Number 16061443
Review Stop P
Sequence Number 3
Notes
Date Text
2017-03-20 06:32:401) SHT. A7.41 - INDICATE ON THE PLANS THAT THE SHOWER
 SEAT IN ALTERNATE ROLL-IN SHOWER IS OF THE FOLDING
 TYPE. 2014 FBC-ACCESSIBILITY SEC.610.3. 2ND REQUEST.
 2) A LINT INTERCEPTOR IS REQUIRED FOR THE WASHING
 MACHINES PER 2014 FBC-PLUMBING SEC.1003.6. SUBMIT A
 DETAIL AND SIZING CALCULATIONS FOR THE UNIT. THE
 SUBMITTED RESPONSE NARRATIVE REFERS TO A DETAIL ON SHT.
 P5.01 BUT THERE IS NO DETAIL ON THIS PLAN AND I COULD
 NOT FIND A DETAIL ANYWHERE IN THE PLANS. 2ND REQUEST.
 3) SHT. P4.03 - SANITARY RISER # S/14 - 13TH FLOOR
 TOILET ROOM #1305 BY STAIR # 2 - THE SANITARY RISER
 DOEES NOT COMPLY WITH FBC 2014-PLUMBING SECS. 912 OR
 914 FOR A HORIZONTAL WET VET OR A CIRCUIT VENT. PLACING
 A VENT ON THE FIRST WATER CLOSET CONNECTED TO THE
 HORIZONTAL DRAIN WILLL CORRECT THIS ISSUE. 2ND REQUEST.
 4) SHT. P4.03 - SANITARY RISER S/14 - 7TH FLOOR KING
 SUITE AND FLOORS 8 - 11 - A MAXIMUM OF 4 FIXTURE UNITS
 ARE PERMITTED ON A 2 INCH WET VENT PER 2014
 FBC-PLUMBING SEC.912.3 & TABLE 912.3. THE RISER SHOWS 6
 FIXTURE UNITS ON A WET VENT.
 5) SHTS. P4.04 & P4.05 - WATER RISERS -WATER FILTERS,
 BEVERAGE DISPENSERS, COFFEE MACHINES AND NONCARBONATED
 BEVERAGE DISPENSERS SHALL BE PROTECTED AGAINST BACKFLOW
 PERR 2014 FBC-PLUMBING SECS.608.16.1 & 608.16.10. THESE
 APPLIANCES ARE USUALLY UNDER CONTINUOUS PRESSURE AND A
 ATMOSPHERIC VACUUM BREAKER AS CALLED OUT ON THE PLANS
 DOES NOT MEET COMPLIANCE WITH THE NOTED CODE SECTIONS.
 NONCARBONATED & CARBONATED BEVERAGE DISPENSERS, COFFEE
 MACHINES, ETC. SHALL BE PROTECTED AGAINST BACKFLOW BY A
 BACKFLOW PREVENTER CONFORMING TO ASSE 1022.
 6) SHT. P2.01 - # 25 SHOWS A 2 INCH DRAIN FROM A
 "SCRUBBER" TO THE GREASE WASTE AND SHT. P4.01 SHOWS A 1
 INCH DRAIN FROM THE "SCRUBBER"". CLARIFY. SUBMIT
 DETAILS / INFORMATION FOR THE SCRUBBER.
 7) SUBMIT FACTORY SIZING CALCULATIONS FOR THE GREASE
 INTERCEPTOR. 2014 FBC - PLUMBING SEC.1003.2.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW