2017-03-20 10:25:561) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE GAS
 REGULATORS. THE SUBMITTED NARRATIVE RESPONSE REFERS TO
 AN ATTACHED KITCHEN BROCHURE BY DEI. I COULD NOT FIND
 ANY BROCHURE FROM DEI. CLARIFY. 2014 FBC-FUEL GAS
 SECS.410.1, 410.2. 3RD REQUEST.
 2) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT AND APPLIANCES. GAS APPLIANCES REGULATED
 BY THE FUEL GAS CODE SHALL BE LISTED AND LABELED PER
 2014 FBC-FUEL GAS SEC.301.3. 2ND REQUEST.THE NARRATIVE
 RESPONSE REFERS TO A KITCHEN EQUIPMENT BROCHURE BY
 DEI.I COULD NOT FIND ANY SUCHBRROCHURE FROM DEI.
 CLARIFY.
 3) SHT. M2.01 & M2.02 - COMBUSTION AIR CALCULATIONS -
 WHERE COMBUSTION AIR IS MECHANICALLY SUPPLIED THROUGH
 AN HVAC SYSTEM, THE SYSTEM MUST DELIVER THE REQUIRED
 COMBUSTION AIR RATE ABOVE AND BEYOND ANY OUTDOOR AIR
 RATE SUPPLIED FOR VENTILATION OF THE OCCCUPIED
 SPACES.THE HVAC SYSTEM MUST ALSO BE INTERLOCKED WITH
 THE APPLIANCE(S) AS REQUIRED BY 2014 FBC FUEL GAS
 SEC.304.9.2. NEITHER CONTINUOUS OPERATION NOR PARALLEL
 OPERATION OF THE HVAC SYSTEM SATISFIES THE REQUIREMENT
 FOR A TRUE INTERLOCK AS REQUIRED BY 304.9.2. I CANNOT
 DETERMINE HOW THE REQUIREMENT FOR THE COMBUSTION AIR IN
 SEC. 304.9.3 HAS BEEN MET. CLARIFY.
 4) SHT.K1PRS SHOWS GAS APPLIANCE PBF-1 (DECK
 OVEN/PIZZA) AT 140 MBTU.I DO NOT SEE THIS APPLIANCE OR
 THE BTU VALUE ON THE GAS PLANS / RISER. SHOW ALL GAS
 APPLIANCES ON THE GAS RISER AND THE CORRESPONDING BTU
 LOAD. 2014 FBC-FUEL GAS SEC.402.2. THE NARRATIVE
 RESPONSE REFERS TO A KITCHEN EQUIPMENT BROCHURE BY
 DEI.I COULD NOT FIND ANY SUCHBRROCHURE FROM DEI.
 CLARIFY.
 5) SHT. P4.01 - I HAVE ADDED THE BTU LOAD OF EACH GAS
 APPLIANCE LISTED IN THE KEY NOTES 4 TIMES AND I STILL
 ARRIVE AT A TOTAL BTU LOAD OF 4363 MBTU'S. CLARIFY.
  
 THE FOLLOWING ITEMS WILL BE DEFERRED SUBMITTALS:
 1) SPECIFICATIONS FOR THE BOILER,VENT DETAILS,VENT
 PIPING, ETC.
 2) DETAILS FOR THE DRYER VENTS,VENT MATERIAL, ETC.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW