2017-03-14 16:00:22 | 718 SOUTH DIXIE HIGHWAY - 14 STORY HILTON |
| PERMIT #16061443 |
| 3RD ROUND REVIEW COMMENTS - FIRE DEPARTMENT |
| NOTE: UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY |
| REVIEW COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE |
| (2012 EDITION WITH FLORIDA AMENDMENTS.) |
| |
| REPEAT COMMENT (3RD REQUEST) - SHEET C-10: PER NFPA 24 |
| SECTION 6.2.1, ALL CONNECTIONS TO PRIVATE FIRE SERVICE |
| MAINS FOR FIRE PROTECTION SYSTEMS SHALL BE ARRANGED IN |
| ACCORDANCE WITH ONE OF THE FOLLOWING SO THAT THEY CAN |
| BE ISOLATED: |
| (1) A WALL POST INDICATOR VALVE |
| (2) A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING |
| VALVE NOT LESS THAN 40 FEET FROM THE BUILDING |
| (3) CONTROL VALVES INSTALLED IN A FIRE-RATED ROOM |
| ACCESSIBLE FROM THE EXTERIOR |
| (4) CONTROL VALVES IN A FIRE-RATED STAIR ENCLOSURE |
| ACCESSIBLE FROM THE EXTERIOR AS PERMITTED BY THE |
| AUTHORITY HAVING JURISDICTION |
| |
| SHEET A203, A204, A203A AND A204A APPEAR IN THE DRAWING |
| SET TWICE WITH DIFFERING FLOOR PLANS. ALSO NEWLY ADDED |
| SHEETS A203A AND A204A SHOW THE EMERGENCY GENERATOR ON |
| DIFFERING FLOORS. CHECK ALL MEPF SHEETS; SEVERAL |
| DUPLICATE SHEETS (PARTICULARLY ELECTRICAL) WITH OLD |
| FLOOR PLANS ARE IN THE REVISED SET OF DRAWINGS. |
| |
| SHEET E4.02: PER FFPC SECTION11.9 (NFPA 1) THE |
| FOLLOWING CONTROLS/INDICATORS COULD NOT BE LOCATED IN |
| THE EMERGENCY COMMAND CENTER: |
| |
| (4) STATUS INDICATORS AND CONTROLS FOR AIR-HANDLING |
| SYSTEMS |
| (5) CONTROLS FOR UNLOCKING STAIRWAY DOORS |
| SIMULTANEOUSLY |
| (8) FIRE PUMP STATUS INDICATORS |
| (9) GENERATOR SUPERVISION DEVICES AND MANUAL START AND |
| TRANSFER FEATURES |
| (11) CONTROLS REQUIRED FOR SMOKE CONTROL |
| |
| REPEAT COMMENT (2ND REQUEST) SHEET FP2.05: THE |
| SPRINKLERS PROTECTING THE FIRST FLOOR RESTAURANT AREA |
| ARE LOCATED 75 FEET ABOVE THE FLOOR BEING PROTECTED. |
| THIS ELEVATION DIFFERENCE AND SUSPENDED ARCHITECTURAL |
| FEATURES WILL CERTAINLY DELAY SPRINKLER ACTIVATION IF |
| ACTIVATION OCCURS AT ALL. HAS SMOKE/HEAT STRATIFICATION |
| BEEN EVALUATED FOR THIS TALL CEILING? WILL THE WATER |
| DROPLETS FROM STANDARD SPRAY SPRINKLERS BE ABLE TO |
| REACH THE SEAT OF THE FIRE OR WILL EVAPORATION BE A |
| FACTOR ALLOWING A FIRE IN THIS AREA GROW TO A SIZE THAT |
| CANNOT BE CONTROLLED BY THE CEILING SPRINKLERS? THIS |
| AREA NEEDS AN IN-DEPTH ENGINEERING ANALYSIS. |
| |
| SHEET K1EP: PROVIDE UL LISTING (OR EQUAL), APPLIANCE |
| SPECIFICATIONS AND INSTALLATION DATA FOR THE SOLID FUEL |
| COOKING EQUIPMENT. DATA SHALL INDICATE IF A SUPPRESSION |
| SYSTEM IS REQUIRED FOR THIS APPLIANCE. |
| |
| WESLEY JOLIN |
| ASSISTANT FIRE MARSHAL |
| WEST PALM BEACH FIRE RESCUE |