2016-12-21 10:45:201) SHT.A7.41 - THE ACCESSIBLE SHOWERS APPEAR TO BE OF
 THE ALTERNATE ROLL-IN TYPE.THE SEATS LOCATED IN THE
 HANDICAPPED ACCESSIBLE SHOWERS SHALL COMPLY WITH 2014
 FBC-ACCESS. SECS.610.3. THE SEAT SHALL EXTEND FROM THE
 ADJACENT SIDE WALL TO A POINT WITHIN 3 INCHES OF THE
 COMPARTMENT ENTRY. CLEARLY THE TYPE OF ROLL-IN SHOWER
 ON THE PLAN, STANDARD ROLL-IN TYPE OR ALTERNATE ROLL-IN
 TYPE.
 2) SHT.A7.41 - THE TOILET PAPER DISPENSERS SHALL COMPLY
 WITH 2014 FBC-ACCESS. SEC.604.9.6 ( 7 INCHES MINIMUM
 AND 9 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET
 MEASURED TO THE CENTERLINE OF THE DISPENSER). 2ND
 REQUEST.
 3) SHT.A7.41 - DETAIL #13 - THE SHOWER SEAT GRAB BAR
 ADJACENT TO THE SEAT SHALL BE A MAXIMUM OF 6 INCHES
 FROM THE BACK WALL PER 2014 FBC-ACCESS. SEC.608.3.3.
 3) A LINT INTERCEPTOR IS REQUIRED PER 2014 FBC-PLUMBING
 SEC.1003.6.SUBMIT A DETAIL AND SIZING CALCULATIONS.SEC
 1003.2. A SCREEN PLACED IN A TROUGH/TRENCH DRAIN DOES
 NOT MEET THE INTENT.
 4) SHT.P2.09 - STAIR # 1 - THERE IS A KEY NOTE #12 NEXT
 TO THE 4 INCH SANITARY LINE DOWN BUT THERE IS NO
 KEYNOTE #12 LISTED. CLARIFY.
 5) SHT. P4.02 - KEYNOTE #1 IS SHOWN AS A 2 INCH VENT AT
 POINT "S" AND ALSO AS A 3 INCH VENT AT POINT
 "B".CLARIFY. IS IT 2 INCH OR 3 INCH?
 6) SHT. P4.02 - THE URINAL IN THE MEN'S RESTROOM IS
 INSTALLED ON A VERTICAL WET VENT WHICH IS NOT PERMITTED
 PER 2014 FBC-PLUMBING SEC. 912.1.1 (SEE DEFINITION OF
 BATHROOM GROUP). THE URINAL SHALL BE INDIVIDUALLY
 VENTED.
 7) SHT.P4.01 - RISER S/2 - POINT "P" - THE VENT FROM
 THE STACK IS SHOWN AS 3 INCH, REDUCES TO 2 INCH AND
 THEN INCREASES TO 3 INCH AT THE CONNECTION TO RISER S/2
 ON SHT.P4.03 - CLARIFY.
 8) SHT. P4.03 - RISER S/14 - 13TH FLOOR TOILET ROOM
 #1305 BY STAIRS #2 - THE SANITARY RISER DOES NOT COMPLY
 WITH 2014 FBC-PLUMBING SECS.912 OR 914 FOR A HORIZONTAL
 WET VENT OR A CIRCUIT VENT.PLACING AN INDIVIDUAL VENT
 ON THE FIRST WATER CLOSET CONNECTED TO THE HORIZONTAL
 DRAIN WILL CORRECT THIS ISSUE.
 9) SHT. P4.03 - 7TH FLOOR KING SUITE - ONLY 4 FIXTURE
 UNITS ARE PERMITTED ON A 2 INCH WET VENT PER 2014
 FBC-PLUMBING SEC.912.3 & TABLE 912.3. SEE FLOORS #7-
 #12.
 10) SHT. P4.06 - WATER RISER #1 - BEVERAGE DISPENSERS,
 COFFEE MACHINES AND NONCARBONATED BEVERAGE DISPENSERS
 SHALL BE PROTECTED AGAINST BACKFLOW PER 2014
 FBC-PLUMBING SECS.608.16.1 & 608.16.10. I COULD NOT
 FIND THE NOTE ON THE PLAN. CLARIFY.
 11) SHT. P4.07 - DETAILS "A" &"B" - BOTH WATER RISERS
 INCLUDE "TYPICAL KING ROOM" VERBIAGE - CLARIFY.
 12) SHT. P4.07 - DETAIL "B" - IF THIS WATER RISER IS
 SUPPOSED TO BE THE "KING SUITE" A WATER CLOSET IS
 MISSING FROM THE RISER IN THE HALF BATH AND A LAVATORY
 IS MISSING FROM THE RISER IN THE FULL BATH.
 13) SUBMIT A CCOMPLETE WATER RISER FOR THE LAUNDRY
 ROOM.WPB AMEND. TO FBC SEC. 107.3.5.1.3.
 14) PLACE A NOTE ON THE SANITARY DRAWINGS THAT ALL
 FLOOR DRAINS SHALL BE EQUIPPED WITH TRAP PRIMERS. I
 CANNOT FIND THE NOTE AS STATED IN THE NARRATIVE. 2014
 FBC-PLUMBING SEC.1002.4.
 15) THE FUNNEL DRAINS RECEIVING THE DISCHARGE FROM THE
 ELEVATOR SUMPS SHALL BE EQUIPPED WITH TRAP PRIMERS.
 2014 FBC-PLUMBING SEC.1002.4.
  