2016-12-27 11:56:19GAS REVIEW
 1) SHOW THE DEVELOPED LENGTH OF THE PIPING FROM THE
 SECOND STAGE REGULATOR TO THE FURTHEST OUTLET. THIS
 DISTANCE IS USED FOR THE SIZING OF THE LOW PRESSURE
 SYSTEM.2ND REQUEST.
 2) SHT. P4.10 - THE BTU LOAD FOR THE TWO DOMESTIC
 BOILERS ADDS TO 1,500 MBTU BUT THE PLANS SHOW 1,700
 MBTU. CLARIFY. 2ND REQUEST.
 3) SHT. P4.10 - KEYNOTE #10 SHOWS TWO BOILERS AT 199
 MBTU EACH WHICH IS 398 MBTU BUT THE RISER SHOWS 798
 MBTU. CLARIFY.2ND REQUEST.
 4) MY CALCULATION OF BTU'S AT ONE SECTION OF THE GAS
 RISER IS 1,898 MBTU BUT THE PLAN SHOWS 2,498 MBTU.
 THERE IS ANOTHER SECTION WITH A BTU LOAD OF 3,698 MBTU
 AND MY CALCULATIONS ADD TO 3,098 MBTU. CLARIFY.2ND
 REQUEST.
 5) THE TOTAL BTU LOAD ON THE SYSTEM SHOULD BE 4,413
 MBTU. PLEASE CHECK THE CALCULATIONS.2ND REQUEST.
 6) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR THE
 GAS REGULATORS. FGC SEC. 410.1, 410.2.2ND REQUEST.THE
 NARRATIVE REFERS TO NOTE #13 ON SHT. P4.10 - NOTE #13
 REFERS TO THE VENTLESS PRESSURE REGULATOR.
 7) SUBMIT MANUF. SPECIFICATION SHEETS FOR THE ALL GAS
 EQUIPMENT AND APPLIANCES. APPLIANCES REGULATED BY THE
 CODE SHALL BE LISTED AND LABELED. FGC 301.3.
 8) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR ALL GAS
 FIRED EQUIPMENT (KITCHEN EQUIPMENT, DRYERS, POOL
 EQUIPMENT, BOILERS, ETC.) PER FGC SEC. 304. SEE FGC
 SEC. 304.9.3 FOR COMBUSTION AIR BEING SUPPLIED BY
 MECHANICAL SYSTEMS.
 9) SHT. M2.01 - KITCHEN GAS APPLIANCE CALCULATIONS - IN
 ACCORDANCE WITH 2014 FBC-FUEL GAS SEC.304.9.3 - THE
 MAKEUP AIR FOR THE EXHAUST FOR THE HOOD CANNOT BE USED
 TO SUPPLY COMBUSTION AIR TO THE APPLIANCES.
 10) SUBMIT SPECIFICATIONS FOR THE BOILER, VENT DETAILS,
 VENT PIPING, ETC. WPB AMEND. TO FBC SEC. 107.2.1.
 11) SUBMIT DETAILS FOR DRYER VENTS, TERMINATION POINTS,
 VENT MATERIAL, ETC. WPB AMEND. TO FBC SEC. 107.2.1.
 12) SHT. K1 PRS SHOWS GAS APPLIANCE PBF-1 (DECK
 OVEN/PIZZA) AT 140 MBTU. I DO NOT SEE THIS APPLIANCE OR
 THE BTU VALUE ON THE GAS PLANS. CLARIFY.
 13) SUBMIT SPECS .FOR THE PVC VENTS FOR THE BOILERS TO
 CONFIRM PVC IS APPROVED.SHOW THE HEIGHT ABOVE THE ROOF,
 ANCHORING DETAILS (IF APPLICABLE), COMPLY WITH 2014
 FBC-FUEL GAS SEC.
 14) SUBMIT DETAILS FOR THE DRYER VENTS, VENT MATERIAL,
 HEIGHT ABOVE ROOF, ANCHORING DETAILS (IF APPLICABLE).
 IF PVC IS USED, SUBMIT DETAILS FROM DRYER MANUF. TO
 SHOW PVC IS APPROVED TO BE USED.ROOF THE RESPONSE
 NARRATIVE REFERS TO SHT. M2.10, NOTES #2,3,& 4. THESE
 NOTES HAVE NOTHING TO DO WITH THE DRYER VENTS. THE
 LAUNDRY IS ON THE 2ND FLOOR, NOT THE ROOF.
 15) INDICATE THE POOL/SPA BOILERS ON THE PLANS.WPB
 AMEND. TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805 PLUMBING PLAN REVIEW