Plan Review Notes
Plan Review Notes For Permit 16061443
Permit Number 16061443
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2016-12-08 11:16:43718 SOUTH DIXIE HIGHWAY - 14 STORY HILTON
 PERMIT #16061443
 REVIEW COMMENTS - FIRE DEPARTMENT
 NOTE: UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY
 REVIEW COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE
 (2012 EDITION WITH FLORIDA AMENDMENTS.)
  
  
 REPEAT COMMENT - SHEET C-10: THE FIRE LINE BACKFLOW
 PREVENTERS CAN BE USED TO CONTROL THE WATER SUPPLY. THE
 ADDITIONAL PIVS SHOULD BE ELIMINATED. ALSO PER NFPA 24
 SECTION 6.2.1, ALL CONNECTIONS TO PRIVATE FIRE SERVICE
 MAINS FOR FIRE PROTECTION SYSTEMS SHALL BE ARRANGED IN
 ACCORDANCE WITH ONE OF THE FOLLOWING SO THAT THEY CAN
 BE ISOLATED:
 (1) A WALL POST INDICATOR VALVE
 (2) A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING
 VALVE NOT LESS THAN 40 FEET FROM THE BUILDING
 (3) CONTROL VALVES INSTALLED IN A FIRE-RATED ROOM
 ACCESSIBLE FROM THE EXTERIOR
 (4) CONTROL VALVES IN A FIRE-RATED STAIR ENCLOSURE
 ACCESSIBLE FROM THE EXTERIOR AS PERMITTED BY THE
 AUTHORITY HAVING JURISDICTION
  
 SHEET A1.14: PLANS INDICATE A COMMON PATH OF TRAVEL
 DISTANCE OF 115 FEET FROM STORAGE #405. THE FIRE CODE
 LIMITS THE COMMON PATH OF TRAVEL TO 100 FEET IN STORAGE
 OCCUPANCIES.
  
 REPEAT COMMENT: NO 3 FOOT HIGH PONY WALL PROVIDED. THE
 DETAILS ON THE ARCHITECTURAL AND FIRE PROTECTION
 DRAWINGS ARE INSUFFICIENT TO ENSURE GLAZING DESIGN,
 MULLION DEPTHS AND SPRINKLER COVERAGE IS CORRECT.
 ORIGINAL COMMENT - SHEET A1.12 & A8.05: PLANS INDICATE
 THE USE OF TYCO WINDOW SPRINKLERS (WINDOW TYPES UU, WW
 & YY) IN LIEU OF FIRE RATED GLAZING. PROVIDE A
 SPRINKLER INSTALLATION WINDOW DETAIL ACCORDING TO THE
 MANUFACTURER'S LISTING CRITERIA. THE SPRINKLER LISTING
 DETAILS ARE VERY PARTICULAR AND REQUIRE SPRINKLERS ON
 BOTH SIDES OF THE GLAZING. THE MAXIMUM GLAZING HEIGHT
 IS LIMITED TO 13 FEET. THE GLASS CURTAIN WALL NEEDS TO
 BE ATTACHED TO A THREE FOOT HIGH PONY WALL TO KEEP
 COMBUSTIBLE MATERIALS AT LEAST TWO-INCHES AWAY FROM THE
 GLAZING. VERTICAL MULLIONS SHALL BE OF A DEPTH THAT
 PREVENTS COLD SOLDERING OF ADJACENT SPRINKLERS. THE
 SPRINKLER DESIGN SHOULD INDICATE WHICH WINDOW SPRINKLER
 MODEL WILL BE USED (HORIZONTAL SIDEWALL OR PENDENT
 VERTICAL SIDEWALL) AS THIS WILL AFFECT HOW DEEP THE
 VERTICAL MULLIONS NEED TO BE. A MULLION WILL ACT AS A
 BAFFLE WHEN THE MULLION EXTENDS TO THE BACK OF
 SPRINKLER DEFLECTOR (PENDENT VERTICAL SIDEWALL) OR WHEN
 THE MULLION EXTENDS TO THE SPRINKLER WRENCH FLAT
 (HORIZONTAL SIDEWALL).
  
 SHEET P2.04: PIPE SHALL NOT BE ROUTED THROUGH THE FIRE
 RATED EXIT STAIR ENCLOSURE OF STAIR #3. THIS IS
 PROHIBITED BY NFPA 101.
  
 REPEAT COMMENT: THE GREASE DUCT DISCHARGE IS NOT PER
 NFPA 96 SECTION 7.8.3. THE GENERATOR AIR INTAKE IS
 DIRECTLY ABOVE THE GREASE DUCT EXHAUST. PER NFPA 96 THE
 CLOSEST POINT OF ANY AIR INTAKE OR OPERABLE DOOR OR
 WINDOW ABOVE THE PLANE OF THE EXHAUST TERMINATION SHALL
 BE A MINIMUM OF 10 FEET IN DISTANCE, PLUS 3-INCHES FOR
 EACH 1 DEGREE FROM HORIZONTAL, THE ANGLE OF DEGREE
 BEING MEASURED FROM THE CENTER OF THE EXHAUST
 TERMINATION TO THE CENTER OF THE AIR INTAKE OR OPERABLE
 DOOR OR WINDOW, AS INDICATED IN FIGURE 7.8.3.
 ORIGINAL COMMENT - SHEET M2.01: THE THREE KITCHEN
 EXHAUST FANS INDICATE SIDEWALL DISCHARGE; HOWEVER, THE
 AIR LOUVERS FOR THE GARAGE APPEAR TO BE LOCATED WITHIN
 32 FEET OF THE GREASE DUCT DISCHARGE PER NFPA 96
 SECTION 7.8.3.
  
 SHEET FP2.02: PROVIDE STANDPIPE AND HOSE VALVES IN NEW
 STAIR #3.
  
  
 SHEET FP2.02: HOW WILL THE TYCO WINDOW SPRINKLERS ON
 THE WEST SIDE OF THE GLAZING BE ATTACHED TO THE
 STRUCTURE? TWO SPRINKLERS ARE LOCATED ON THE VERTICAL
 MULLION. WHAT IS THE DEPTH OF THE MULLION AND HOW WILL
 BE ENSURED THAT THE ENTIRE SURFACE OF THE GLAZING IS
 WETTED? WHAT WINDOW SPRINKLER MODEL IS BEING USED
 (PENDENT VERTICAL SIDEWALL OR HORIZONTAL SIDEWALL)?
 SPRINKLER SCHEDULE INDICATES THE USE OF A VIKING
 SPRINKLER.
  
 SHEET FP2.05: THE SPRINKLERS PROTECTING THE FIRST FLOOR
 RESTAURANT AREA ARE LOCATED 75 FEET ABOVE THE FLOOR
 BEING PROTECTED. THIS ELEVATION DIFFERENCE AND
 SUSPENDED ARCHITECTURAL FEATURES WILL CERTAINLY DELAY
 SPRINKLER ACTIVATION IF ACTIVATION OCCURS AT ALL. HAS
 SMOKE/HEAT STRATIFICATION BEEN EVALUATED FOR THIS TALL
 CEILING? WILL THE WATER DROPLETS FROM STANDARD SPRAY
 SPRINKLERS BE ABLE TO REACH THE SEAT OF THE FIRE OR
 WILL EVAPORATION BE A FACTOR ALLOWING A FIRE IN THIS
 AREA GROW TO A SIZE THAT CANNOT BE CONTROLLED BY THE
 CEILING SPRINKLERS? THIS AREA NEEDS AN IN-DEPTH
 ENGINEERING ANALYSIS.
  
 RESPONSE COMMENT - NOTE #32 ON SHEET FP0.00 INDICATES
 THE CONTRACTOR IS RESPONSIBLE FOR PRESSURE CONTROL.
 CONCEPTUAL SYSTEM PRESSURE CONTROL WILL NEED TO BE
 SHOWN TO A DETERMINED FLOOR LEVEL AND BE PROVIDED ON
 THE FIRE PROTECTION ENGINEERING DOCUMENTS WHILE ACTUAL
 PRESSURE CONTROL WILL NEED TO BE SHOWN THE SPRINKLER
 SHOP DRAWINGS.
 ORIGINAL COMMENT - SHEET FP4.01: SPRINKLER AND
 STANDPIPE SYSTEM PRESSURES APPEAR TO EXCEED 165PSIG AND
 175PSIG RESPECTIVELY WITH NO MEASURES OF CONTROL.
  
 SHEET K1EP: PLAN INDICATES THE USE OF A WOOD FIRED
 PIZZA OVEN. HOW IS THIS OVEN BEING PROTECTED IN
 ACCORDANCE WITH NFPA 96 FOR SOLID FUEL COOKING
 OPERATIONS CONCERNING VENTING, FIRE SUPPRESSION, SOLID
 FUEL STORAGE, EXHAUST VENT CLEANING/MAINTENANCE,
 FLEXIBLE WATER HOSE, ASH DISPOSAL? SUBMIT PRODUCT AND
 INSTALLATION MANUAL FOR WOOD FIRED PIZZA OVEN.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  