2016-12-14 08:32:15 | 2NDL ELECTRICAL PLAN REVIEW |
| |
| APPLICABLE CODES IN EFFECT: |
| FLORIDA BUILDING CODE 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| EDITION |
| NFPA 70- 2011 NEC |
| PREVIOUS COMMENTS: |
| |
| 1. PROVIDE A BLOCK NOTE INDICATING THE REQUIRED |
| SEPARATE PERMITS AND DATA CUT SHEET SUBMITTALS FOR ALL |
| SITE LIGHTING AND ASSOCIATED EQUIPMENT. A NOTE WILL |
| SUFFICE. (PLEASE PROVIDE ON SHEET E0.00) |
| 2. GENERAL NOTES- PROVIDE A BLOCK NOTE INDICATING THE |
| REQUIRED SEPARATE PERMITS AND DATA CUT SHEET SUBMITTALS |
| FOR GENERATOR, FIRE PUMP ALL LOW VOLTAGE SYSTEMS TO |
| INCLUDE BUT NOT LIMITED TO FIRE ALARM, ACCESS CONTROLS, |
| CCTV, PHONE AND DATA, SIGNAGE, WIRELESS SYSTEMS, CAR |
| CHARGING STATIONS, CO2 FANS, POOL, KITCHEN HOODS, CAR |
| LIFTS ETC. A NOTE WILL SUFFICE. (PLEASE PROVIDE ON |
| SHEET E0.00) |
| 3. SHOW AT THE MAIN ELECTRICAL ROOM A NOTE TO REQUIRE |
| PANIC HARDWARE AND DOORS TO SWING IN THE DIRECTION OF |
| EGRESS. NEC 110.26C2 (REVISED DOOR STILL SHOWN SWINGING |
| IN, PLEASE CORRECT SHEET E2.00) |
| 4. NOTE THAT PER NEC 230.2 THIS PROJECT MEETS THE |
| REQUIREMENTS FOR MULTIPLE SERVICES DUE TO CAPACITY |
| LIMITS. REGARDLESS, SPECIAL PERMISSION FROM AHJ TO BE |
| GRANTED PER DESIGN SHOWN. PROVIDE IN WRITING A REQUEST |
| PER CODE SECTION CITED TO AHJ. GENERAL NOTES TO BE |
| PLACED FOR FIRST RESPONDER?S SAFETY. FIRE REVIEW MIGHT |
| REQUIRE OTHER MEANS TO SHUNT SERVICES. FBC 107.3.5 |
| (PLEASE LABEL MAINS 1 OF 4, 2 OF 4 ETC. AS ONE SERVICE |
| IS PROVIDED FRON VAULT AND 4 MAINS ARE SHOWN) |
| 5. PROVIDE FROM UTILITY PROVIDER (FPL), ACTUAL |
| AVAILABLE FAULT CURRENT AT THE VAULT TRANSFORMERS. FBC |
| 107.3.5 (PENDING) |
| 6. PROVIDE AIC CALCULATION PER NEC 110.10- FBC 107.3.5 |
| (PENDING) |
| 7. PROVIDE A NOTE/SIGN TO INDICATE THE REQUIREMENTS NEC |
| 110.24 THE MAX. AVAILABLE FAULT CURRENT SHALL BE |
| DURABLY MARKED AND DATED ON ALL ELECTRICAL APPARATUS |
| AND NEC 110.16 ARC-FLASH HAZARD WARNING LABELS |
| REQUIRED. (PROVIDE NOTE ON SHEET E5.01) |
| 8. PER FBC EC 405.7.3- SHOW VOLTAGE DROP CALCULATIONS |
| FOR FEEDERS AND BRANCH CIRCUITS. (ADDRESSED) |
| 9. MULTIPLE AREAS NEED TO SHOW GFCI PROTECTED PER NEC |
| 210.8B5- IF WITHIN 6FT OF SINK ALL TO BE GFCI. (PLEASE |
| CORRECT SHEET E- 2.02 AND 2.09, MENS RESTROOM TO GFCI |
| PROTECTED CIRCUIT L-41 AND EMPLOYEE BREAKROOOM, SEE |
| CIRCUITS L-26 AND L-20. |
| 10. PER FBC EC 405.7- 50% OF ALL RECEPTACLES 125V, 15 |
| AND 20A MUST BE AUTOMATICALLY CONTROLLED WHERE |
| INSTALLED IN PRIVATE OFFICES, OPEN OFFICES, AND |
| COMPUTER CLASSROOMS. THIS INCLUDES THOSE INSTALLED IN |
| MODULAR PARTITIONS. SHOW COMPLIANCE. ENERGY INPUT DATA |
| REPORT NOT PROVIDED (ADDRESSED) |
| 11. LABEL GFCI ALL RECEPTACLES IN THE MEN?S AND WOMEN?S |
| LOCKER ROOMS PER NEC 210.8B7 (ADDRESSED) |
| 12. LABEL GFCI ALL RECEPTACLES WITHIN 6FT OF SINKS, |
| LAUNDRY, KITCHEN AND PREP AREA AND MULTIPLE AREAS NEC |
| 210.8B5 (ADDRESSED) |
| 13. SHEET E2.01 AND ABOVE REFLECTS DRINKING FOUNTAINS, |
| LABEL ALL RECEPTACLES TO BE GFCI PROTECTED NEC 422.52 |
| MULTIPLE LOCATIONS- (SEE CIRCUIT RL-14 D/F LABEL GFCI |
| PROTECTED) |
| 14. ADDRESS ALL FIRE REVIEWER COMMENTS RELATED TO |
| ELECTRICAL. FBC 107.3.5 (PENDING) |
| 15. AT ROOFTOP AND EXTERIOR LOCATIONS LABEL MULTIPLE |
| RECEPTACLES TO BE WP/GFCI RATED. NEC 406.9B (ADDRESSED) |
| 16. ALL GUEST UNITS TO BE PROVIDED WITH TAMPER |
| RESISTANT RECEPTACLES. PROVIDE A NOTE. NEC 406.13 |
| (ADDRESSED) |
| 17. CLARIFY VERIFY ENTIRE RISER DIAGRAM. NOTES DO NOT |
| MATCH, SEE ITEM15?? PLEASE ID ELECTRICAL ONE LINE WITH |
| SERVICE AND FEEDER CONDUCTOR SIZES, ALL INFO NEEDED ON |
| ONE LINE. FBC 107.3.5 (ADDRESSED) |
| 18. CLARIFY GROUNDING ELECTRODE CONDUCTOR SIZE FOR |
| BUILDING STEEL, WATER ETC. NEC 250 (ADDRESSED) |
| 19. PROVIDE A NOTE FOR FIRE PUMP FEEDER CONDUCTORS TO |
| BE 2HR PROTECTED. NEC 695.6A2CD (ADDRESSED) |
| 20. PANEL SCHEDULE HAS MULTIPLE DISCREPANCIES, SEE |
| PANEL H FOR EXAMPLE, SHOWS 125A TRIP BUT TRANSFORMER |
| SCHEDULE SHOWS 110A TRIP, WILL NEED TO CORRELATE THIS |
| AND MULTIPLE OTHERS. ELEVATOR BREAKER FEEDER CONDUCTOR |
| UNDERSIZED BASED ON TRIP RATING 110A. ALUMINUM #4 |
| SELECTED?? SHUNT TRIP ? REVISIT PANELS ENTIRELY FOR |
| COMPLIANCE AND CORRELATION. NEC 240, NEC 310.15B16 FBC |
| 107.3.5 MINIMUM PLAN REVIEW (ADDRESSED) |
| 21. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL |
| FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS |
| REGARDING THIS PROJECT. |
| |
| NEW COMMENTS DUE TO ENTIRELY REVISED SHEET |
| |
| 1. SHEET E2.00- PROVIDE A NOTE TO MAINTAIN BURIAL |
| DEPTHS AND A WARNING RIBBON PER NEC 300.5 FOR ALL |
| UNDERGROUND CONDUITS |
| 2. E-201A- ELEC. ROOM SHOULD NOT BE CONTROLLED |
| AUTOMATICALLY BY SENSOR. PROVIDE SWITCH IN ALL ROOMS |
| WITH PANELBORDS, MCC SWITHCHBOARDS ETC PER NEC |
| 110.26(D) |
| 3. E-2.02- CLARIFY ELEVATOR MACHINE ROOMS RECEPTACLE |
| AND LIGHTING BRANCH CIRCUITS. PER NEC 620.23 A SEPERATE |
| BRANCH CIRCUIT DEDICATED FOR THIS AREA MUST BE |
| PROVIDED. NO OTHER OUTLETS TO BE ON THESE CIRCUITS. |
| E/M/R ON SHEET E2.09 HAS SAME SCENARIO. PLEASE CORRECT. |
| 4. E-5.01- PLEASE PROVIDE THE SELECTIVE COORDINATION |
| STUDY, WHICH CAN BE PROVISO, |
| |
| |
| VALENTINO PEREZ |