2016-12-14 16:28:42 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16061443 |
| ADD: 718 S. DIXIE HWY. / CANOPY BY HILTON |
| CONT: TBD/ TO BE DETERMINED |
| TEL: 561-718-5987 / MARGARET LEON |
| E-MAIL: MLEONDADLP.COM |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2ND REVIEW |
| DATE: TUES. DEC.13/2016 |
| ACTION: DENIED |
| |
| 1) COMPLIED. 13 STORIES INCLUDING THE HABITABLE POOL, |
| POOL DECK AND A2 DELI/ RESTAURANT AREAS. |
| |
| 2) NOTICE: ART IN PUBLIC PLACES. |
| FOR CONTACT INFORMATION PLEASE CONTACT: |
| MS. SYBILLE WELTER |
| ART IN PUBLIC PLACES COORDINATOR |
| TEL: 822-1515 |
| E-MAIL: [email protected] |
| WEBSITE: WPB.ORG/AIPP/ |
| |
| |
| 3) 2ND REQUEST, TO BE SUBMITTED WHEN CONTRACTOR SUBMITS |
| FOR PERMIT. THIS MAIN BUILDING PERMIT WILL INCLUDE THE |
| FEES FOR THE MECHANICAL, ELECTRICAL, PLUMBING & ROOFING |
| PERMITS. WHEN THE GENERAL CONTRACTOR COMES IN FOR A |
| BUILDING PERMIT WITH THE SIGNED PERMIT APPLICATION FORM |
| BY THE QUALIFIER AND OWNER AND BRINGS IN THE LISTED |
| SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE |
| QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND |
| LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE |
| FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN |
| LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR |
| EACH PERMIT. |
| |
| ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, EXHAUST |
| HOODS, ANSUL SYSTEMS OR ALTERNATIVE AUTOMATIC |
| FIRE-EXTINGUISHING SYSTEMS , WALK IN COOLERS & |
| FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL |
| TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED |
| SUB-PERMITS, AWNING, CANOPY, FENCE, LANDSCAPE , |
| IRRIGATION, TEST PILE, AUGER CAST PILE AND OR |
| FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE |
| REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT. |
| PLEASE LIST AND SUBTRACT THESE LINE ITEMS AND THEIR |
| VALUE FROM THE OVERALL BUILDING VALUE OF |
| $33,000,000.00. THE REMAINING BALANCE WILL BE |
| AFFECTIVELY THE VALUE OF THE BUILDING YOU WILL BE |
| PAYING FOR THIS PERMIT. THE BUILDING DOES NOT WANT TO |
| COLLECT TWICE FOR THE VALUE OF THESE SUB-PERMITS NOT |
| COVERED UNDER THE PRIME OR MASTER PERMIT. |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION 108.3 BUILDING PERMIT VALUATION. |
| |
| 4) SEMI-COMPLIED. PLEASE SHOW COMPLIANCE BY THE 2014 |
| FBC-ENERGY CODE. SEE MECHANICAL COMMENTS, THERE ARE |
| NUMEROUS OMISSIONS AND INCONSISTENCIES SEE MECH. |
| COMMENT # 1. |
| |
| 5) THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING. |
| THRESHOLD BUILDING / FL S. S. 553.71(7) ?THRESHOLD |
| BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN |
| (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN |
| ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE |
| FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN |
| AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| PERSONS. |
| |
| 5A) COMPLIED. 109.3.6.1 THRESHOLD INSPECTION PLAN. |
| |
| 5B) SEMI-COMPLIED. THE SUBMITTED FORMS WERE |
| SEMI-COMPLETED, SHEET 3 OF 6 MISSING THE SPECIAL |
| INSPECTOR SIGNATURE, DATE AND NOTARY NOTED SEE PREVIOUS |
| PAGE. SIGNATURE FROM THE SPECIAL INSPECTOR PAGE 3 OF 6 |
| AND HAVE THE JOBSITE INSPECTOR REFILE THE FORM SO ALL |
| THE SIGNATURES ARE ON THE SAME SHEET. |
| SHEET 5 OF 6 THERE IS NO CONTRACTOR SIGNATURE NOR |
| NOTARY WORK COMPLETED. THIS SHEET WE WILL ACCEPT THE |
| BOTTOM SIGNATURE AND SEAL OF THE ENGINEER OF RECORD. |
| THRESHOLD INSPECTOR FORMS: WPB AMENDMENT 109.3.6.2 |
| W.P.B. CONSTRUCTION SERVICES DEPARTMENT. |
| |
| |
| 5C) COMPLIED. ARCHITECTURAL AND STRUCTURAL SHEETS. |
| THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B. AMENDMENT |
| 110.3.7.4.4/ 633 FLORIDA STATUTE. |
| |
| 5D) THE SPECIAL INSPECTORS ONSITE REPRESENTATIVE MARK |
| PINA HAS PRODUCED A RESUME? BUT THE RESUME DOES NOT |
| INCLUDE ANY POST TENSION SLAB INSPECTION HISTORY. |
| BEFORE THIS INSPECTOR CAN BE APPROVED AS THE PRIMARY |
| JOBSITE INSPECTOR, THERE WILL NEED TO SHOW A HISTORY OF |
| THIS TYPE OF INSPECTION. 61G15-35.004. |
| |
| WILL THERE BE MORE THAN ONE REPRESENTATIVE FROM THE |
| ENGINEERING COMPANY DOING THE STRUCTURAL THRESHOLD |
| INSPECTIONS? |
| |
| |
| 1ST ROUND OF COMMENTS. FOR THE SPECIAL INSPECTOR PLEASE |
| PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS |
| PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL |
| CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL |
| OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER THE |
| RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED. |
| |
| 5E) 2ND REQUEST. THE CONTRACTOR WILL PRODUCE A JOB |
| SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION. |
| THRESHOLD INSPECTION FORMS , GUIDELINES AND POLICIES |
| FOR PROJECTS WERE E-MAILED TO: |
| [email protected], PLEASE NOTE THIS E-MAIL ADDRESS CAME |
| BACK UNDELIVERABLE. 07/14/2016 11:35 AM. |
| [email protected] |
| |
| 5F) NOTICE ONLY. FOR DIGITAL PLANS, AFTER PERMIT |
| ISSUANCE, PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE |
| PERMIT BEING ISSUED, THE PERMIT LIBRARIAN WILL THEN |
| E-MAIL YOU THE APPROVED AND BATCH STAMPED PLANS SO YOU |
| MAY PRINT YOUR PLANS, TWO SETS OF PLANS WILL NEED TO BE |
| PRINTED IN COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE |
| OTHER FOR THE MEP INSPECTORS OTHER PLANS YOU WISH TO |
| PRINT MAYBE IN BLACK & WHITE.. |
| 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD |
| BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS |
| CONCERNING SPECIAL INSPECTORS. |
| |
| 5G) PROVISO: 110.3.7.4.3 ALL SHORING AND RESHORING |
| PROCEDURES, PLANS AND DETAILS SHALL BE SUBMITTED TO THE |
| ENFORCEMENT AGENCY FOR RECORDKEEPING. EACH SHORING AND |
| RESHORING INSTALLATION SHALL BE SUPERVISED, INSPECTED |
| AND CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING |
| DOCUMENTS BY THE CONTRACTOR. |
| 5H) PLEASE CALL THE CITY OF WEST PALM BEACHS AUTOMATED |
| TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL |
| BUILDING INSPECTIONS FOR AUDITING OF JOBSITE |
| INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6 |
| MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. |
| |
| 5H) INFORMATIONAL NO ACTION REQUIRED. 109.3.6 THRESHOLD |
| BUILDINGS, OPERATING GUIDELINES FOR THRESHOLD |
| INSPECTORS #26. ASSURE THAT THE DESIGNER HAS REQUIRED |
| ON THE PLANS OR SPECIFICATIONS ONE MATERIAL, APPROVED |
| FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND CEILINGS. |
| |
| 6) 2ND REQUEST, IN THE PROCESS OF EITHER UNITY OF TITLE |
| OR REPLAT. SHEET C-01 INDICATES THE PROPOSED SITE IS |
| MADE UP OF 4 LOTS. UNDER THE 2014 FBC-B TABLE 602, |
| BUILDINGS CANNOT BE BUILT OVER PROPERTY LINES. EITHER A |
| REPLAT OF THE 4 LOTS WILL NEED TO OCCUR OR A UNITY OF |
| TITLE. |
| UNITY OF TITLE. THE PROPOSED BUILDING STRUCTURE |
| TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE LOTS |
| WHICH COMBINE TO FORM 'THE SITE'. A 'UNITY OF TITLE' |
| SHALL BE RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A |
| COPY OF THE RECORDED 'UNITY OF TITLE' DOCUMENT SO THAT |
| FBC TABLE 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED |
| NOT APPLICABLE. SEE WEBSITE FOR APPLICATION: |
| HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP |
| "APPLICATION FOR UNITY OF TITLE" |
| HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45 |
| -38-UNITYOFTITLE3.PDF |
| VINCENT J NOEL |
| SURVEYOR/REAL ESTATE SUPERVISOR |
| ENGINEERING SERVICES DEPARTMENT |
| 401 CLEMATIS STREET |
| WEST PALM BEACH, FL 33401 |
| PHONE: 494-1040 EXT: 1096 |
| FAX: 494-1116 |
| E-MAIL: [email protected] |
| ********************************************* |
| MANUEL JULIAN GONZALEZ |
| ENGINEERING PROJECT COORDINATOR |
| ENGINEERING SERVICES DEPARTMENT |
| 401 CLEMATIS STREET, 4TH FLOOR |
| WEST PALM BEACH, FL 33401 |
| (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) |
| MAIN PHONE: (561) 822-1200 |
| DIRECT: (561) 494-1085 |
| FAX: (561) 494-1116 |
| MOBILE: (561) 644-7301 |
| EMAIL: [email protected] |
| WWW.WPB.ORG/ENGINEERING |
| |
| 7) PERIMETER FENCING UNDER A SEPARATE PERMIT. PLEASE |
| PROVIDE COMPLIANCE WITH: 2014 FBC-B 3306.5 BARRIERS. |
| BARRIERS SHALL BE A MINIMUM OF 8 FEET (2438 MM) IN |
| HEIGHT AND SHALL BE PLACED ON THE SIDE OF THE WALKWAY |
| NEAREST THE CONSTRUCTION. BARRIERS SHALL EXTEND THE |
| ENTIRE LENGTH OF THE CONSTRUCTION SITE. |
| |
| 8) 2014 FBC0B 3306.2 WALKWAYS. A WALKWAY SHALL BE |
| PROVIDED FOR PEDESTRIAN TRAVEL IN FRONT OF EVERY |
| CONSTRUCTION AND DEMOLITION SITE UNLESS THE APPLICABLE |
| GOVERNING AUTHORITY AUTHORIZES THE SIDEWALK TO BE |
| FENCED OR CLOSED. WALKWAYS SHALL BE OF SUFFICIENT WIDTH |
| TO ACCOMMODATE THE PEDESTRIAN TRAFFIC, BUT IN NO CASE |
| SHALL THEY BE LESS THAN 4 FEET (1219 MM) IN WIDTH. |
| WALKWAYS SHALL BE PROVIDED WITH A DURABLE WALKING |
| SURFACE. WALKWAYS SHALL BE ACCESSIBLE IN ACCORDANCE |
| WITH CHAPTER 11 AND SHALL BE DESIGNED TO SUPPORT ALL |
| IMPOSED LOADS AND IN NO CASE SHALL THE DESIGN LIVE LOAD |
| BE LESS THAN 150 POUNDS PER SQUARE FOOT (PSF). WILL THE |
| WALKWAYS ON THE SOUTH SIDE OF TRINITY PLACE BE CLOSED? |
| |
| 9) 2014 FBC-B 3306.7 COVERED WALKWAYS. COVERED WALKWAYS |
| SHALL HAVE A CLEAR HEIGHT OF NOT LESS THAN 8 FEET (2438 |
| MM) AS MEASURED FROM THE FLOOR SURFACE TO THE CANOPY |
| OVERHEAD. ADEQUATE LIGHTING SHALL BE PROVIDED AT ALL |
| TIMES. COVERED WALKWAYS SHALL BE DESIGNED TO SUPPORT |
| ALL IMPOSED LOADS. IN NO CASE SHALL THE DESIGN LIVE |
| LOAD BE LESS THAN 150 PSF FOR THE ENTIRE STRUCTURE. |
| |
| 10) COMPLIED. POLLUTION PREVENTION PLAN. 2014 FBC-B |
| 3307. |
| |
| 11) PROVISO: DEFERRED SUBMITTAL . 2014 FBC-B 3306.9 |
| ADJACENT TO EXCAVATIONS. STRUCTURAL NOTES S1.01. |
| |
| 11A) PROVISO: DEFERRED SUBMITTAL. STRUCTURAL NOTES |
| S1.01 AND SOILS REPORT BY LANGAN ENGINEERING SOILS |
| REPORT MAY 21/ 2015. 2014 FBC-B 3307.1 PROTECTION |
| REQUIRED. ADJOINING PUBLIC AND PRIVATE PROPERTY SHALL |
| BE PROTECTED FROM DAMAGE DURING CONSTRUCTION AND |
| DEMOLITION WORK. PROTECTION SHALL BE PROVIDED FOR |
| FOOTINGS, FOUNDATIONS, PARTY WALLS, CHIMNEYS, SKYLIGHTS |
| AND ROOFS. WITH THE EXCAVATION AND AUGER CAST PILE HOW |
| WILL THE BUILDING TO THE SOUTH BE PROTECTED FROM |
| SETTLEMENT? |
| |
| 11B) COMPLIED. NOTED ON PLAN. 2014 FBC-B 3307.1 THE |
| PERSON MAKING OR CAUSING AN EXCAVATION TO BE MADE SHALL |
| PROVIDE WRITTEN NOTICE TO THE OWNERS OF ADJOINING |
| BUILDINGS ADVISING THEM THAT THE EXCAVATION IS TO BE |
| MADE AND THAT THE ADJOINING BUILDINGS SHOULD BE |
| PROTECTED. SAID NOTIFICATION SHALL BE DELIVERED NOT |
| LESS THAN 10 DAYS PRIOR TO THE SCHEDULED STARTING DATE |
| OF THE EXCAVATION. |
| |
| 12) COMPLIED. NOTED ON PLAN. WHEN EXCAVATING WILL THE |
| EXCESS SOILS BE STORED ON SITE? 2014 FBC-B 3304.1.2 |
| SURCHARGE. NO FILL OR OTHER SURCHARGE LOADS SHALL BE |
| PLACED ADJACENT TO ANY BUILDING OR STRUCTURE UNLESS |
| SUCH BUILDING OR STRUCTURE IS CAPABLE OF WITHSTANDING |
| THE ADDITIONAL LOADS CAUSED BY THE FILL OR SURCHARGE. |
| EXISTING FOOTINGS OR FOUNDATIONS WHICH CAN BE AFFECTED |
| BY ANY EXCAVATION SHALL BE UNDERPINNED ADEQUATELY OR |
| OTHERWISE PROTECTED AGAINST SETTLEMENT AND SHALL BE |
| PROTECTED AGAINST LATER MOVEMENT. |
| |
| 13-19) COMPLIED. |
| |
| 20) SHEET A0.01; |
| 20A)COMPLIED. |
| |
| 20B) SEMI- COMPLIED. THE RESPONSE INDICATED SEE REVISED |
| SHEET M0.00 FOR THE BUILDING THERMOS INSULATION FOR |
| EXTERIOR WALLS AND FOR THE ROOF. THE MINIMUM FOR THE |
| ROOF IS STATED AS A R-19. THE POOL DECK (SHEET A2.10) |
| NOR THE INTERSTITIAL SPACE (SHEET A2.09) ABOVE THE |
| HIGHEST AIR CONDITIONED FLOOR SHOW INSULATION |
| SEPARATING THE NON-CONDITIONED SPACE FROM AIR |
| CONDITIONED SPACE. 2014 FBC-ENERGY CODE C402.2.5 FLOORS |
| OVER OUTDOOR AIR OR UNCONDITIONED SPACE. |
| |
| |
| |
| 20C) SEMI ?COMPLIED. THE INTENT OF THIS COMMENT WAS TO |
| STATE WHEN LOCATED OUTSIDE OF THE HIGH VELOCITY |
| HURRICANE ZONE WE CANNOT ENFORCE THE REQUIREMENTS OF |
| THE HIGH VELOCITY HURRICANE ZONE. ONLY BROWARD AND |
| MIAMI-DADE COUNTY ARE UNDER THE HIGH VELOCITY HURRICANE |
| ZONE. |
| THE CITY OF WEST PALM BEACH ACCEPTS BOTH PRODUCT |
| APPROVALS FROM THE STATE OF FLORIDA APPROVAL SYSTEM AND |
| THE MIAMI-DADE NOAS. |
| |
| |
| 1ST ROUND OF COMMENTS. UNDER THE HEADING BUILDING |
| MATERIALS THE STATEMENT STATES ALL APPROVALS FOR |
| WINDOWS AND DOORS ARE REQUIRED TO BE APPROVED BY |
| MIAMI/DADE COUNTY REQUIREMENTS FOR HIGH VELOCITY |
| HURRICANE ZONE REQUIREMENTS. PLEASE NOTE ONLY BROWARD |
| AND MIAMI-DADE COUNTY ARE UNDER THE HIGH VELOCITY |
| HURRICANE ZONE. SEE DEFINITIONS UNDER 202. |
| HIGH-VELOCITY HURRICANE ZONE. THIS ZONE CONSISTS OF |
| BROWARD AND DADE COUNTIES. |
| |
| 20D) BUILDING PROVISO: PRODUCT APPROVALS LISTED BELOW |
| CAN BE DEFERRED SUBMITTALS WITH THE APPROVAL OF EITHER |
| THE DESIGNER OF RECORD OR CONTRACTOR ONCE THE WIND |
| DESIGN CRITERIA IS REVIEWED AND APPROVED THEN THE |
| SUBMITTALS CAN BE SUBMITTED AFTER PERMIT ISSUANCE. |
| 107.3.4.2 DEFERRED SUBMITTALS. |
| 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (B) WINDOWS, MULLIONS |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, EFIS SYSTEMS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS, |
| INTAKE AND EXHAUST FANS |
| (E) SHUTTERS |
| (F) SKYLIGHTS |
| (G PRE-ENGINEERED A/C STANDS |
| FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH |
| ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR |
| TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL |
| 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 20E) BUILDING PROVISO, DEFERRED SUBMITTALS PRODUCT |
| APPROVALS & SHOP DRAWINGS. |
| IDENTIFY GLAZING/ MULLIONS. FOR ALL PRODUCTS WITH |
| GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, |
| TYPE OF GLAZING, MULLION INFORMATION IF REQUIRED, |
| ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING |
| SIZE. 107.2.1 CONSTRUCTION DOCUMENTS SHALL BE OF |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| DETERMINED BY THE BUILDING OFFICIAL. |
| |
| 20F) 2ND REQUEST. ROOFING: FOR ALL ROOFING PRODUCTS |
| PLEASE IDENTIFY ALL ROOFING SUB-SYSTEMS AND THEIR |
| ASSOCIATED PRESSURES FOR ROOF ZONE # 1. REVIEW THE |
| PRODUCT APPROVAL LIMITATIONS, IF ENHANCED FASTENING IS |
| ALLOWED FOR ROOF ZONES 2 & 3. IF SO RAS 117 |
| CALCULATIONS ARE REQUIRED BY EITHER A FLORIDA ARCHITECT |
| OR ENGINEER. PLEASE ALSO PROVIDE A SHOP DRAWING FOR THE |
| TAPERED ROOF INSULATION SHOWING COMPLIANCE WITH A |
| MINIMUM VALUE OF R-19 ( NOT AN AVERAGED VALUE). |
| 2014 FBC-B 1603.1.4 WIND DESIGN DATA. 107.2.1.2 FOR |
| ROOF ASSEMBLIES REQUIRED BY THE CODE, THE CONSTRUCTION |
| DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND DELINEATE THE |
| TYPE OF ROOFING SYSTEM, MATERIALS, FASTENING |
| REQUIREMENTS, FLASHING REQUIREMENTS AND WIND RESISTANCE |
| RATING THAT ARE REQUIRED TO BE |
| INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL |
| INDICATE COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR |
| THE SPECIFIC SITE OR A STATEMENT BY AN ARCHITECT OR |
| ENGINEER FOR THE SPECIFIC SITE MUST BE SUBMITTED WITH |
| THE CONSTRUCTION DOCUMENTS. |
| |
| 21A) 2ND REQUEST. SHEET A1.01.THE REVISED SITE PLAN |
| SHOWS 72 PARKING SPACES. SHEET A2.03 THERE IS 26 |
| SPACES, SHEET A2.04 ANOTHER 26 SPACES AND SHEET A2.05 |
| 22 SPACES OR A TOTAL OF 74 SPACES. PLEASE CORRECT THE |
| TOTAL COUNT. 107.2.1.3 ADDITIONAL INFORMATION IS |
| REQUIRED. |
| 21B) ON SHEET A2.05 THE PLANS SHOW A TOTAL OF 3 |
| ACCESSIBLE PARKING SPACES. WITH THE LOCATION OF THE 2 |
| SPACES LOCATED ON THE EXTERIOR WALL AND THE ENTRY INTO |
| THE ELEVATOR LOBBY ONE OF THE ACCESSIBLE PARKING SPACES |
| REQUIRES THE OCCUPANT TO HAVE TO TRAVEL BEHIND PARKED |
| CARS. |
| 2014 FBC-ACCESS. CODE 208.3.1. PARKING SPACES COMPLYING |
| WITH 502 THAT SERVE A PARTICULAR BUILDING OR FACILITY |
| SHALL BE LOCATED ON THE SHORTEST ACCESSIBLE ROUTE FROM |
| PARKING TO AN ENTRANCE COMPLYING WITH 206.4. ALL SPACES |
| MUST BE LOCATED ON AN ACCESSIBLE ROUTE THAT IS AT LEAST |
| 44 INCHES (1118 MM) WIDE AND SO THAT USERS ARE NOT |
| COMPELLED TO WALK OR WHEEL BEHIND PARKED VEHICLES |
| EXCEPT BEHIND HIS OR HER OWN VEHICLE. |
| |
| 1ST ROUND OF COMMENTS. SITE PLAN A1.01 INDICATES THERE |
| ARE 79 PARKING SPACES WITHIN THE BUILDING. SHEET A1.15 |
| THE 5TH FLOOR LIFE SAFETY PLAN THE 3RD PARKING LEVEL |
| SHOWS A TOTAL OF 4 ACCESSIBLE PARKING SPACES, OF THE 4 |
| ACCESSIBLE PARKING SPACES, (1) SPACE NEEDS TO COMPLY |
| WITH THE VERTICAL ACCESSIBILITY REQUIREMENTS OF ACCESS. |
| CODE 502.5 VERTICAL CLEARANCES FROM THE ENTRY OF THE |
| 1ST FLOOR, VEHICLE ELEVATORS INCOMING AND OUTGOING AND |
| THE VEHICLE ROUTE SERVING THEM. SEE ACCESS. CODE 502.5. |
| ADVISORY 502.5 VERTICAL CLEARANCE. |
| SIGNS PROVIDED AT ENTRANCES TO PARKING FACILITIES |
| INFORMING DRIVERS OF CLEARANCES AND THE LOCATION OF VAN |
| ACCESSIBLE PARKING SPACES CAN PROVIDE USEFUL CUSTOMER |
| ASSISTANCE. |
| |
| FLORIDA LAW, S.553.511, F.S., REQUIRES SIGNS BE POSTED |
| THAT WILL WARN HANDICAPPED-EQUIPPED VAN OPERATORS OF |
| HEIGHT LIMITATIONS SO THEY WILL NOT PASS BEYOND A POINT |
| WHERE THE VAN CANNOT BE MANEUVERED. |
| |
| FLORIDA LAW ALSO PREEMPTS LOCAL GOVERNMENT HEIGHT |
| RESTRICTION ORDINANCES THAT WOULD PROHIBIT COMPLIANCE |
| WITH THE MINIMUM HEIGHT REQUIREMENTS OF THIS SECTION. |
| ALSO, ANY LOCAL OR STATE LAW OR REGULATION THAT |
| PROHIBITS A COVERED ENTITY FROM COMPLYING WITH |
| REQUIREMENTS OF THE ADA MAY RENDER SUCH JURISDICTION IN |
| VIOLATION OF THE ADA. |
| |
| 22) COMPLIED. VAN ACCESSIBILITY. 2014 FBC-ACCESS. 502.6 |
| IDENTIFICATION. |
| |
| 23A) SHEET A1.11 GROUND FLOOR LIFE SAFETY PLAN VS. |
| A2.01 GROUND FLOOR PLAN. THIS COMMENT WILL HOLD TRUE |
| FOR ALL FLOORS, WITH THE EXCEPTION OF THE 3 PARKING |
| FLOORS. NEITHER OF THESE PLANS HAVE LABELED, IDENTIFIED |
| THE DOORS ON THE PLAN TO THE DOOR SCHEDULE FOUND ON |
| A8.02. OPENING PROTECTIVES CANNOT BE REVIEWED UNDER |
| FBC-B TABLE 716.5. EXAMPLE STAIR # 1 THERE ARE 3 DOORS |
| ASSOCIATED WITH THE VERTICAL STAIR ENCLOSURE FOUND ON |
| THE 1ST FLOOR. |
| |
| 23B)SEMI- COMPLIED. LIFE SAFETY SHEET A1.THE OCCUPANCY |
| LOAD SHOWN FOR THE 2ND FLOOR OF 569. THE CODE ANALYSIS |
| INDICATES THERE ARE 2 STAIRS AT 57 INCHES WHICH WILL |
| ACCEPT 190 OCCUPANTS NOT 206. THE 3RD STAIR IS LABELED |
| AS 52 INCHES WIDE. THE 600 SERIES PLANS FOR STAIRS IT |
| APPEARS ALL 3 STAIRS ARE 57 INCHES WIDE. 57/0.3= 190 |
| OCCUPANTS X 3 STAIRS= 570 OCCUPANTS. AGREED THE STAIRS |
| APPEAR TO BE THE LIMITING FACTOR. |
| TO USE THE 57/0.2 FACTOR NOT ONLY DOES THE BUILDING |
| REQUIRE FIRE SPRINKLERS BUT COMPLIANCE WITH AN |
| EMERGENCY VOICE/ALARM COMMUNICATIONS SYSTEM. |
| |
| 23C)(1 & 2) COMPLIED. |
| |
| 23D-G) COMPLIED. |
| |
| 24A) COMPLIED. |
| |
| 24B) COMPLIED. SHEET A1.12 LIFE SAFETY 3 STAIRS ARE A |
| MINIMUM OF 57 INCHES/ 0.3= 190 OCC. X 3= 570 OCCUPANTS. |
| |
| 24C) COMPLIED. CONFERENCE ROOMS 2 MEANS OF EGRESS. |
| |
| 24D) 2ND REQUEST . SEMI-COMPLIED. SHEET FP2.02 SHOWS |
| THE USE OF TYCO WINDOW SPRINKLERS, IT APPEARS THAT (2) |
| SPRINKLERS ARE LOCATED ON THE VERTICAL MULLION. PLEASE |
| PROVIDE A DETAIL FOR SPRINKLER AND WASHING OF THE |
| GLAZING FOR THIS AREA. 404.6 EXCEPTION 1.1. |
| |
| 1ST REVIEW COMMENTS. THERE IS A NOTE FOR S SMOKE |
| PARTITION FOR THE 2 STORY ATRIUM USING THE EXCEPTION #1 |
| REQUIRING BOTH REQUIREMENTS OF 404.6 EXCEPTION 1.1 & |
| 1.2 BE MET. PLEASE PROVIDE DETAILS FOR THE SPACING OF |
| THE FIRE SPRINKLERS AND COMPLIANCE WITH 1.2 1.2. THE |
| GLASS WALL SHALL BE INSTALLED IN A GASKETED FRAME IN A |
| MANNER THAT THE FRAMING SYSTEM DEFLECTS WITHOUT |
| BREAKING (LOADING) THE GLASS BEFORE THE SPRINKLER |
| SYSTEM OPERATES. |
| |
| 24E) COMPLIED. |
| |
| 25) SHEET A1.13 THE 3RD FLOOR PARKING & SHEET A2.03, |
| THESE SHEETS WILL BE COMMON COMMENTS FOR THE 3RD, 4TH |
| AND 5TH FLOORS. |
| |
| 25A)(1) COMPLIED. FBC-B 3007.7.2. THE FIRE SERVICE |
| ACCESS ELEVATOR LOBBY . SECTION 3007.7.3. |
| |
| 25A)(2) NEW COMMENT, DESIGN ISSUE, NOT A CODE ISSUE. |
| THE ACCESSIBLE PARKING SPACES ARE FOUND ON THE 5TH |
| FLOOR PARKING. TO GAIN ACCESS TO ANY OF THE FLOORS A |
| WHEELCHAIR BOUND PERSON WILL NEED TO USE THE FIREMEN?S |
| ELEVATOR. IF THE BUILDING GOES INTO FIRE ALARM THE |
| ACTUATION OF ANY BUILDING FIRE ALARM-INITIATING DEVICE |
| SHALL INITIATE PHASE I EMERGENCY RECALL OPERATION ON |
| ALL FIRE SERVICE ACCESS ELEVATORS IN ACCORDANCE WITH |
| THE REQUIREMENTS IN ASME A17.1/CSA B44. THE OCCUPANT IN |
| THE FIREMEN?S LOBBY ELEVATOR WILL BE STRANDED WITHOUT |
| ANY MEANS OF COMMUNICATION!!!! |
| AS YOU KNOW THE 2014 ACCESSIBILITY CODE SECTION 207.1 |
| REFERS YOU IN THE 2003 IBC TO SECTION 1007 FOR |
| ACCESSIBLE MEANS OF EGRESS. IN SECTION 1007.6 IS THE |
| SECTION FOR AREAS OF REFUGE. SECTION 1007.3 EXCEPTION 2 |
| AREAS OF REFUGE ARE NOT REQUIRED IN BUILDINGS THAT ARE |
| EQUIPPED THROUGHOUT IN ACCORDANCE WITH SECTION |
| 903.3.1.1. |
| |
| 25B-D) COMPLIED. |
| |
| 25E) SEMI-COMPLIED. A6.12 NOW DOES SHOW VERTICAL |
| BI-PARTING DOORS. THERE IS NO DOOR IDENTIFICATION TAG |
| PROVIDED, NEITHER IS THERE INFORMATION ON THIS DOOR AS |
| FAR AS HOURS OF RATING. THIS IS A 5 STORY SHAFT |
| REQUIRING 2 HR. RATING OF WALLS AND 90 MINUTE OPENING |
| PROTECTIVES, TABLE 716.5 OF THE 2014 FBC-B. |
| 1ST ROUND OF COMMENTS. THIS COMMENT IS A COMMON FOR THE |
| 3 PARKING FLOORS AND THE 1ST FLOOR. THE PLANS INDICATE |
| TO PROVIDE FALL PROTECTION AT THE ENTRY OF THE |
| AUTOMOBILE ELEVATOR. PLEASE PROVIDE COMPLIANCE WITH |
| 2014 FBC-B 1013.2 GUARDS SHALL BE LOCATED ALONG |
| OPEN-SIDED, EQUIPMENT PLATFORMS, STAIRS, RAMPS AND |
| LANDINGS THAT ARE LOCATED MORE THAN 30 INCHES (762 MM) |
| MEASURED VERTICALLY TO THE FLOOR OR GRADE BELOW AT ANY |
| POINT WITHIN 36 INCHES (914 MM) HORIZONTALLY TO THE |
| EDGE OF THE OPEN SIDE. GUARDS SHALL BE ADEQUATE IN |
| STRENGTH AND ATTACHMENT IN ACCORDANCE WITH SECTION |
| 1607.8. |
| |
| 25F) COMPLIED. 1607.8.3 VEHICLE BARRIERS. |
| |
| 25G)SEMI-COMPLIED. DEPENDING ON THE NEW LOCATION OF |
| COMMENT (21D). SHEET A2.05 LIFE SAFETY PLAN INDICATES 2 |
| ACCESSIBLE PARKING STALLS WITH COLUMNS IN THE ACCESS |
| AISLE. PLEASE PROVIDE THE CLEAR WIDTH FROM THE COLUMN |
| TO THE ACCESSIBLE PARKING STALL. FBC-ACCESSIBILITY CODE |
| 502.3.1 WIDTH. ACCESS AISLES SERVING CAR AND VAN |
| PARKING SPACES SHALL BE 60 INCHES (1525 MM) WIDE |
| MINIMUM. |
| |
| 26) SHEET A1.16 6TH FLOOR LIFE SAFETY PLAN & A7.05 & |
| A7.06 ENLARGED FLOOR PLAN 6TH FLOOR. |
| |
| 26A-E) COMPLIED |
| |
| 26F) BUILDING PROVISO/ DEFERRED SUBMITTAL: OPEN AIR |
| TERRACE WATERPROOFING MATERIAL AND DETAILS. SHEET 5.11. |
| ADMINISTRATION 107.3.4 DESIGN PROFESSIONAL IN |
| RESPONSIBLE CHARGE. THE REGISTERED DESIGN |
| PROFESSIONAL IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE |
| FOR REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS |
| PREPARED BY OTHERS, INCLUDING PHASED AND DEFERRED |
| SUBMITTAL ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF |
| THE BUILDING. PRODUCTS SHALL BE REVIEWED AND APPROVED |
| IN WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL. |
| |
| 26G) BUILDING PROVISO/ DEFERRED SUBMITTALS: OPEN AIR |
| TERRACE VIVA BLADE GUARD RAIL SYSTEM. SHEET 5.11. |
| ADMINISTRATION 107.3.4 DESIGN PROFESSIONAL IN |
| RESPONSIBLE CHARGE. THE REGISTERED DESIGN |
| PROFESSIONAL IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE |
| FOR REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS |
| PREPARED BY OTHERS, INCLUDING PHASED AND DEFERRED |
| SUBMITTAL ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF |
| THE BUILDING. PRODUCTS SHALL BE REVIEWED AND APPROVED |
| IN WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL. |
| |
| 26H) WE NEED A LETTER ADDRESSED TO THE BUILDING |
| OFFICIAL ROBERT BROWN FOR REVIEW AND APPROVAL BY ROBERT |
| BROWN UNDER THE 2014 FLORIDA BUILDING CODE W 2014 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1, ADMINISTRATION SECTION 104.11 ALTERNATE |
| MATERIALS, DESIGN AND METHODS OF CONSTRUCTION. MR. |
| BROWN HAS ALREADY REVIEWED THIS CONCEPT, BUT WILL NEED |
| THE LETTER TO BE SUBMITTED REQUESTING THE ALTERNATE |
| DESIGN IN MEETING THE CODE REQUIREMENT. |
| |
| ** COMMON COMMENT FOR ALL FLOORS (7-12) WHERE THE |
| ALLOWABLE COMMON PATH OF TRAVEL IS EXCEEDED. EXAMPLE: |
| ROOMS 718 & 719 FROM THE MOST REMOTE POINT IN THE SUITE |
| TO THE NEAREST VERTICAL EXIT IS OVER THE ALLOWABLE 75 |
| FT. TO ACHIEVE THE ALLOWABLE 75 FT. A RATED WALL IS |
| INSTALLED IN THE EXIT ACCESS CORRIDOR, ON THE DOOR |
| SCHEDULE THIS DOOR IS NOT FIRE RATED. PLEASE PROVIDE A |
| CODE SECTION WHERE THIS IS ALLOWED TO BE CONSIDERED |
| CODE COMPLIANT. 2014 FBC-B TABLE 1014.3. DEFINITION: |
| COMMON PATH OF EGRESS TRAVEL. THAT PORTION OF EXIT |
| ACCESS WHICH THE OCCUPANTS ARE REQUIRED TO TRAVERSE |
| BEFORE TWO SEPARATE AND DISTINCT PATHS OF EGRESS TRAVEL |
| TO TWO EXITS ARE AVAILABLE. PATHS THAT MERGE ARE COMMON |
| PATHS OF TRAVEL. COMMON PATHS OF EGRESS TRAVEL SHALL BE |
| INCLUDED WITHIN THE PERMITTED TRAVEL DISTANCE. |
| |
| 27) WE NEED A LETTER ADDRESSED TO THE BUILDING OFFICIAL |
| ROBERT BROWN FOR REVIEW AND APPROVAL BY ROBERT BROWN |
| UNDER THE 2014 FLORIDA BUILDING CODE W 2014 WEST PALM |
| BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER |
| 1, ADMINISTRATION SECTION 104.11 ALTERNATE MATERIALS, |
| DESIGN AND METHODS OF CONSTRUCTION. MR. BROWN HAS |
| ALREADY REVIEWED THIS CONCEPT, BUT WILL NEED THE LETTER |
| TO BE SUBMITTED REQUESTING THE ALTERNATE DESIGN IN |
| MEETING THE CODE REQUIREMENT. |
| |
| MR. BROWN HAS LOOKED AT THE ADDITIONAL COST INVOLVED IN |
| THE 2 HR. RATING OF THE WHOLE CORRIDOR AND 1 1/2 HOUR |
| RATING OF ALL DOORS WITHIN THE CORRIDOR. |
| |
| MR. BROWNS SUGGESTION IS TO CREATE A 2 HOUR VESTIBULE |
| IN FRONT OF STAIRWELL NUMBER ONE. LEAVE THE 1 ? HOUR |
| DOOR FOR THE STAIRWELL AND EXTEND THE 2 HOUR FIRE |
| RATING TO JUST WEST OF THE ROOMS 715 & 722, A PAIR OF |
| DOORS, SWING THE DOORS IN THE EGRESS TRAVEL AND HAVE |
| THE DOORS ON HOLD OPENS. TO THE WEST OF THE STAIRWELL 1 |
| DOOR OPENING HAVE A SECOND PAIR OF DOORS ON HOLD OPENS |
| IN LINE WITH UNITS 713 & 714, ON THE OPPOSITE WALL IT |
| APPEARS A FIRE EXTINGUISHER CABINET WOULD HAVE TO BE |
| RELOCATED. THIS DESIGN WOULD HOLD TRUE FOR THE FLOORS |
| 7-12. FLOOR 6 WE MEET THE TRAVEL DISTANCE SINCE THE |
| STAIRWELL # 1 WAS EXTENDED WITH THE 2ND REQUIRED DOOR |
| OPENING. |
| |
| SHEET A1.18 & A7.09 & A7.10. THE 8TH, 10TH & 12TH |
| FLOORS. THIS COMMENT FOR THE ROOMS 818,819,1018, |
| 1019,1218 & 1219 ALL EXCEED THE ALLOWABLE 75 FT. |
| ALLOWABLE COMMON PATH OF TRAVEL OF 75 FT. 2014 FBC-B |
| TABLE 1014.3 |
| |
| 28) COMPLIED. |
| |
| 29) SHEET A2.09 & A7.41 13TH FLOOR ROOFTOP GARDEN: |
| 29A-D) COMPLIED. |
| |
| 29E) 2ND REQUEST. THE INTERIOR LOBBY/ DINING AREA SHOWS |
| 36 INDOOR SEATS AT TABLES NOT 26. 36X0.05= 1.8 OR (2) |
| SEATS, COMPLIED. |
| THE AREA OF NON-COMPLIANCE IS THE OUTDOOR LOUNGE AREA |
| SHOWS TABLES AND 20 CHAIRS REQUIRING AT LEAST (1) |
| ACCESSIBLE SEAT. 20X0.05= 1 |
| 1ST ROUND OF COMMENTS. THE AREAS ROOF LOUNGE AND LOBBY, |
| 1313 & 1314 MAY NEED TO COMPLY WITH ACCESS. CODE 902.3 |
| IF THERE ARE TABLES PRESENT. THIS PLAN DOES NOT SHOW A |
| SEATING ARRANGEMENT IN THE ROOF LOUNGE 1314. |
| |
| 29F) 2ND REQUEST. STAIRWELL # 1 SHOWS A ROOF TOP HATCH |
| FOR ACCESS TO THE UPPER ROOF WITH MECHANICAL EQUIPMENT |
| ON THE ROOF TOP. PLEASE PROVIDE THE CLEAR OPENING FOR |
| THE ROOF TOP ROOF HATCH AND COMPLIANCE WITH 2014 FBC-B |
| SECTION 1009.16.1 EXCEPTION. IN BUILDINGS WITHOUT AN |
| OCCUPIED ROOF, ACCESS TO THE ROOF SHALL BE PERMITTED TO |
| BE A ROOF HATCH OR TRAP DOOR NOT LESS THAN 16 SQUARE |
| FEET IN AREA AND HAVING A MINIMUM DIMENSION OF 2 FEET . |
| |
| 1ST ROUND COMMENTS. STAIRWELL # 1 SHOWS A LADDER TO |
| GAIN ACCESS TO THE ROOF TOP EQUIPMENT. 2014 FBC-B |
| SECTION 1022.4 OPENINGS. INTERIOR EXIT STAIRWAY AND |
| RAMP OPENING PROTECTIVES SHALL BE IN ACCORDANCE WITH |
| THE REQUIREMENTS OF SECTION 716. OPENINGS IN INTERIOR |
| EXIT STAIRWAYS AND RAMPS OTHER THAN UNPROTECTED |
| EXTERIOR OPENINGS SHALL BE LIMITED TO THOSE NECESSARY |
| FOR EXIT ACCESS TO THE ENCLOSURE FROM NORMALLY OCCUPIED |
| SPACES AND FOR EGRESS FROM THE ENCLOSURE. |
| |
| 30) POOL AND JACUZZI ARE NOT PART OF THIS PERMIT, WILL |
| REQUIRE A SEPARATE PERMIT, REVIEW AND ASSOCIATED FEES. |
| |
| 31) BUILDING PROVISO. FENCING AND GATES AROUND THE POOL |
| WILL REQUIRE A SEPARATE PERMIT, REVIEW AND ASSOCIATED |
| FEES. |
| |
| 32) COMPLIED. |
| |
| 33-34) COMPLIED. |
| |
| 35) BUILDING PROVISO: DEFERRED SUBMITTAL. SHEETS A6.02 |
| & A6.03 STAIR GUARDRAIL/ HANDRAILS . ADMINISTRATION |
| 107.3.4 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE. THE |
| REGISTERED DESIGN |
| PROFESSIONAL IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE |
| FOR REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS |
| PREPARED BY OTHERS, INCLUDING PHASED AND DEFERRED |
| SUBMITTAL ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF |
| THE BUILDING. |
| FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL |
| FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE |
| ENGINEER OF RECORD FOR REVIEW. |
| |
| 36) SHEET A4.01 SHOWS A NORTH ELEVATION WITH A NOTE FOR |
| CONCRETE CANOPY WITH WOOD COMPOSITE UNDERNEATH FINISH. |
| THE STRUCTURAL SHEET S5.21 DETAIL PROVIDES STRUCTURAL |
| DETAILS AS TO THE THICKNESS OF THIS CANOPY, AND THE |
| PLACEMENT OF REINFORCEMENT. THERE ARE 2 AREAS OF |
| CONCERN: |
| |
| 36A) 2ND REQUEST. SHEET A4.01 THERE IS A NOTE |
| INDICATING THE MATERIAL ON THE UNDERSIDE OF THE CANOPY |
| IS A CLADDING PANEL COMPOSITE. PLEASE PROVIDE THE |
| LITERATURE ON THIS PRODUCT, IF THE PRODUCT DOES NOT |
| MEET THE DEFINITION OF COMPOSITE THEN CHANGE THE |
| TERMINOLOGY, BUT PRODUCT INFORMATION IS STILL GOING TO |
| BE REQUIRED. PLEASE PROVIDE THE PRODUCT APPROVAL |
| MIAMI-DADE NOA 15-0211.05 FOR REVIEW FOR WIND PRESSURES |
| AS WELL AS FOR FLAME SPREAD AND SMOKE DEVELOPMENT. |
| 1ST ROUND OF COMMENTS. THE NOTE FOUND ON A4.01 |
| INDICATES THE UNDERNEATH SIDE OF THE CANOPY IS TO BE |
| FINISHED WITH A WOOD COMPOSITE MATERIAL. WE FIND THIS |
| SAME NOTE AT AROUND THE 155 FT. & 173.5 FT. ELEVATION. |
| PLEASE PROVIDE PRODUCT LITERATURE ON THIS PRODUCT TO |
| SEE HOW THIS MATERIAL WAS TESTED, TO WHAT STANDARD? |
| DOES IT MEET THE DEFINITION OF A COMPOSITE MATERIAL. |
| |
| DEFINITION OF COMPOSITE MATERIAL: 703.5.2 COMPOSITE |
| MATERIALS. MATERIALS HAVING A STRUCTURAL BASE OF |
| NONCOMBUSTIBLE MATERIAL AS DETERMINED IN ACCORDANCE |
| WITH SECTION 703.5.1 WITH A SURFACING NOT MORE THAN |
| 0.125 INCH (3.18 MM) THICK THAT HAS A FLAME SPREAD |
| INDEX NOT GREATER THAN 50 WHEN TESTED IN ACCORDANCE |
| WITH ASTM E 84 OR UL 723 SHALL BE ACCEPTABLE AS |
| NONCOMBUSTIBLE MATERIALS. |
| |
| 2014 FBC-B 1406.2.1 TYPE I, II, III AND IV |
| CONSTRUCTION. ON BUILDINGS OF TYPE I, II, III AND IV |
| CONSTRUCTION, EXTERIOR WALL COVERINGS SHALL BE |
| PERMITTED TO BE CONSTRUCTED OF COMBUSTIBLE MATERIALS, |
| COMPLYING WITH THE FOLLOWING LIMITATIONS: |
| 1. COMBUSTIBLE EXTERIOR WALL COVERINGS SHALL NOT EXCEED |
| 10 PERCENT OF AN EXTERIOR WALL SURFACE AREA WHERE THE |
| FIRE SEPARATION DISTANCE IS 5 FEET (1524 MM) OR LESS. |
| 2. COMBUSTIBLE EXTERIOR WALL COVERINGS SHALL BE LIMITED |
| TO 40 FEET (12 192 MM) IN HEIGHT ABOVE GRADE PLANE. |
| 3. COMBUSTIBLE EXTERIOR WALL COVERINGS CONSTRUCTED OF |
| FIRE-RETARDANT-TREATED WOOD COMPLYING WITH SECTION |
| 2303.2 FOR EXTERIOR INSTALLATION SHALL NOT BE LIMITED |
| IN WALL SURFACE AREA WHERE THE FIRE SEPARATION DISTANCE |
| IS 5 FEET (1524 MM) OR LESS AND SHALL BE PERMITTED UP |
| TO 60 FEET (18 288 MM) IN HEIGHT ABOVE GRADE PLANE |
| REGARDLESS OF THE FIRE SEPARATION DISTANCE. |
| 4. WOOD VENEERS SHALL COMPLY WITH SECTION 1405.5. |
| 1406.2.1.1.2 FIRE SEPARATION GREATER THAN 5 FEET. FOR |
| FIRE SEPARATION DISTANCES GREATER THAN 5 FEET (1524 |
| MM), ANY EXTERIOR WALL COVERING SHALL BE PERMITTED THAT |
| HAS BEEN EXPOSED TO A REDUCED LEVEL OF INCIDENT RADIANT |
| HEAT FLUX IN ACCORDANCE WITH THE NFPA 268 TEST METHOD |
| WITHOUT EXHIBITING SUSTAINED FLAMING. THE MINIMUM FIRE |
| SEPARATION DISTANCE REQUIRED FOR THE EXTERIOR WALL |
| COVERING SHALL BE DETERMINED FROM TABLE 1406.2.1.1.2 |
| BASED ON THE MAXIMUM TOLERABLE LEVEL OF INCIDENT |
| RADIANT HEAT FLUX THAT DOES NOT CAUSE SUSTAINED FLAMING |
| OF THE EXTERIOR WALL COVERING. |
| |
| 36B) 2ND REQUEST. THE RESPONSE INDICATES A NEW SHEET |
| A5.15 EYEBROW DETAILS 1-6 ALL SHOW THE RESYSTA CP 140 |
| COMPOSITE CLADDING PANEL AND ATTACHMENT OF THE PANELS |
| PER THE NOA, BUT NO INFORMATION IS PROVIDED AS TO THE |
| MECHANICAL ATTACHMENT OF THE 1 X 3 TO THE CONCRETE |
| EYEBROW. |
| 1ST ROUND OF COMMENTS. THE WOOD COMPOSITE MATERIAL, |
| PLEASE PROVIDE HOW THIS MATERIAL WILL BE ATTACHED TO |
| THE SUB-STRUCTURE, ADHERED, PINNED? 107.2.1.3 |
| ADDITIONAL INFORMATION REQUIRED. |
| |
| 36C) PROVISO: POLYMER MODIFIED CEMENT WATER PROOFING TO |
| THE TOP OF THE CONCRETE EYEBROW. SUBMIT PRODUCT |
| APPROVAL. TO BE REVIEWED BY THE DESIGNER OF RECORD |
| BEFORE BEING SUBMITTED TO THE BUILDING DEPARTMENT. |
| |
| 37) BUILDING PROVISO/ DEFERRED SUBMITTAL. SHEET A4.01 |
| THE NORTH WALL ELEVATION ON THE GARAGE LEVELS 3-5 THE |
| PLANS SHOW PERFORATED ALUMINUM PANEL SYSTEM. PLEASE |
| PROVIDE PRODUCT LITERATURE, AND ENGINEERING ANALYSIS OF |
| THE SYSTEM, WITH THE WIND DESIGN CRITERIA AND ANCHORING |
| SYSTEMS REVIEWED BY THE ENGINEER OF RECORD. FL |
| 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL FORWARD |
| THE DELEGATED ENGINEERING DOCUMENTS TO THE ENGINEER OF |
| RECORD FOR REVIEW. 2014 FBC-B 1503.1 ROOF DECKS SHALL |
| BE COVERED WITH APPROVED ROOF COVERINGS SECURED TO THE |
| BUILDING OR STRUCTURE IN ACCORDANCE WITH THE PROVISIONS |
| OF THIS CHAPTER. ROOF COVERINGS SHALL BE DESIGNED AND |
| INSTALLED IN ACCORDANCE WITH THIS CODE AND THE APPROVED |
| MANUFACTURERS INSTRUCTIONS SUCH THAT THE ROOF COVERING |
| SHALL SERVE TO PROTECT THE BUILDING OR STRUCTURE. |
| |
| |
| 38A) COMPLIED. FIRE COMMAND CENTER LAYOUT. FBC-B |
| 911.1.4. |
| |
| 38B) SEMI-COMPLIED) 911.1.5 REQUIRED FEATURES. |
| THE FIRE COMMAND CENTER SHALL COMPLY WITH NFPA 72 AND |
| SHALL CONTAIN THE FOLLOWING FEATURES: |
| |
| 1.-5) SHEET E4.02 |
| 6. 2ND REQUEST, SEMI-COMPLIED. PLEASE REVIEW THE |
| MECHANICAL PLANS REVIEW COMMENT # 3, 2ND REVIEW. |
| THE FIREFIGHTERS CONTROL PANEL REQUIRED BY SECTION |
| 909.16 FOR SMOKE CONTROL SYSTEMS INSTALLED IN THE |
| BUILDING. |
| |
| 7-12). SHEET E4.02. |
| |
| 13) BUILDING PROVISO/ DEFERRED SUBMITTALS. (13.1-13.7) |
| AN APPROVED BUILDING INFORMATION CARD THAT CONTAINS, |
| BUT IS NOT LIMITED TO, THE FOLLOWING INFORMATION: |
| |
| 13.1. GENERAL BUILDING INFORMATION THAT INCLUDES: |
| PROPERTY NAME, ADDRESS, THE NUMBER OF FLOORS IN THE |
| BUILDING (ABOVE AND BELOW GRADE), USE AND OCCUPANCY |
| CLASSIFICATION (FOR MIXED USES, IDENTIFY THE DIFFERENT |
| TYPES OF OCCUPANCIES ON EACH FLOOR), ESTIMATED BUILDING |
| POPULATION (I.E., DAY, NIGHT, WEEKEND); |
| |
| 13.2. BUILDING EMERGENCY CONTACT INFORMATION THAT |
| INCLUDES: A LIST OF THE BUILDING?S EMERGENCY CONTACTS |
| (E.G., BUILDING MANAGER, BUILDING ENGINEER, ETC.) AND |
| THEIR RESPECTIVE WORK PHONE NUMBER, CELL PHONE NUMBER, |
| EMAIL ADDRESS; |
| |
| 13.3. BUILDING CONSTRUCTION INFORMATION THAT INCLUDES: |
| THE TYPE OF BUILDING CONSTRUCTION (E.G., FLOORS, WALLS, |
| COLUMNS, AND ROOF ASSEMBLY); |
| |
| 13.4. EXIT STAIR INFORMATION THAT INCLUDES: NUMBER OF |
| EXIT STAIRS IN BUILDING, EACH EXIT STAIR DESIGNATION |
| AND FLOORS SERVED, LOCATION WHERE EACH EXIT STAIR |
| DISCHARGES, EXIT STAIRS THAT ARE PRESSURIZED, EXIT |
| STAIRS PROVIDED WITH EMERGENCY LIGHTING, EACH EXIT |
| STAIR THAT ALLOWS REENTRY, EXIT STAIRS PROVIDING ROOF |
| ACCESS; ELEVATOR INFORMATION THAT INCLUDES: NUMBER OF |
| ELEVATOR BANKS, ELEVATOR BANK DESIGNATION, ELEVATOR CAR |
| NUMBERS AND RESPECTIVE FLOORS THAT THEY SERVE, LOCATION |
| OF ELEVATOR MACHINE ROOMS, LOCATION OF SKY LOBBY, |
| LOCATION OF FREIGHT ELEVATOR BANKS; |
| |
| 13.5. BUILDING SERVICES AND SYSTEM INFORMATION THAT |
| INCLUDES: LOCATION OF MECHANICAL ROOMS, LOCATION OF |
| BUILDING MANAGEMENT SYSTEM, LOCATION AND CAPACITY OF |
| ALL FUEL OIL TANKS, LOCATION OF EMERGENCY GENERATOR, |
| LOCATION OF NATURAL GAS SERVICE; |
| |
| 13.6. FIRE PROTECTION SYSTEM INFORMATION THAT INCLUDES: |
| LOCATIONS OF STANDPIPES, LOCATION OF FIRE PUMP ROOM, |
| LOCATION OF FIRE DEPARTMENT CONNECTIONS, FLOORS |
| PROTECTED BY AUTOMATIC SPRINKLERS, LOCATION OF |
| DIFFERENT TYPES OF SPRINKLER SYSTEMS INSTALLED (E.G., |
| DRY, WET, PRE-ACTION, ETC.); AND |
| |
| 13.7 HAZARDOUS MATERIAL INFORMATION THAT INCLUDES: |
| LOCATION OF HAZARDOUS MATERIAL, QUANTITY OF HAZARDOUS |
| MATERIAL. |
| |
| 14. WORK TABLE. |
| |
| 15. GENERATOR SUPERVISION DEVICES, MANUAL START AND |
| TRANSFER FEATURES. |
| |
| 16. PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED |
| BY OTHER SECTIONS OF THIS CODE. |
| |
| 17. ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME |
| A17.1. |
| |
| 18. ELEVATOR EMERGENCY OR STANDBY POWER SELECTOR |
| SWITCH(ES), WHERE EMERGENCY OR STANDBY POWER IS |
| PROVIDED. |
| |
| 39) COMPLIED. 2014 FBC-B 403.5.3 STAIRWAY DOOR |
| OPERATION. |
| |
| 40) SEMI ?COMPLIED. PLEASE REVIEW THE MECHANICAL PLANS |
| REVIEW COMMENT # 3, 2ND REVIEW. 2014 FBC-B 403.4.7 |
| SMOKE REMOVAL./ 909.4 ANALYSIS. A RATIONAL ANALYSIS |
| SUPPORTING THE TYPES OF SMOKE CONTROL SYSTEMS TO BE |
| EMPLOYED, THEIR METHODS OF OPERATION, THE SYSTEMS |
| SUPPORTING THEM AND THE METHODS OF CONSTRUCTION TO BE |
| UTILIZED SHALL ACCOMPANY THE SUBMITTED CONSTRUCTION |
| DOCUMENTS AND SHALL INCLUDE, BUT NOT BE LIMITED TO, THE |
| ITEMS INDICATED IN SECTIONS 909.4.1 THROUGH 909.4.6. |
| |
| 41) COMPLIED. FBC-B 403.5.5 LUMINOUS EGRESS PATH |
| MARKINGS.. |
| |
| 42) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| 43) COMPLIED, THANK YOU. FOR THE RESUBMISSION OF PLANS, |
| PLEASE BREAK THE PLAN SETS DOWN TO SMALLER MANAGEABLE |
| ROLLS. BUILDING AND ID DRAWINGS TOGETHER, STRUCTURAL BY |
| ITSELF AND MEP TOGETHER. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |