2016-08-14 08:49:55 | 1) CIVIL DRAWING C-10 SHOWS A 1500 GALLON GREASE |
| INTERCEPTOR AND PLUMBING SHEET P5.06 CALLS OUT A 1250 |
| GALLON INTERCEPTOR. CLARIFY. |
| 2) LANDSCAPE DRAWINGS - SHOW THE SOURCE OF WATER FOR |
| THE IRRIGATION SYSTEM AND THE LOCATION OF THE |
| IRRIGATION SYSTEM CONTROLLER AND THE RAIN SENSOR. WPB |
| AMEND TO FBC SEC. 107.2.1. |
| 3) SUBMIT THE OCCUPANT LOAD FOR THE DIFFERENT |
| OCCUPANCIES (ASSEMBLY- A-2, A-3, BUSINESS, STORAGE, |
| ETC.). THIS INFORMATION IS NEEDED TO DETERMINE THE |
| MINIMUM REQUIRED SANITARY FACILITIES FOR THE DIFFERENT |
| OCCUPANCY GROUPS FOR THE COMMON AREAS PER THE 2014 FPC |
| TABLE 403.1. |
| 4) THE ASSEMBLY AREAS MAY BE REQUIRED TO COMPLY WITH |
| THE POTTY PARITY REQUIREMENTS OF THE 2014 FPC SEC. |
| 403.1.3. |
| 5) PLACE A NOTE ON THE ARCHITECTURAL PLANS THAT THE |
| GENERATOR & FUEL PIPING WILL BE DONE UNDER A SEPARATE |
| PERMIT. |
| 6) SHT. A0.01 NOTES THIS BUILDING IS A 6 STORY MIDRISE |
| BUT THE APPLICATION NOTES THAT IT IS A 17 STORY |
| BUILDING. IT APPEARS TO BE A 13 STORY BUILDING. |
| CLARIFY. |
| 7) SHT. A2.09 REFERS TO DETAIL 4 ON SHT. A7.41 - THERE |
| IS NO DETAIL 4 ON A7.41. CLARIFY. |
| 8) SHT. A7.41 - DETAIL #13 - SHOWER HEAD LOCATION - A |
| FIXED SHOWER HEAD MOUNTED AT 48 INCHES ABOVE THE FINISH |
| FLOOR IS NOT PERMITTED IN TRANSIENT LODGING ROOMS PER |
| THE 2014 FBC-ACCESS. SEC.608.6 EXCEPTION. |
| 9) SHT. A7.41 - SEATS LOCATED IN THE HANDICAPPED |
| ACCESSIBLE SHOWERS SHALL COMPLY WITH THE 2014 |
| FBC-ACCESS. SECS. 610.3 & 806.2.4. SUBMIT COMPLETE |
| DETAILS FOR THE TYPE OF SEAT (RECTANGULAR OR L-SHAPED,) |
| DIMENSIONS FROM WALLS, LOCATION, ETC. |
| 10) SHT. A7.41 - DETAIL #13 SHOWS THE MAXIMUM HEIGHT |
| RANGE FOR THE ACCESSIBLE LAVATORY AS 3 FEET. THE |
| MAXIMUM HEIGHT SHALL BE 34 INCHES. 2014 FAC SEC. 606.3. |
| 11) SHT. A8.01 - SHOW THE WALL FINISH MATERIAL FOR |
| ROOMS #130,131,142,210,211,212,621, & 622. COMPLY WITH |
| THE 2014 FBC SEC. 1210. |
| 12) GRAB BARS SHALL BE MEASURED TO THE TOP OF THE |
| GRIPPING SURFACE, NOT TO THE CENTERLINE AS SHOWN. FAC |
| SEC. 609.4. |
| 13) SHT. A7.41 - ALTERNATE ROLL-IN SHOWER MEN'S & |
| WOMEN'S LOCKER ROOM - THE CONTROLS FOR THE ALTERNATE |
| ROLL-IN SHOWER SHALL COMPLY WITH 2014 FAC SECS. |
| 608.5.3,608.6. THE THRESHOLD SHALL COMPLY WITH 608.7. |
| 14) SHT. A7.41 - THE DETAILS SHOW ALL THE HANDICAPPED |
| WATER CLOSETS AT A HEIGHT OF ONE FOOT THREE INCHES |
| ABOVE THE FINISH FLOOR YET DETAIL #3 SHOWS ONE FOOT |
| SEVEN INCHES. CLARIFY. |
| 15) SHT. A7.41 - TOILET PAPER DISPENSERS SHALL BE |
| LOCATED IN ACCORDANCE WITH THE FAC SEC.604.9.6. |
| 16) SHT. A7.41 - DETAIL #6 - THE LENGTH OF THE STANDARD |
| TOILET STALLS SHALL COMPLY WITH FBC-PLUMBING SEC.403. |
| 17) SHT. ID-0.1 ADA GUIDELINES - THE ACCESSIBILITY CODE |
| THAT IS IN EFFECT IN FLORIDA IS THE 2014 |
| FBC-ACCESSIBILITY VOLUME, NOT THE ADA. THE FLORIDA CODE |
| IS AN ADA EQUIVALENT CODE AND CERTIFIED BY THE DOJ. |
| THESE DETAILS ARE NOT REQUIRED AND MAY CONFLICT WITH |
| THE FBC. |
| 18) SHT.ID-2.40 - DETAIL 03 & SHT.ID-4.30 - SHOWS A |
| SINK LOCATED IN THE CORRIDOR. IF AVAILABLE TO THE |
| GUESTS THIS SINK SHALL COMPLY WITH FBC-ACCESS. SECS. |
| 305. 606. MAX. HEIGHT SHALL BE 34 INCHES. |
| 19) SUBMIT MANUFACTURER SPECIFICATIONS FOR THE ZOELLER |
| ALARM FOR THE ELEVATOR SUMP PUMP. WPB AMEND. TO FBC |
| SEC. 107.2.1. |
| 20) SHT. P-2.01 - SHOWS THE FIRE STANDPIPE DRAIN |
| DISCHARGING TO THE STORM DRAINAGE SYSTEM. CITY CODE OF |
| ORDINANCES ARTICLE V, SEC. 90-203 (A) PROHIBITS THE |
| DISCHARGE OF ANYTHING OTHER THAN STORM WATER INTO THE |
| STORM DRAINAGE SYSTEM. |
| 21) LABEL THE GW WATER RISERS ON THE WATER DISTRIBUTION |
| ISOMETRICS. WPB AMEND. TO FBC SEC. 107.3.5.1.3. |
| 22) SHT. P4.01 - GREASY WASTE RISER GR/1 SHOWS NO |
| CONTINUATION POINT. CLARIFY. SUBMIT A COMPLETE |
| RISER/COLLECTION SYSTEM FOR THE GREASE WASTE SYSTEM. |
| WPB AMEND. TO FBC SEC. 107.3.5.1.3. |
| 23) SHT. P4.01 - SHOW THE CONTINUATION POINT FOR THE |
| VENT FOR THE HAND SINK IN THE CAFE? (ROOM #134). |
| 24) INDIVIDUAL VENTS, BRANCH VENTS, CIRCUIT VENTS AND |
| RELIEF VENTS EXCEEDING 40 FEET IN DEVELOPED LENGTH |
| SHALL BE INCREASED BY ONE NOMINAL PIPE SIZE FOR THE |
| ENTIRE DEVELOPED LENGTH OF THE VENT PIPE PER 2014 FPC |
| SEC.906.2. |
| 25) SHT. P2.08 - KEYNOTE #16 - REFERS TO 3 INCH |
| SANITARY TO LEVEL 6 AND STATES "SEE P2.06 FOR LAYOUT." |
| P2.06 IS FOR THE FOURTH FLOOR. CLARIFY. |
| 26) SHT. P2.09 - KEYNOTE #6 REFERS TO SHT. P2.01 FOR |
| CONTINUATION. THIS LINE IS NOT SHOWN ON P2.01. CLARIFY. |
| 27) SHT. P2.09 - 3 PD'S (62 SF, 18 SF, 18 SF) & 1 DD |
| (1161 SF) AT GRID LINES 7-8 & B-C DO NOT APPEAR TO BE |
| ON THE STORM RISER DRAWINGS. CLARIFY. |
| 28) SHT. P2.12 - KEYNOTE #8 REFERS TO A GAS SOLENOID |
| VALVE & SHUTOFF VALVE. THE VALVES SHALL BE LOCATED IN |
| THE SAME ROOM AS THE APPLIANCE. 2014 FGC SEC.409.5.1. |
| 29) SHT. P2.12 -KEYNOTE #11 REFERS TO SHTS.P4.04 & |
| P4.06 FOR ENLARGED KITCHEN/BAR PLANS. THERE ARE NO SUCH |
| ENLARGED PLANS ON THESE SHEETS. CLARIFY. |
| 30) SHT. P2.12 - BOTTOM PLAN - KEYNOTE # 3 REFERS TO |
| SHTS. P4.04 & P4.06 FOR GREASY WASTE PIPING. THERE IS |
| NO GREASY WASTE PIPING ON THESE SHEETS. REVISE NOTE TO |
| REFER TO CORRECT PAGE. |
| 31) SHT. P2.12 - IDENTIFY ALL THE RISERS WITH A RISER |
| IDENTIFYING TAG NUMBER. WPB AMEND. TO FBC SEC. 107.2.1. |
| 32) SHT. P2.13 - BOTTOM PLAN - KEYNOTE # 9 - SHOW THESE |
| RISERS ON P2.09 AS NOTED. I CANNOT FIND THESE RISERS ON |
| P2.09.CLEARLY IDENTIFY THESE RISERS. WPB AMEND. TO FBC |
| SEC. 107.2.1. |
| 33) SHT. P2.09 SHOWS A SANITARY AND WATER LINE IN |
| STAIRWELL #1. THIS IS NOT PERMITTED PER 2014 |
| FBC-BUILDING SEC. 1009.3.1.5.1. |
| 34) SHT. P4.01 - THE PLANS SHOW THE WASTE FROM THE |
| ELEVATOR SUMPS DISCHARGING INTO THE GREASY WASTE |
| SYSTEM. THIS IS NOT PERMITTED. THE ELEVATOR SUMPS ARE |
| EQUIPPED WITH ALARMS. THIS DISCHARGE CAN GO TO THE |
| SANITARY OR TO A SEPARATE OIL SEPARATOR IF DESIRED. FBC |
| 1003.3.1. |
| 35) SHT. P4.01 - RESTROOMS #209 & 210 AND ROOMS #235, |
| 236, 237 & 238 - THE RISER DOES NOT COMPLY WITH THE |
| 2014 FPC FOR WET VENTS OR CIRCUIT VENTS. |
| 36) A LINT INTERCEPTOR IS REQUIRED FOR THE LAUNDRY ROOM |
| PER 2014 FPC SEC. 1003.6. |
| 37) SHTS. P4.01 & P4.02 - CLEARLY IDENTIFY THE |
| CONTINUATION POINTS OF ALL VENTS. |
| 38) SHT. P4.02 - I CANNOT FIND KEYNOTE #1 ON THE PLAN. |
| CLARIFY. |
| 39) SHT. P4.02 - CLARIFY THE DESIGN OF THE FIRST LEVEL |
| SANITARY SYSTEM. IT DOES NOT COMPLY WITH THE 2014 FPC |
| SEC. 912 FOR WET VENTS OR SEC. 914 FOR CIRCUIT VENTING. |
| 40) SHT. P4.02 - THE LAYOUT OF THE 5TH FLOOR SANITARY |
| DOES NOT CORRELATE WITH THE FLOOR PLAN ON SHT. P2.08. - |
| CLARIFY. |
| 41) SHT.P4.02 - THE 1ST LEVEL RISER SHOWS A PIECE OF |
| KITCHEN EQUIPMENT DISCHARGING INTO THE SANITARY. THEY |
| SHALL DISCHARGE INDIRECTLY INTO THE GREASE WASTE |
| SYSTEM. FPC SEC. 1003.3.1. |
| 42) SHT. P4.02 - REFERS TO SHT. P5.01 FOR CONTINUATION |
| OF SANITARY LINES AND VENTS. THERE ARE NO RISERS ON |
| SHT. P5.01. CLARIFY. |
| 43) SHT. P4.03 - RISER S/2 - KEYNOTE #3 - THE |
| REFERENCED VENT IS NOT IDENTIFIED ON SHT. P4.02. |
| CLARIFY. |
| 44) SHT. P4.03 - RISER S/15 - THERE ARE NOT FIXTURES |
| SHOWN ON THE STACK AND IT IS INCOMPLETE. PROVIDE THE |
| ENTIRE RISER FOR REVIEW. |
| 45) SHT. P4.03 - RISER S/14 - RESTROOMS BY STAIR #2 - |
| THE RISER DOES NOT COMPLY WITH THE FPC SEC. 912 OR SEC. |
| 914 FOR A HORIZONTAL WET VENT OR A CIRCUIT VENT. |
| 46) SHT. P4.04 - KEYNOTE #2 REFERS TO SHT. P4.03 FOR |
| THE CONTINUATION OF WATER LINES. SHT.P4.03 IS SANITARY |
| RISERS. KEYNOTE #2 DOES CORRELATE WITH WHAT IS SHOWN ON |
| THE WATER RISER. SEE KEYNOTES #3 & #8 ALSO. CLARIFY. |
| 47) SHT. P4.05 - KEYNOTE #1 REFERS TO SHT. P4.03A. |
| THERE IS NO SUCH SHEET. CLARIFY. |
| 48) SHT. P4.05 - SIZE ALL SECTIONS OF THE WATER RISER. |
| SEE KEYNOTE #1 AND PIPING AT POINTS A & B. |
| 49) SHEET P4.05 - SHOW THE CONTINUATION POINTS OF THE |
| "A" LINE. THE RISER APPEARS TO SHOW TWO LINES TURNED |
| DOWN. |
| 50) SHT. P4.05 - KEYNOTE #5 DOES NOT APPEAR TO |
| CORRELATE WITH THE RISER. CLARIFY. |
| 51) SHT. P4.05 - SHOW THE CONTINUATION POINT OF THE 140 |
| DEGREE WATER. |
| 52) SHT. P4.06 - WATER RISER #1 - BEVERAGE DISPENSERS, |
| COFFEE MACHINES AND NONCARBONATED BEVERAGE DISPENSERS |
| SHALL BE PROTECTED AGAINST BACKFLOW PER FPC SECS. |
| 608.16.1 & 608.16.10. |
| 53) SUBMIT A WATER RISER FOR THE TYPICAL KING ROOM. THE |
| WATER RISER ON P4.07 IS FOR THE KING SUITE. WPB AMEND. |
| TO FBC SEC. 107.3.5.1.3. |
| 54) SHT. P4.07 - DETAIL "C" THE WATER RISER SHOWS 2 |
| LAVATORIES IN EACH ROOM & SHT. P2.10 AND RISER S/12 |
| APPEAR TO SHOW ONE LAVATORY IN EACH ROOM. CLARIFY. |
| 55) SHT. P4.07 - DETAIL 'H" - IDENTIFY THE L/SK & SK ON |
| THE WATER RISER. IF THESE ARE IN THE LAUNDRY ROOM |
| INCLUDE THE LAUNDRY ROOM NUMBER ON THE DETAIL AND |
| SUBMIT A COMPLETE WATER RISER FOR THE LAUNDRY. |
| 56) ALL FLOOR DRAINS SHALL HAVE TRAP PRIMERS. 2014 FPC |
| SEC. 1002.4. |
| 57) SHT. P4.10 - SUPPLY THE TONS OF REFRIGERANT PER |
| RISER. THE SIZING OF THE CONDENSATE RISERS SHALL COMPLY |
| WITH FPC TABLE 314.2.2. |
| 58) THE FLOOR DRAINS RECEIVING THE DISCHARGE FROM THE |
| ELEVATOR SUMPS SHALL BE EQUIPPED WITH TRAP PRIMERS. |
| 2014 FPC SEC.1002.4. |
| |
| NOTE: THE BUILDING CODE REQUIREMENTS FOR THE POOL |
| EQUIPMENT ROOM WILL BE REVIEWED WHEN THE POOL PLANS ARE |
| SUBMITTED. |
| |