Plan Review Notes
Plan Review Notes For Permit 16061443
Permit Number 16061443
Review Stop P
Sequence Number 1
Notes
Date Text
2016-08-14 08:49:551) CIVIL DRAWING C-10 SHOWS A 1500 GALLON GREASE
 INTERCEPTOR AND PLUMBING SHEET P5.06 CALLS OUT A 1250
 GALLON INTERCEPTOR. CLARIFY.
 2) LANDSCAPE DRAWINGS - SHOW THE SOURCE OF WATER FOR
 THE IRRIGATION SYSTEM AND THE LOCATION OF THE
 IRRIGATION SYSTEM CONTROLLER AND THE RAIN SENSOR. WPB
 AMEND TO FBC SEC. 107.2.1.
 3) SUBMIT THE OCCUPANT LOAD FOR THE DIFFERENT
 OCCUPANCIES (ASSEMBLY- A-2, A-3, BUSINESS, STORAGE,
 ETC.). THIS INFORMATION IS NEEDED TO DETERMINE THE
 MINIMUM REQUIRED SANITARY FACILITIES FOR THE DIFFERENT
 OCCUPANCY GROUPS FOR THE COMMON AREAS PER THE 2014 FPC
 TABLE 403.1.
 4) THE ASSEMBLY AREAS MAY BE REQUIRED TO COMPLY WITH
 THE POTTY PARITY REQUIREMENTS OF THE 2014 FPC SEC.
 403.1.3.
 5) PLACE A NOTE ON THE ARCHITECTURAL PLANS THAT THE
 GENERATOR & FUEL PIPING WILL BE DONE UNDER A SEPARATE
 PERMIT.
 6) SHT. A0.01 NOTES THIS BUILDING IS A 6 STORY MIDRISE
 BUT THE APPLICATION NOTES THAT IT IS A 17 STORY
 BUILDING. IT APPEARS TO BE A 13 STORY BUILDING.
 CLARIFY.
 7) SHT. A2.09 REFERS TO DETAIL 4 ON SHT. A7.41 - THERE
 IS NO DETAIL 4 ON A7.41. CLARIFY.
 8) SHT. A7.41 - DETAIL #13 - SHOWER HEAD LOCATION - A
 FIXED SHOWER HEAD MOUNTED AT 48 INCHES ABOVE THE FINISH
 FLOOR IS NOT PERMITTED IN TRANSIENT LODGING ROOMS PER
 THE 2014 FBC-ACCESS. SEC.608.6 EXCEPTION.
 9) SHT. A7.41 - SEATS LOCATED IN THE HANDICAPPED
 ACCESSIBLE SHOWERS SHALL COMPLY WITH THE 2014
 FBC-ACCESS. SECS. 610.3 & 806.2.4. SUBMIT COMPLETE
 DETAILS FOR THE TYPE OF SEAT (RECTANGULAR OR L-SHAPED,)
 DIMENSIONS FROM WALLS, LOCATION, ETC.
 10) SHT. A7.41 - DETAIL #13 SHOWS THE MAXIMUM HEIGHT
 RANGE FOR THE ACCESSIBLE LAVATORY AS 3 FEET. THE
 MAXIMUM HEIGHT SHALL BE 34 INCHES. 2014 FAC SEC. 606.3.
 11) SHT. A8.01 - SHOW THE WALL FINISH MATERIAL FOR
 ROOMS #130,131,142,210,211,212,621, & 622. COMPLY WITH
 THE 2014 FBC SEC. 1210.
 12) GRAB BARS SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE, NOT TO THE CENTERLINE AS SHOWN. FAC
 SEC. 609.4.
 13) SHT. A7.41 - ALTERNATE ROLL-IN SHOWER MEN'S &
 WOMEN'S LOCKER ROOM - THE CONTROLS FOR THE ALTERNATE
 ROLL-IN SHOWER SHALL COMPLY WITH 2014 FAC SECS.
 608.5.3,608.6. THE THRESHOLD SHALL COMPLY WITH 608.7.
 14) SHT. A7.41 - THE DETAILS SHOW ALL THE HANDICAPPED
 WATER CLOSETS AT A HEIGHT OF ONE FOOT THREE INCHES
 ABOVE THE FINISH FLOOR YET DETAIL #3 SHOWS ONE FOOT
 SEVEN INCHES. CLARIFY.
 15) SHT. A7.41 - TOILET PAPER DISPENSERS SHALL BE
 LOCATED IN ACCORDANCE WITH THE FAC SEC.604.9.6.
 16) SHT. A7.41 - DETAIL #6 - THE LENGTH OF THE STANDARD
 TOILET STALLS SHALL COMPLY WITH FBC-PLUMBING SEC.403.
 17) SHT. ID-0.1 ADA GUIDELINES - THE ACCESSIBILITY CODE
 THAT IS IN EFFECT IN FLORIDA IS THE 2014
 FBC-ACCESSIBILITY VOLUME, NOT THE ADA. THE FLORIDA CODE
 IS AN ADA EQUIVALENT CODE AND CERTIFIED BY THE DOJ.
 THESE DETAILS ARE NOT REQUIRED AND MAY CONFLICT WITH
 THE FBC.
 18) SHT.ID-2.40 - DETAIL 03 & SHT.ID-4.30 - SHOWS A
 SINK LOCATED IN THE CORRIDOR. IF AVAILABLE TO THE
 GUESTS THIS SINK SHALL COMPLY WITH FBC-ACCESS. SECS.
 305. 606. MAX. HEIGHT SHALL BE 34 INCHES.
 19) SUBMIT MANUFACTURER SPECIFICATIONS FOR THE ZOELLER
 ALARM FOR THE ELEVATOR SUMP PUMP. WPB AMEND. TO FBC
 SEC. 107.2.1.
 20) SHT. P-2.01 - SHOWS THE FIRE STANDPIPE DRAIN
 DISCHARGING TO THE STORM DRAINAGE SYSTEM. CITY CODE OF
 ORDINANCES ARTICLE V, SEC. 90-203 (A) PROHIBITS THE
 DISCHARGE OF ANYTHING OTHER THAN STORM WATER INTO THE
 STORM DRAINAGE SYSTEM.
 21) LABEL THE GW WATER RISERS ON THE WATER DISTRIBUTION
 ISOMETRICS. WPB AMEND. TO FBC SEC. 107.3.5.1.3.
 22) SHT. P4.01 - GREASY WASTE RISER GR/1 SHOWS NO
 CONTINUATION POINT. CLARIFY. SUBMIT A COMPLETE
 RISER/COLLECTION SYSTEM FOR THE GREASE WASTE SYSTEM.
 WPB AMEND. TO FBC SEC. 107.3.5.1.3.
 23) SHT. P4.01 - SHOW THE CONTINUATION POINT FOR THE
 VENT FOR THE HAND SINK IN THE CAFE? (ROOM #134).
 24) INDIVIDUAL VENTS, BRANCH VENTS, CIRCUIT VENTS AND
 RELIEF VENTS EXCEEDING 40 FEET IN DEVELOPED LENGTH
 SHALL BE INCREASED BY ONE NOMINAL PIPE SIZE FOR THE
 ENTIRE DEVELOPED LENGTH OF THE VENT PIPE PER 2014 FPC
 SEC.906.2.
 25) SHT. P2.08 - KEYNOTE #16 - REFERS TO 3 INCH
 SANITARY TO LEVEL 6 AND STATES "SEE P2.06 FOR LAYOUT."
 P2.06 IS FOR THE FOURTH FLOOR. CLARIFY.
 26) SHT. P2.09 - KEYNOTE #6 REFERS TO SHT. P2.01 FOR
 CONTINUATION. THIS LINE IS NOT SHOWN ON P2.01. CLARIFY.
 27) SHT. P2.09 - 3 PD'S (62 SF, 18 SF, 18 SF) & 1 DD
 (1161 SF) AT GRID LINES 7-8 & B-C DO NOT APPEAR TO BE
 ON THE STORM RISER DRAWINGS. CLARIFY.
 28) SHT. P2.12 - KEYNOTE #8 REFERS TO A GAS SOLENOID
 VALVE & SHUTOFF VALVE. THE VALVES SHALL BE LOCATED IN
 THE SAME ROOM AS THE APPLIANCE. 2014 FGC SEC.409.5.1.
 29) SHT. P2.12 -KEYNOTE #11 REFERS TO SHTS.P4.04 &
 P4.06 FOR ENLARGED KITCHEN/BAR PLANS. THERE ARE NO SUCH
 ENLARGED PLANS ON THESE SHEETS. CLARIFY.
 30) SHT. P2.12 - BOTTOM PLAN - KEYNOTE # 3 REFERS TO
 SHTS. P4.04 & P4.06 FOR GREASY WASTE PIPING. THERE IS
 NO GREASY WASTE PIPING ON THESE SHEETS. REVISE NOTE TO
 REFER TO CORRECT PAGE.
 31) SHT. P2.12 - IDENTIFY ALL THE RISERS WITH A RISER
 IDENTIFYING TAG NUMBER. WPB AMEND. TO FBC SEC. 107.2.1.
 32) SHT. P2.13 - BOTTOM PLAN - KEYNOTE # 9 - SHOW THESE
 RISERS ON P2.09 AS NOTED. I CANNOT FIND THESE RISERS ON
 P2.09.CLEARLY IDENTIFY THESE RISERS. WPB AMEND. TO FBC
 SEC. 107.2.1.
 33) SHT. P2.09 SHOWS A SANITARY AND WATER LINE IN
 STAIRWELL #1. THIS IS NOT PERMITTED PER 2014
 FBC-BUILDING SEC. 1009.3.1.5.1.
 34) SHT. P4.01 - THE PLANS SHOW THE WASTE FROM THE
 ELEVATOR SUMPS DISCHARGING INTO THE GREASY WASTE
 SYSTEM. THIS IS NOT PERMITTED. THE ELEVATOR SUMPS ARE
 EQUIPPED WITH ALARMS. THIS DISCHARGE CAN GO TO THE
 SANITARY OR TO A SEPARATE OIL SEPARATOR IF DESIRED. FBC
 1003.3.1.
 35) SHT. P4.01 - RESTROOMS #209 & 210 AND ROOMS #235,
 236, 237 & 238 - THE RISER DOES NOT COMPLY WITH THE
 2014 FPC FOR WET VENTS OR CIRCUIT VENTS.
 36) A LINT INTERCEPTOR IS REQUIRED FOR THE LAUNDRY ROOM
 PER 2014 FPC SEC. 1003.6.
 37) SHTS. P4.01 & P4.02 - CLEARLY IDENTIFY THE
 CONTINUATION POINTS OF ALL VENTS.
 38) SHT. P4.02 - I CANNOT FIND KEYNOTE #1 ON THE PLAN.
 CLARIFY.
 39) SHT. P4.02 - CLARIFY THE DESIGN OF THE FIRST LEVEL
 SANITARY SYSTEM. IT DOES NOT COMPLY WITH THE 2014 FPC
 SEC. 912 FOR WET VENTS OR SEC. 914 FOR CIRCUIT VENTING.
 40) SHT. P4.02 - THE LAYOUT OF THE 5TH FLOOR SANITARY
 DOES NOT CORRELATE WITH THE FLOOR PLAN ON SHT. P2.08. -
 CLARIFY.
 41) SHT.P4.02 - THE 1ST LEVEL RISER SHOWS A PIECE OF
 KITCHEN EQUIPMENT DISCHARGING INTO THE SANITARY. THEY
 SHALL DISCHARGE INDIRECTLY INTO THE GREASE WASTE
 SYSTEM. FPC SEC. 1003.3.1.
 42) SHT. P4.02 - REFERS TO SHT. P5.01 FOR CONTINUATION
 OF SANITARY LINES AND VENTS. THERE ARE NO RISERS ON
 SHT. P5.01. CLARIFY.
 43) SHT. P4.03 - RISER S/2 - KEYNOTE #3 - THE
 REFERENCED VENT IS NOT IDENTIFIED ON SHT. P4.02.
 CLARIFY.
 44) SHT. P4.03 - RISER S/15 - THERE ARE NOT FIXTURES
 SHOWN ON THE STACK AND IT IS INCOMPLETE. PROVIDE THE
 ENTIRE RISER FOR REVIEW.
 45) SHT. P4.03 - RISER S/14 - RESTROOMS BY STAIR #2 -
 THE RISER DOES NOT COMPLY WITH THE FPC SEC. 912 OR SEC.
 914 FOR A HORIZONTAL WET VENT OR A CIRCUIT VENT.
 46) SHT. P4.04 - KEYNOTE #2 REFERS TO SHT. P4.03 FOR
 THE CONTINUATION OF WATER LINES. SHT.P4.03 IS SANITARY
 RISERS. KEYNOTE #2 DOES CORRELATE WITH WHAT IS SHOWN ON
 THE WATER RISER. SEE KEYNOTES #3 & #8 ALSO. CLARIFY.
 47) SHT. P4.05 - KEYNOTE #1 REFERS TO SHT. P4.03A.
 THERE IS NO SUCH SHEET. CLARIFY.
 48) SHT. P4.05 - SIZE ALL SECTIONS OF THE WATER RISER.
 SEE KEYNOTE #1 AND PIPING AT POINTS A & B.
 49) SHEET P4.05 - SHOW THE CONTINUATION POINTS OF THE
 "A" LINE. THE RISER APPEARS TO SHOW TWO LINES TURNED
 DOWN.
 50) SHT. P4.05 - KEYNOTE #5 DOES NOT APPEAR TO
 CORRELATE WITH THE RISER. CLARIFY.
 51) SHT. P4.05 - SHOW THE CONTINUATION POINT OF THE 140
 DEGREE WATER.
 52) SHT. P4.06 - WATER RISER #1 - BEVERAGE DISPENSERS,
 COFFEE MACHINES AND NONCARBONATED BEVERAGE DISPENSERS
 SHALL BE PROTECTED AGAINST BACKFLOW PER FPC SECS.
 608.16.1 & 608.16.10.
 53) SUBMIT A WATER RISER FOR THE TYPICAL KING ROOM. THE
 WATER RISER ON P4.07 IS FOR THE KING SUITE. WPB AMEND.
 TO FBC SEC. 107.3.5.1.3.
 54) SHT. P4.07 - DETAIL "C" THE WATER RISER SHOWS 2
 LAVATORIES IN EACH ROOM & SHT. P2.10 AND RISER S/12
 APPEAR TO SHOW ONE LAVATORY IN EACH ROOM. CLARIFY.
 55) SHT. P4.07 - DETAIL 'H" - IDENTIFY THE L/SK & SK ON
 THE WATER RISER. IF THESE ARE IN THE LAUNDRY ROOM
 INCLUDE THE LAUNDRY ROOM NUMBER ON THE DETAIL AND
 SUBMIT A COMPLETE WATER RISER FOR THE LAUNDRY.
 56) ALL FLOOR DRAINS SHALL HAVE TRAP PRIMERS. 2014 FPC
 SEC. 1002.4.
 57) SHT. P4.10 - SUPPLY THE TONS OF REFRIGERANT PER
 RISER. THE SIZING OF THE CONDENSATE RISERS SHALL COMPLY
 WITH FPC TABLE 314.2.2.
 58) THE FLOOR DRAINS RECEIVING THE DISCHARGE FROM THE
 ELEVATOR SUMPS SHALL BE EQUIPPED WITH TRAP PRIMERS.
 2014 FPC SEC.1002.4.
  
 NOTE: THE BUILDING CODE REQUIREMENTS FOR THE POOL
 EQUIPMENT ROOM WILL BE REVIEWED WHEN THE POOL PLANS ARE
 SUBMITTED.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805 PLUMBING PLAN REVIEW
 -6692
 [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  