2016-07-14 15:00:41REVIEW FBC-14 MECHANICAL
 PERMIT #16061443
 CANOPY HOTEL
 7/12/16
  
 NOTE: UNLESS NOTED OTHERWISE ALL COMMENTS REFERENCE THE
 FLORIDA BUILDING CODE FIFTH EDITION 2014 MECHANICAL.
  
 1) SUBMIT THE FOLLOWING LIST OF SUPPORTING DOCUMENTS
 FOR THE PROPOSED PROJECT:
  
 A) ENERGY CALCULATIONS- SECTION C101.2 & C401.2 FBC-14
 ENERGY CONSERVATION.
 B) SYSTEM COMMISSIONING PLAN- SECTION C408 FBC-14
 ENERGY CONSERVATION.
 C) SMOKE CONTROL SPECIAL INSPECTION AND TEST
 REQUIREMENTS REPORT- SECTION 513.3
 D) SMOKE CONTROL RATIONAL ANALYSIS- SECTION 513.4.
 E) AC COOLING AND HEATING CALCULATIONS- SECTION
 C403.2.1 FBC-14 ENERGY CONSERVATION (PLEASE NOTE THAT
 THE CALCULATIONS SUBMITTED DO NOT INCLUDE THESE
 SYSTEMS: OARTU-1, AHU'S 1-12, AND VRV SYSTEMS FC-2.9,
 FC-2.10, FC-3T-H, FC-13.1, & FC-13.2).
 F) AC CALCULATION SUBMITTAL PACKAGE: PLEASE PROVIDE A
 SIGNED AND SEALED INDEX SHEET LISTING ALL UNITS
 CONTAINED IN THE DOCUMENT.
 G) FLORIDA PRODUCT APPROVALS AND/OR MIAMI-DADE NOA'S
 FOR ALL EXHAUST OUTLET AND AIR INTAKE LOUVERS, ROOFTOP
 AND SIDEWALL FANS, AC ROOF STANDS AND WALL BRACKETS,
 ROOFTOP AC AND FAN CURBS. ALL SUBMITTALS SHALL BEAR THE
 SHOP DRAWING APPROVAL SIGNATURE BY THE ENGINEER OF
 RECORD.
 H) PRODUCT DATA SUBMITTALS FOR ALL SMOKE CONTROL FANS,
 FIRE AND FIRE/SMOKE DAMPERS, DUCT SMOKE DETECTORS,
 CARBON MONOXIDE DETECTORS, MOTORIZED DAMPERS, FLAMEBAR
 DUCTWORK, REFRIGERANT PIPING INSULATIONS, LAUNDRY
 APPLIANCES, KITCHEN COOKING APPLIANCES, KITCHEN EXHAUST
 HOODS AND FANS, VRV UNITS, AND BOILER AND BOILER VENT
 PIPING. ALL SUBMITTALS SHALL BEAR THE SHOP DRAWING
 APPROVAL STAMP AND SIGNATURES OF THE EOR.
  
 2) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES- TABLE 403.3. PROVIDE ON THE PLAN A
 SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDED CFMS
 OF OUTDOOR AIR FOR ALL ROOMS AND SPACES.
  
 3) PROVIDE EXHAUST VENTILATION CALCULATIONS INCLUDING A
 SCHEDULE ON THE PLAN INDICATING THE REQUIRED AND
 PROVIDED CFMS OF EXHAUST WHERE REQUIRED INCLUDING BUT
 NOT LIMITED TO THE PARKING GARAGES, THE GROUND FLOOR
 AND ROOFTOP KITCHENS, THE GENERATOR ROOM, THE LAUNDRY
 ROOM, SOILED LINEN ROOM, TRASH ROOM, JANITOR'S CLOSETS,
 POOL EQUIPMENT ROOM, LOCKER ROOMS ETC. PLEASE SEE TABLE
 403.3 AND SECTION 404 FBC-14 MECHANICAL, AND TABLE 6-4
 ASHRAE 62.1- 2010. A) THE PLAN INDICATES TOILET EXHAUST
 FROM THE GUEST ROOMS DISCHARGING INTO THE OARTU-1,
 HOWEVER PER TABLE 403.3 FOOTNOTE G, RECIRCULATION IS
 PROHIBITED EXCEPT THAT RECIRCULATION SHALL BE PERMITTED
 WHERE THE RESULTING SUPPLY AIRSTREAM CONSISTS OF NOT
 MORE THAN 10% AIR RECIRCULATED FROM THE TOILET ROOMS.
 PROVIDE CALCULATIONS TO VERIFY COMPLIANCE.
  
 4) PROVIDE AIR BALANCE CALCULATIONS- SECTION 501.4
  
 5) THE SUBMITTED AC CALCULATIONS ARE INCORRECTLY
 INDICATING MIAMI AS THE LOCATION OF THE PROJECT- PLEASE
 CORRECT.
  
 6) WHERE OUTDOOR AIR INTAKES ARE SHOWN ON THE
 MECHANICAL PLANS, PLEASE PROVIDE THE CLEARANCE DISTANCE
 MEASUREMENTS AS INDICATED IN SECTION 401.4. WHERE
 EXHAUST OUTLETS ARE SHOWN ON THE MECHANICAL PLANS
 PLEASE PROVIDE THE CLEARANCE DISTANCE MEASUREMENTS AS
 INDICATED IN SECTION 501.3.1.
  
 7) SHEET M201: ADVISORY- SEPARATE PERMITS ARE REQUIRED
 FOR COMMERCIAL KITCHEN EXHAUST AND FIRE SUPPRESSION
 SYSTEMS, AND WALK-IN COOLERS AND FREEZERS- PLEASE PLACE
 A NOTE IN BOLD LETTERS ON THE PLANS.
  
 8) M201: SEE FIRE PLAN REVIEW COMMENTS CITING NFPA 101
 FOR PROHIBITION OF THE DUCTS SHOWN IN THE FIRE PUMP
 ROOM, AND SECTION 1023.6 FBC-14 BUILDING PROHIBITING
 THE DUCT AND DIFFUSER SHOWN IN THE EXIT PASSAGEWAY OF
 STAIR #1.
  
 9) A722 & M201: IT APPEARS THAT THE LOCATION OF THE
 GREASE EXHAUST TERMINATIONS FOR KEF 1 & 2 SHOWN ON THE
 PLAN BY THE FPL VAULT WOULD NOT MEET COMPLIANCE WITH
 REQUIRED DISCHARGE CLEARANCES AS OUTLINED IN SECTIONS
 506.3.13.2, 506.3.13.3, & 501.3.1 PLEASE PROVIDE
 ADDITIONAL INFORMATION INCLUDING CLEARANCE DISTANCE
 MEASUREMENTS, DETAILS, AND NOTES. PLEASE NOTE THAT KEF
 1, 2, & 3 AND KSF 1 & 2 WILL BE UNDER SEPARATE PERMIT
 WITH THE KITCHEN HOODS, HOWEVER SOME ISSUES MUST BE
 ADDRESSED ON THE MAIN PLANS FOR CONSTRUCTION PURPOSES.
 REVIEW SECTIONS 506, 507, & 508 AND PROVIDE ALL
 APPLICABLE DETAILS AND NOTES ON THE MAIN PLANS.
 ADDITIONALLY, PROVIDE AN INSTALLATION DETAIL FOR
 INSTALLATION OF KEF-1 WHICH IS LISTED AT 2260 LBS. ON
 THE SCHEDULE.
  
 10) M201: PROVIDE THE DUCT TRUNK SIZES FOR THE AC
 SUPPLY AND RETURN SYSTEMS, THE KITCHEN SUPPLY AND
 EXHAUST SYSTEMS, THE RESTROOM AND JANITOR EXHAUST
 SYSTEMS, AND THE O/A AIR SYSTEMS.
  
 11) M201: DUCT SMOKE DETECTORS ARE REQUIRED IN THE
 RETURN AIR SYSTEMS OF FC-1.3, 1.5, 1.6, 1.7, 1.8-
 SECTION 606.2.1.
  
 12) M201: INDICATE HOW ACCESS FOR MAINTENANCE AND
 REPLACEMENT OF UNITS FC-1.2, 1.3, & 1.4, 1.7, & 1.8
 SHOWN ABOVE DRYWALL CEILINGS ON SHEET A301 WILL BE
 PROVIDED- SECTION 306.1. PLEASE SHOW ACCESS PANEL
 LOCATIONS WHERE REQUIRED AND PROVIDE CONSTRUCTION
 DETAILS.
  
 13) M201: THE RESTROOMS FAN EF-1.1 IS NOT SHOWN IN THE
 SCHEDULE ON M601. PLEASE PROVIDE A SEQUENCE OF
 OPERATION FOR THE FAN- SEE TABLE 403.3
  
 14) M201: PROVIDE AN EXHAUST VENTILATION SYSTEM FOR THE
 TRASH ROOM 112 AND THE JANITOR'S CLOSET 118 - TABLE 6-4
 ASHRAE 62.1-2010.
  
 15) M201: CORRIDORS 109 AND 113 SHALL NOT BE USED AS
 RETURN AIR DUCTS FOR AIR BEING SUPPLIED TO ENGINEERING
 110 & DRY STORAGE 124; AND CORRIDOR 133 SHALL NOT
 TRANSFER AIR TO CORRIDOR 129- SEE SECTION 601.2.
  
 16 ) M201: REFER TO SECTION 304 FBC-14 FUEL GAS AND
 PROVIDE COMBUSTION AIR CALCULATIONS FOR ALL GAS-FIRED
 COOKING APPLIANCES AND EQUIPMENT. INDICATE HOW THE
 COMBUSTION IS BEING SUPPLIED AND SEE SECTION 304.9.3
 FOR COMBUSTION AIR BEING SUPPLIED BY MECHANICAL
 SYSTEMS.
  
 17) M201: AS PREVIOUSLY NOTED, EXHAUST VENTILATION
 CALCULATIONS ARE REQUIRED FOR THE KITCHEN AND
 RECIRCULATION OF AIR FROM THOS SPACE IS PROHIBITED PER
 TABLE 403.3 FOOTNOTE B.
  
 18) M202 & A1.12. : FIRE DAMPERS MISSING AT THESE
 LOCATIONS- THE O/A DUCTS PENETRATING THE LAUNDRY ROOM
 WALLS, AC DUCTS PENETRATING WALLS AT THE LINEN STORAGE
 228, HOUSEKEEPING 229, STORAGE 223, STORAGE 213. PLEASE
 NOTE THERE ARE FIRE DAMPERS AT DUCTS PENETRATING WALLS
 ON THE MECHANICAL PLAN THAT ARE NOT SHOWN AS FIRE-RATED
 WALLS ON THE LIFE SAFETY PLAN.
  
 19) M202: THE LENGTH OF THE DRYER EXHAUST DUCTS ARE
 EXCEEDING THE MAXIMUM ALLOWABLE 35 FT. LENGTH PER
 SECTION 504.6.4.1, AND CAN ONLY BE APPROVED AS SHOWN IF
 THEY CONFORM TO MANUFACTURER'S INSTALLATION
 INSTRUCTIONS AS NOTED IN SECTION 504.6.2. PLEASE SUBMIT
 MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS FOR THE DRYERS AND THE IRONER.
 A) INDICATE THE TYPE AND GAGE OF DRYER AND IRONER
 EXHAUST DUCT, AND PROVIDE SUPPORT AND CONNECTION
 DETAILS. B) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 DRYERS PER SECTION 304 FBC-14 FUEL GAS. C) REVISE SHEET
 A401 TO SHOW EXHAUST OUTLET LOCATIONS ON THE ELEVATION
 DRAWING.
  
 20) M202: EXHAUST VENTILATION IS REQUIRED FOR THE
 KITCHEN (WARMING AREA 226) PER TABLE 403.3, AND TABLE
 6-4 ASHRAE 62.1-2010. PLEASE NOTE THAT PER FOOTNOTE B
 RECIRCULATION OF AIR FROM THE KITCHEN IS PROHIBITED.
  
 21) M202: THERE IS A TRANSFER DUCT RETURNING AIR INTO
 CORRIDOR 224, HOWEVER THE CORRIDOR SHALL NOT BE USED AS
 A RETURN AIR DUCT PER SECTION 601.2.
  
 22) M202: INDICATE HOW ACCESS FOR MAINTENANCE AND
 REPLACEMENT OF THE FAN COIL UNITS AND LAUNDRY MAKEUP
 AIR FANS WILL BE PROVIDED- SECTION 306.1. SHOW ACCESS
 PANEL LOCATIONS WHERE REQUIRED AND PROVIDE CONSTRUCTION
 DETAILS.
  
 23) M201 & M202: CLARIFY HOW ACCESS TO FD'S AND FSD'S
 WILL BE PROVIDED WHERE DAMPERS ARE IN CONCEALED
 LOCATIONS ABOVE HARD CEILINGS. SHOW LOCATIONS OF ACCESS
 PANELS AND PROVIDE CONSTRUCTION DETAILS.
  
 24) M202 & M601: PROVIDE AN EQUIPMENT SCHEDULE FOR
 EF-2.1. NOTE: SCHEDULES WILL BE REQUIRED FOR THE
 BOOSTER FANS IF THE UNITS ARE APPROVED FOR USE.
  
 25) M203, M204, M205- PARKING GARAGES: A) AS PREVIOUSLY
 REQUESTED IN THIS REVIEW PROVIDE EXHAUST VENTILATION
 CALCULATIONS FOR THE GARAGES PER TABLE 403.3 AND
 SECTION 404. B) CLARIFY HOW EXHAUST VENTILATION WILL BE
 PROVIDED AND SEQUENCED FOR THE AUTOMOBILE HOISTWAYS AND
 PROVIDE A CALCULATION. THE CURRENT PLAN IS NOT
 PROVIDING ANY HVAC NOTES OR DETAILS- SEE SECTION 404,
 AND SECTION 3004.1 FBC-14 BUILDING. C) PROVIDE MORE
 SPECIFIC INFORMATION FOR THE SEQUENCE OF OPERATIONS
 SHOWN ON M203- SEE SECTION 404.2 AND INDICATE WHICH FAN
 ON EACH FLOOR IS TO RUN AT ALL TIMES AND PROVIDE A
 CALCULATION TO VERIFY THE REQUIRED MINIMUM RATE OF .05
 CFM PER SQUARE FOOT WILL BE ACCOMPLISHED. D) SOME OF
 THE CIRCULATION FANS (CF-1) APPEAR TO BE LOCATED IN
 VEHICLE DRIVE AND PARKING AREAS. INDICATE THE HEIGHT
 FROM THE FINISH FLOOR TO THE BOTTOM OF THE FANS PER
 SECTION 304.6.
  
 26) M203: PLEASE PLACE A NOTE ON THE PLANS INDICATING
 THE EMERGENCY GENERATOR WILL BE DONE UNDER SEPARATE
 PERMIT.
  
 27) M205: AS PREVIOUSLY REQUESTED, SUBMIT
 MANUFACTURER'S SPECIFICATIONS FOR THE FLAMEBAR DUCT
 WITH SHOP DRAWING APPROVAL SIGNATURE BY THE EOR. A)
 PROVIDE A UL TESTED AND APPROVED FIRESTOPPING DETAIL
 FOR WALL AND CEILING PENETRATIONS.
  
 28) M206, M207, M208: FIRE/SMOKE DAMPERS NOT SHOWN FOR
 O/A DUCTS PENETRATING THE CORRIDORS/GUEST ROOM WALLS-
 SEE SECTION 513.5.2 AND 607.5.4.
  
 29) M206, M207, M208: CLARIFY HOW AIR IS BEING RETURNED
 TO EACH FC SHOWN ON THE PLANS- NO RETURN GRILLS ARE
 SHOWN ON THE PLANS.
  
 30) M206, M207, M208: INDICATE HOW ACCESS FOR
 MAINTENANCE AND REPLACEMENT OF THE FAN COIL UNITS WILL
 BE PROVIDED ABOVE THE DRYWALL CEILINGS- SECTION 306.1.
 SHOW ACCESS PANEL LOCATIONS AND PROVIDE CONSTRUCTION
 DETAILS.
  
 31) M208A: THE ACCESS HATCHES SHOWN IN THE STAIRWAY
 ENCLOSURES ARE NOT PERMITTED PER SECTION 1022.4 FBC-14
 BUILDING.
  
 32) M209: PROVIDE EQUIPMENT SCHEDULES FOR FC-13.1 &
 13.2, AND EF-13.1, 13.2, & 13.3.
  
 33) M209: PROVIDE AN EXHAUST VENTILATION CALCULATION
 FOR THE COMMERCIAL KITCHEN. THE PLAN INDICATES AIR
 BEING RECIRCULATED IN THE KITCHEN WHICH IS PROHIBITED
 PER TABLE 403.3 FOOTNOTE B.
  
 34) M209: A DUCT SMOKE DETECTOR IS REQUIRED IN THE
 RETURN AIR SYSTEM OF FC-13.2. PROVIDE A SYMBOL ON THE
 PLAN AND PROVIDE DETAILS.
  
 35) M209: PROVIDE AN EXHAUST VENTILATION CALCULATION
 FOR THE POOL EQUIPMENT ROOM AND COMBUSTION AIR
 CALCULATIONS FOR GAS-FIRED POOL EQUIPMENT- SECTION 304
 FBC-14 FUEL GAS.
  
 36) M210: PROVIDE EXHAUST VENTILATION AND COMBUSTION
 AIR CALCULATIONS FOR THE ROOFTOP BOILER AND PUMP ROOM-
 REFER TO SECTION 304 FBC-14 FUEL GAS, AND SUBMIT
 MANUFACTURER?S SPECIFICATIONS FOR THE BOILERS AND
 BOILER VENTING
  
 37) M2.10: REFER TO SECTION 301.15 AND PROVIDE COMPLETE
 ENGINEERED DETAILS FOR TIE DOWN OF ALL THE ROOF TOP
 MECHANICAL EQUIPMENT INCLUDING BUT NOT LIMITED TO THE
 PRESSURIZATION AND SMOKE EXHAUST FANS AND CURBS, THE
 OARTU AND CURB, THE CU'S, CU ROOF STANDS, THE MD
 WEATHERHOODS, AND EXTERIOR DUCTWORK. PLEASE NOTE THE
 DETAILS ON SHEET M703 ARE INCOMPLETE.
  
 38) PROVIDE A SEQUENCE OF OPERATION FOR THE OARTU-1.
 CLARIFY HOW OUTDOOR AIR WILL BE SUPPLIED TO ALL THE
 VARIOUS FAN COIL UNITS IN THE ROOMS AND COMMON AREAS.
 WILL THE SYSTEMS BE DIGITALLY CONTROLLED? PLEASE REFER
 TO SECTION C403.2.4.4 FBC-14 ENERGY CONSERVATION.
  
 39) REFER TO SECTION C403.2.5.1 FBC-14 ENERGY
 CONSERVATION- DEMAND CONTROLLED VENTILATION IS REQUIRED
 FOR THE RESTAURANT AND THE MEETING ROOMS. INDICATE HOW
 COMPLIANCE WILL BE MET AND PROVIDE DETAILS.
  
 40) M501: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 VRV UNITS WITH ALLOWABLE LENGTH TABLES FOR REFRIGERANT
 PIPING.
  
 41) M801: AS PREVIOUSLY NOTED, A RATIONAL ANALYSIS AND
 CALCULATIONS MUST BE SUBMITTED FOR THE SMOKE CONTROL
 SYSTEM.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  