2016-07-14 15:00:41 | REVIEW FBC-14 MECHANICAL |
| PERMIT #16061443 |
| CANOPY HOTEL |
| 7/12/16 |
| |
| NOTE: UNLESS NOTED OTHERWISE ALL COMMENTS REFERENCE THE |
| FLORIDA BUILDING CODE FIFTH EDITION 2014 MECHANICAL. |
| |
| 1) SUBMIT THE FOLLOWING LIST OF SUPPORTING DOCUMENTS |
| FOR THE PROPOSED PROJECT: |
| |
| A) ENERGY CALCULATIONS- SECTION C101.2 & C401.2 FBC-14 |
| ENERGY CONSERVATION. |
| B) SYSTEM COMMISSIONING PLAN- SECTION C408 FBC-14 |
| ENERGY CONSERVATION. |
| C) SMOKE CONTROL SPECIAL INSPECTION AND TEST |
| REQUIREMENTS REPORT- SECTION 513.3 |
| D) SMOKE CONTROL RATIONAL ANALYSIS- SECTION 513.4. |
| E) AC COOLING AND HEATING CALCULATIONS- SECTION |
| C403.2.1 FBC-14 ENERGY CONSERVATION (PLEASE NOTE THAT |
| THE CALCULATIONS SUBMITTED DO NOT INCLUDE THESE |
| SYSTEMS: OARTU-1, AHU'S 1-12, AND VRV SYSTEMS FC-2.9, |
| FC-2.10, FC-3T-H, FC-13.1, & FC-13.2). |
| F) AC CALCULATION SUBMITTAL PACKAGE: PLEASE PROVIDE A |
| SIGNED AND SEALED INDEX SHEET LISTING ALL UNITS |
| CONTAINED IN THE DOCUMENT. |
| G) FLORIDA PRODUCT APPROVALS AND/OR MIAMI-DADE NOA'S |
| FOR ALL EXHAUST OUTLET AND AIR INTAKE LOUVERS, ROOFTOP |
| AND SIDEWALL FANS, AC ROOF STANDS AND WALL BRACKETS, |
| ROOFTOP AC AND FAN CURBS. ALL SUBMITTALS SHALL BEAR THE |
| SHOP DRAWING APPROVAL SIGNATURE BY THE ENGINEER OF |
| RECORD. |
| H) PRODUCT DATA SUBMITTALS FOR ALL SMOKE CONTROL FANS, |
| FIRE AND FIRE/SMOKE DAMPERS, DUCT SMOKE DETECTORS, |
| CARBON MONOXIDE DETECTORS, MOTORIZED DAMPERS, FLAMEBAR |
| DUCTWORK, REFRIGERANT PIPING INSULATIONS, LAUNDRY |
| APPLIANCES, KITCHEN COOKING APPLIANCES, KITCHEN EXHAUST |
| HOODS AND FANS, VRV UNITS, AND BOILER AND BOILER VENT |
| PIPING. ALL SUBMITTALS SHALL BEAR THE SHOP DRAWING |
| APPROVAL STAMP AND SIGNATURES OF THE EOR. |
| |
| 2) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL |
| ROOMS AND SPACES- TABLE 403.3. PROVIDE ON THE PLAN A |
| SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDED CFMS |
| OF OUTDOOR AIR FOR ALL ROOMS AND SPACES. |
| |
| 3) PROVIDE EXHAUST VENTILATION CALCULATIONS INCLUDING A |
| SCHEDULE ON THE PLAN INDICATING THE REQUIRED AND |
| PROVIDED CFMS OF EXHAUST WHERE REQUIRED INCLUDING BUT |
| NOT LIMITED TO THE PARKING GARAGES, THE GROUND FLOOR |
| AND ROOFTOP KITCHENS, THE GENERATOR ROOM, THE LAUNDRY |
| ROOM, SOILED LINEN ROOM, TRASH ROOM, JANITOR'S CLOSETS, |
| POOL EQUIPMENT ROOM, LOCKER ROOMS ETC. PLEASE SEE TABLE |
| 403.3 AND SECTION 404 FBC-14 MECHANICAL, AND TABLE 6-4 |
| ASHRAE 62.1- 2010. A) THE PLAN INDICATES TOILET EXHAUST |
| FROM THE GUEST ROOMS DISCHARGING INTO THE OARTU-1, |
| HOWEVER PER TABLE 403.3 FOOTNOTE G, RECIRCULATION IS |
| PROHIBITED EXCEPT THAT RECIRCULATION SHALL BE PERMITTED |
| WHERE THE RESULTING SUPPLY AIRSTREAM CONSISTS OF NOT |
| MORE THAN 10% AIR RECIRCULATED FROM THE TOILET ROOMS. |
| PROVIDE CALCULATIONS TO VERIFY COMPLIANCE. |
| |
| 4) PROVIDE AIR BALANCE CALCULATIONS- SECTION 501.4 |
| |
| 5) THE SUBMITTED AC CALCULATIONS ARE INCORRECTLY |
| INDICATING MIAMI AS THE LOCATION OF THE PROJECT- PLEASE |
| CORRECT. |
| |
| 6) WHERE OUTDOOR AIR INTAKES ARE SHOWN ON THE |
| MECHANICAL PLANS, PLEASE PROVIDE THE CLEARANCE DISTANCE |
| MEASUREMENTS AS INDICATED IN SECTION 401.4. WHERE |
| EXHAUST OUTLETS ARE SHOWN ON THE MECHANICAL PLANS |
| PLEASE PROVIDE THE CLEARANCE DISTANCE MEASUREMENTS AS |
| INDICATED IN SECTION 501.3.1. |
| |
| 7) SHEET M201: ADVISORY- SEPARATE PERMITS ARE REQUIRED |
| FOR COMMERCIAL KITCHEN EXHAUST AND FIRE SUPPRESSION |
| SYSTEMS, AND WALK-IN COOLERS AND FREEZERS- PLEASE PLACE |
| A NOTE IN BOLD LETTERS ON THE PLANS. |
| |
| 8) M201: SEE FIRE PLAN REVIEW COMMENTS CITING NFPA 101 |
| FOR PROHIBITION OF THE DUCTS SHOWN IN THE FIRE PUMP |
| ROOM, AND SECTION 1023.6 FBC-14 BUILDING PROHIBITING |
| THE DUCT AND DIFFUSER SHOWN IN THE EXIT PASSAGEWAY OF |
| STAIR #1. |
| |
| 9) A722 & M201: IT APPEARS THAT THE LOCATION OF THE |
| GREASE EXHAUST TERMINATIONS FOR KEF 1 & 2 SHOWN ON THE |
| PLAN BY THE FPL VAULT WOULD NOT MEET COMPLIANCE WITH |
| REQUIRED DISCHARGE CLEARANCES AS OUTLINED IN SECTIONS |
| 506.3.13.2, 506.3.13.3, & 501.3.1 PLEASE PROVIDE |
| ADDITIONAL INFORMATION INCLUDING CLEARANCE DISTANCE |
| MEASUREMENTS, DETAILS, AND NOTES. PLEASE NOTE THAT KEF |
| 1, 2, & 3 AND KSF 1 & 2 WILL BE UNDER SEPARATE PERMIT |
| WITH THE KITCHEN HOODS, HOWEVER SOME ISSUES MUST BE |
| ADDRESSED ON THE MAIN PLANS FOR CONSTRUCTION PURPOSES. |
| REVIEW SECTIONS 506, 507, & 508 AND PROVIDE ALL |
| APPLICABLE DETAILS AND NOTES ON THE MAIN PLANS. |
| ADDITIONALLY, PROVIDE AN INSTALLATION DETAIL FOR |
| INSTALLATION OF KEF-1 WHICH IS LISTED AT 2260 LBS. ON |
| THE SCHEDULE. |
| |
| 10) M201: PROVIDE THE DUCT TRUNK SIZES FOR THE AC |
| SUPPLY AND RETURN SYSTEMS, THE KITCHEN SUPPLY AND |
| EXHAUST SYSTEMS, THE RESTROOM AND JANITOR EXHAUST |
| SYSTEMS, AND THE O/A AIR SYSTEMS. |
| |
| 11) M201: DUCT SMOKE DETECTORS ARE REQUIRED IN THE |
| RETURN AIR SYSTEMS OF FC-1.3, 1.5, 1.6, 1.7, 1.8- |
| SECTION 606.2.1. |
| |
| 12) M201: INDICATE HOW ACCESS FOR MAINTENANCE AND |
| REPLACEMENT OF UNITS FC-1.2, 1.3, & 1.4, 1.7, & 1.8 |
| SHOWN ABOVE DRYWALL CEILINGS ON SHEET A301 WILL BE |
| PROVIDED- SECTION 306.1. PLEASE SHOW ACCESS PANEL |
| LOCATIONS WHERE REQUIRED AND PROVIDE CONSTRUCTION |
| DETAILS. |
| |
| 13) M201: THE RESTROOMS FAN EF-1.1 IS NOT SHOWN IN THE |
| SCHEDULE ON M601. PLEASE PROVIDE A SEQUENCE OF |
| OPERATION FOR THE FAN- SEE TABLE 403.3 |
| |
| 14) M201: PROVIDE AN EXHAUST VENTILATION SYSTEM FOR THE |
| TRASH ROOM 112 AND THE JANITOR'S CLOSET 118 - TABLE 6-4 |
| ASHRAE 62.1-2010. |
| |
| 15) M201: CORRIDORS 109 AND 113 SHALL NOT BE USED AS |
| RETURN AIR DUCTS FOR AIR BEING SUPPLIED TO ENGINEERING |
| 110 & DRY STORAGE 124; AND CORRIDOR 133 SHALL NOT |
| TRANSFER AIR TO CORRIDOR 129- SEE SECTION 601.2. |
| |
| 16 ) M201: REFER TO SECTION 304 FBC-14 FUEL GAS AND |
| PROVIDE COMBUSTION AIR CALCULATIONS FOR ALL GAS-FIRED |
| COOKING APPLIANCES AND EQUIPMENT. INDICATE HOW THE |
| COMBUSTION IS BEING SUPPLIED AND SEE SECTION 304.9.3 |
| FOR COMBUSTION AIR BEING SUPPLIED BY MECHANICAL |
| SYSTEMS. |
| |
| 17) M201: AS PREVIOUSLY NOTED, EXHAUST VENTILATION |
| CALCULATIONS ARE REQUIRED FOR THE KITCHEN AND |
| RECIRCULATION OF AIR FROM THOS SPACE IS PROHIBITED PER |
| TABLE 403.3 FOOTNOTE B. |
| |
| 18) M202 & A1.12. : FIRE DAMPERS MISSING AT THESE |
| LOCATIONS- THE O/A DUCTS PENETRATING THE LAUNDRY ROOM |
| WALLS, AC DUCTS PENETRATING WALLS AT THE LINEN STORAGE |
| 228, HOUSEKEEPING 229, STORAGE 223, STORAGE 213. PLEASE |
| NOTE THERE ARE FIRE DAMPERS AT DUCTS PENETRATING WALLS |
| ON THE MECHANICAL PLAN THAT ARE NOT SHOWN AS FIRE-RATED |
| WALLS ON THE LIFE SAFETY PLAN. |
| |
| 19) M202: THE LENGTH OF THE DRYER EXHAUST DUCTS ARE |
| EXCEEDING THE MAXIMUM ALLOWABLE 35 FT. LENGTH PER |
| SECTION 504.6.4.1, AND CAN ONLY BE APPROVED AS SHOWN IF |
| THEY CONFORM TO MANUFACTURER'S INSTALLATION |
| INSTRUCTIONS AS NOTED IN SECTION 504.6.2. PLEASE SUBMIT |
| MANUFACTURER'S SPECIFICATIONS AND INSTALLATION |
| INSTRUCTIONS FOR THE DRYERS AND THE IRONER. |
| A) INDICATE THE TYPE AND GAGE OF DRYER AND IRONER |
| EXHAUST DUCT, AND PROVIDE SUPPORT AND CONNECTION |
| DETAILS. B) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE |
| DRYERS PER SECTION 304 FBC-14 FUEL GAS. C) REVISE SHEET |
| A401 TO SHOW EXHAUST OUTLET LOCATIONS ON THE ELEVATION |
| DRAWING. |
| |
| 20) M202: EXHAUST VENTILATION IS REQUIRED FOR THE |
| KITCHEN (WARMING AREA 226) PER TABLE 403.3, AND TABLE |
| 6-4 ASHRAE 62.1-2010. PLEASE NOTE THAT PER FOOTNOTE B |
| RECIRCULATION OF AIR FROM THE KITCHEN IS PROHIBITED. |
| |
| 21) M202: THERE IS A TRANSFER DUCT RETURNING AIR INTO |
| CORRIDOR 224, HOWEVER THE CORRIDOR SHALL NOT BE USED AS |
| A RETURN AIR DUCT PER SECTION 601.2. |
| |
| 22) M202: INDICATE HOW ACCESS FOR MAINTENANCE AND |
| REPLACEMENT OF THE FAN COIL UNITS AND LAUNDRY MAKEUP |
| AIR FANS WILL BE PROVIDED- SECTION 306.1. SHOW ACCESS |
| PANEL LOCATIONS WHERE REQUIRED AND PROVIDE CONSTRUCTION |
| DETAILS. |
| |
| 23) M201 & M202: CLARIFY HOW ACCESS TO FD'S AND FSD'S |
| WILL BE PROVIDED WHERE DAMPERS ARE IN CONCEALED |
| LOCATIONS ABOVE HARD CEILINGS. SHOW LOCATIONS OF ACCESS |
| PANELS AND PROVIDE CONSTRUCTION DETAILS. |
| |
| 24) M202 & M601: PROVIDE AN EQUIPMENT SCHEDULE FOR |
| EF-2.1. NOTE: SCHEDULES WILL BE REQUIRED FOR THE |
| BOOSTER FANS IF THE UNITS ARE APPROVED FOR USE. |
| |
| 25) M203, M204, M205- PARKING GARAGES: A) AS PREVIOUSLY |
| REQUESTED IN THIS REVIEW PROVIDE EXHAUST VENTILATION |
| CALCULATIONS FOR THE GARAGES PER TABLE 403.3 AND |
| SECTION 404. B) CLARIFY HOW EXHAUST VENTILATION WILL BE |
| PROVIDED AND SEQUENCED FOR THE AUTOMOBILE HOISTWAYS AND |
| PROVIDE A CALCULATION. THE CURRENT PLAN IS NOT |
| PROVIDING ANY HVAC NOTES OR DETAILS- SEE SECTION 404, |
| AND SECTION 3004.1 FBC-14 BUILDING. C) PROVIDE MORE |
| SPECIFIC INFORMATION FOR THE SEQUENCE OF OPERATIONS |
| SHOWN ON M203- SEE SECTION 404.2 AND INDICATE WHICH FAN |
| ON EACH FLOOR IS TO RUN AT ALL TIMES AND PROVIDE A |
| CALCULATION TO VERIFY THE REQUIRED MINIMUM RATE OF .05 |
| CFM PER SQUARE FOOT WILL BE ACCOMPLISHED. D) SOME OF |
| THE CIRCULATION FANS (CF-1) APPEAR TO BE LOCATED IN |
| VEHICLE DRIVE AND PARKING AREAS. INDICATE THE HEIGHT |
| FROM THE FINISH FLOOR TO THE BOTTOM OF THE FANS PER |
| SECTION 304.6. |
| |
| 26) M203: PLEASE PLACE A NOTE ON THE PLANS INDICATING |
| THE EMERGENCY GENERATOR WILL BE DONE UNDER SEPARATE |
| PERMIT. |
| |
| 27) M205: AS PREVIOUSLY REQUESTED, SUBMIT |
| MANUFACTURER'S SPECIFICATIONS FOR THE FLAMEBAR DUCT |
| WITH SHOP DRAWING APPROVAL SIGNATURE BY THE EOR. A) |
| PROVIDE A UL TESTED AND APPROVED FIRESTOPPING DETAIL |
| FOR WALL AND CEILING PENETRATIONS. |
| |
| 28) M206, M207, M208: FIRE/SMOKE DAMPERS NOT SHOWN FOR |
| O/A DUCTS PENETRATING THE CORRIDORS/GUEST ROOM WALLS- |
| SEE SECTION 513.5.2 AND 607.5.4. |
| |
| 29) M206, M207, M208: CLARIFY HOW AIR IS BEING RETURNED |
| TO EACH FC SHOWN ON THE PLANS- NO RETURN GRILLS ARE |
| SHOWN ON THE PLANS. |
| |
| 30) M206, M207, M208: INDICATE HOW ACCESS FOR |
| MAINTENANCE AND REPLACEMENT OF THE FAN COIL UNITS WILL |
| BE PROVIDED ABOVE THE DRYWALL CEILINGS- SECTION 306.1. |
| SHOW ACCESS PANEL LOCATIONS AND PROVIDE CONSTRUCTION |
| DETAILS. |
| |
| 31) M208A: THE ACCESS HATCHES SHOWN IN THE STAIRWAY |
| ENCLOSURES ARE NOT PERMITTED PER SECTION 1022.4 FBC-14 |
| BUILDING. |
| |
| 32) M209: PROVIDE EQUIPMENT SCHEDULES FOR FC-13.1 & |
| 13.2, AND EF-13.1, 13.2, & 13.3. |
| |
| 33) M209: PROVIDE AN EXHAUST VENTILATION CALCULATION |
| FOR THE COMMERCIAL KITCHEN. THE PLAN INDICATES AIR |
| BEING RECIRCULATED IN THE KITCHEN WHICH IS PROHIBITED |
| PER TABLE 403.3 FOOTNOTE B. |
| |
| 34) M209: A DUCT SMOKE DETECTOR IS REQUIRED IN THE |
| RETURN AIR SYSTEM OF FC-13.2. PROVIDE A SYMBOL ON THE |
| PLAN AND PROVIDE DETAILS. |
| |
| 35) M209: PROVIDE AN EXHAUST VENTILATION CALCULATION |
| FOR THE POOL EQUIPMENT ROOM AND COMBUSTION AIR |
| CALCULATIONS FOR GAS-FIRED POOL EQUIPMENT- SECTION 304 |
| FBC-14 FUEL GAS. |
| |
| 36) M210: PROVIDE EXHAUST VENTILATION AND COMBUSTION |
| AIR CALCULATIONS FOR THE ROOFTOP BOILER AND PUMP ROOM- |
| REFER TO SECTION 304 FBC-14 FUEL GAS, AND SUBMIT |
| MANUFACTURER?S SPECIFICATIONS FOR THE BOILERS AND |
| BOILER VENTING |
| |
| 37) M2.10: REFER TO SECTION 301.15 AND PROVIDE COMPLETE |
| ENGINEERED DETAILS FOR TIE DOWN OF ALL THE ROOF TOP |
| MECHANICAL EQUIPMENT INCLUDING BUT NOT LIMITED TO THE |
| PRESSURIZATION AND SMOKE EXHAUST FANS AND CURBS, THE |
| OARTU AND CURB, THE CU'S, CU ROOF STANDS, THE MD |
| WEATHERHOODS, AND EXTERIOR DUCTWORK. PLEASE NOTE THE |
| DETAILS ON SHEET M703 ARE INCOMPLETE. |
| |
| 38) PROVIDE A SEQUENCE OF OPERATION FOR THE OARTU-1. |
| CLARIFY HOW OUTDOOR AIR WILL BE SUPPLIED TO ALL THE |
| VARIOUS FAN COIL UNITS IN THE ROOMS AND COMMON AREAS. |
| WILL THE SYSTEMS BE DIGITALLY CONTROLLED? PLEASE REFER |
| TO SECTION C403.2.4.4 FBC-14 ENERGY CONSERVATION. |
| |
| 39) REFER TO SECTION C403.2.5.1 FBC-14 ENERGY |
| CONSERVATION- DEMAND CONTROLLED VENTILATION IS REQUIRED |
| FOR THE RESTAURANT AND THE MEETING ROOMS. INDICATE HOW |
| COMPLIANCE WILL BE MET AND PROVIDE DETAILS. |
| |
| 40) M501: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| VRV UNITS WITH ALLOWABLE LENGTH TABLES FOR REFRIGERANT |
| PIPING. |
| |
| 41) M801: AS PREVIOUSLY NOTED, A RATIONAL ANALYSIS AND |
| CALCULATIONS MUST BE SUBMITTED FOR THE SMOKE CONTROL |
| SYSTEM. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |
| 561-805-6719 |
| [email protected] |
| |