Plan Review Notes
Plan Review Notes For Permit 16061443
Permit Number 16061443
Review Stop G
Sequence Number 1
Notes
Date Text
2016-08-16 13:47:46GAS REVIEW
 1) SHT. P4.10 - GAS GENERAL NOTES ? AFTER THE SECOND
 STAGE REGULATOR PRESSURE IS NOTED AS 2 PSI YET THE
 TABLE THAT IS REFERENCED IS FOR LESS THAN A 2 PSI
 SYSTEM (402.4) (2). REVISE THE NOTE.
 2) SHOW THE DEVELOPED LENGTH OF THE PIPING FROM THE
 SECOND STAGE REGULATOR TO THE FURTHEST OUTLET. THIS
 DISTANCE IS USED FOR THE SIZING OF THE LOW PRESSURE
 SYSTEM.
 3) SHT. P4.10 - THE BTU LOAD FOR THE TWO DOMESTIC
 BOILERS ADDS TO 1,500 MBTU BUT THE PLANS SHOW 1,700
 MBTU. CLARIFY.
 4) SHT. P4.10 - KEYNOTE #10 SHOWS TWO BOILERS AT 199
 MBTU EACH WHICH IS 398 MBTU BUT THE RISER SHOWS 798
 MBTU. CLARIFY.
 5) MY CALCULATION OF BTU'S AT ONE SECTION OF THE GAS
 RISER IS 1,898 MBTU BUT THE PLAN SHOWS 2,498 MBTU.
 THERE IS ANOTHER SECTION WITH A BTU LOAD OF 3,698 MBTU
 AND MY CALCULATIONS ADD TO 3,098 MBTU. CLARIFY.
 6) THE TOTAL BTU LOAD ON THE SYSTEM SHOULD BE 4,413
 MBTU. PLEASE CHECK THE CALCULATIONS.
 7) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR THE
 GAS REGULATORS. FGC SEC. 410.1, 410.2.
 8) SUBMIT MANUF. SPECIFICATION SHEETS FOR THE ALL GAS
 EQUIPMENT AND APPLIANCES. APPLIANCES REGULATED BY THE
 CODE SHALL BE LISTED AND LABELED. FGC 301.3.
 9) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR ALL GAS
 FIRED EQUIPMENT (KITCHEN EQUIPMENT, DRYERS, POOL
 EQUIPMENT, BOILERS, ETC.) PER FGC SEC. 304. SEE FGC
 SEC. 304.9.3 FOR COMBUSTION AIR BEING SUPPLIED BY
 MECHANICAL SYSTEMS.
 10) SUBMIT SPECIFICATIONS FOR THE BOILER, VENT DETAILS,
 VENT PIPING, ETC. WPB AMEND. TO FBC SEC. 107.2.1.
 11) SUBMIT DETAILS FOR DRYER VENTS, TERMINATION POINTS,
 VENT MATERIAL, ETC. WPB AMEND. TO FBC SEC. 107.2.1.
 12) SHT. K1 PRS SHOWS GAS APPLIANCE PBF-1 (DECK
 OVEN/PIZZA) AT 140 MBTU. I DO NOT SEE THIS APPLIANCE OR
 THE BTU VALUE ON THE GAS PLANS. CLARIFY.
 13) CARBON MONOXIDE ALARMS SHALL BE PROVIDED AND COMPLY
 WITH FBC SECS. 908.7, 908.7.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805 PLUMBING PLAN REVIEW
 -6692
 [email protected]
  
  
  