2016-08-16 13:47:46 | GAS REVIEW |
| 1) SHT. P4.10 - GAS GENERAL NOTES ? AFTER THE SECOND |
| STAGE REGULATOR PRESSURE IS NOTED AS 2 PSI YET THE |
| TABLE THAT IS REFERENCED IS FOR LESS THAN A 2 PSI |
| SYSTEM (402.4) (2). REVISE THE NOTE. |
| 2) SHOW THE DEVELOPED LENGTH OF THE PIPING FROM THE |
| SECOND STAGE REGULATOR TO THE FURTHEST OUTLET. THIS |
| DISTANCE IS USED FOR THE SIZING OF THE LOW PRESSURE |
| SYSTEM. |
| 3) SHT. P4.10 - THE BTU LOAD FOR THE TWO DOMESTIC |
| BOILERS ADDS TO 1,500 MBTU BUT THE PLANS SHOW 1,700 |
| MBTU. CLARIFY. |
| 4) SHT. P4.10 - KEYNOTE #10 SHOWS TWO BOILERS AT 199 |
| MBTU EACH WHICH IS 398 MBTU BUT THE RISER SHOWS 798 |
| MBTU. CLARIFY. |
| 5) MY CALCULATION OF BTU'S AT ONE SECTION OF THE GAS |
| RISER IS 1,898 MBTU BUT THE PLAN SHOWS 2,498 MBTU. |
| THERE IS ANOTHER SECTION WITH A BTU LOAD OF 3,698 MBTU |
| AND MY CALCULATIONS ADD TO 3,098 MBTU. CLARIFY. |
| 6) THE TOTAL BTU LOAD ON THE SYSTEM SHOULD BE 4,413 |
| MBTU. PLEASE CHECK THE CALCULATIONS. |
| 7) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR THE |
| GAS REGULATORS. FGC SEC. 410.1, 410.2. |
| 8) SUBMIT MANUF. SPECIFICATION SHEETS FOR THE ALL GAS |
| EQUIPMENT AND APPLIANCES. APPLIANCES REGULATED BY THE |
| CODE SHALL BE LISTED AND LABELED. FGC 301.3. |
| 9) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR ALL GAS |
| FIRED EQUIPMENT (KITCHEN EQUIPMENT, DRYERS, POOL |
| EQUIPMENT, BOILERS, ETC.) PER FGC SEC. 304. SEE FGC |
| SEC. 304.9.3 FOR COMBUSTION AIR BEING SUPPLIED BY |
| MECHANICAL SYSTEMS. |
| 10) SUBMIT SPECIFICATIONS FOR THE BOILER, VENT DETAILS, |
| VENT PIPING, ETC. WPB AMEND. TO FBC SEC. 107.2.1. |
| 11) SUBMIT DETAILS FOR DRYER VENTS, TERMINATION POINTS, |
| VENT MATERIAL, ETC. WPB AMEND. TO FBC SEC. 107.2.1. |
| 12) SHT. K1 PRS SHOWS GAS APPLIANCE PBF-1 (DECK |
| OVEN/PIZZA) AT 140 MBTU. I DO NOT SEE THIS APPLIANCE OR |
| THE BTU VALUE ON THE GAS PLANS. CLARIFY. |
| 13) CARBON MONOXIDE ALARMS SHALL BE PROVIDED AND COMPLY |
| WITH FBC SECS. 908.7, 908.7.1. |
| |