Plan Review Notes
Plan Review Notes For Permit 16061443
Permit Number 16061443
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2016-07-01 10:01:51718 SOUTH DIXIE HIGHWAY - 14 STORY HILTON
 PERMIT #16061443
 REVIEW COMMENTS - FIRE DEPARTMENT
 NOTE: UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY
 REVIEW COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE
 (2012 EDITION WITH FLORIDA AMENDMENTS.)
  
 THE CITY OF WEST PALM BEACH REQUIRES CONSTRUCTION
 TRAILERS LARGER THAN A SINGLE "DOUBLE WIDE" (OR TWO
 "SINGLE WIDE") TO EITHER BE PROTECTED BY AN AUTOMATIC
 SPRINKLER SYSTEM OR COMPLY WITH THE SEPARATION
 REQUIREMENTS OF NFPA 241. TEMPORARY CONSTRUCTION
 TRAILERS OR MODULAR BUILDINGS WILL REQUIRE A PERMIT AND
 COMPLIANCE WITH THE FOLLOWING:
 PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION,
 ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2:
 TEMPORARY OFFICES, TRAILERS, AND OTHER FACILITIES OF
 COMBUSTIBLE CONSTRUCTION OR HOUSING COMBUSTIBLE
 CONTENTS SHALL BE SEPARATED FROM ADJACENT BUILDINGS,
 TRAILERS OR STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1.
 PER TABLE 4.2.1:
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION WORK
 SHALL CONFORM TO THE REQUIREMENTS OF NFPA 241. TRASH
 AND CONSTRUCTION DEBRIS SHALL BE REMOVED FROM THE SITE
 DAILY. SMOKING SHALL BE PROHIBITED EXCEPT IN DESIGNATED
 EXTERIOR AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION
 AREAS SHALL HAVE "NO SMOKING" SIGNS POSTED. WHERE
 SMOKING IS PERMITTED, SAFE RECEPTACLES FOR SMOKING
 MATERIALS SHALL BE PROVIDED.
  
 PER NFPA 241, NEW FIRE HYDRANTS SHALL BE INSTALLED,
 INSPECTED, TESTED AND APPROVED PRIOR TO THE
 COMMENCEMENT OF VERTICAL CONSTRUCTION.
  
 FIRE SERVICE ELEVATORS: PLANS SHOW ONE FIRE SERVICE
 ELEVATOR; CONFIRM TWO ARE NOT REQUIRED BY THE FBC FOR
 BUILDINGS WITH AN OCCUPIABLE FLOOR ABOVE 120 FEET.
  
 SHEET C-10: THE FIRE LINE BACKFLOW PREVENTERS CAN BE
 USED TO CONTROL THE WATER SUPPLY. THE ADDITIONAL PIVS
 SHOULD BE ELIMINATED. ALSO PER NFPA 24 SECTION 6.2.1,
 ALL CONNECTIONS TO PRIVATE FIRE SERVICE MAINS FOR FIRE
 PROTECTION SYSTEMS SHALL BE ARRANGED IN ACCORDANCE WITH
 ONE OF THE FOLLOWING SO THAT THEY CAN BE ISOLATED:
 (1) A WALL POST INDICATOR VALVE
 (2) A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING
 VALVE NOT LESS THAN 40 FEET FROM THE BUILDING
 (3) CONTROL VALVES INSTALLED IN A FIRE-RATED ROOM
 ACCESSIBLE FROM THE EXTERIOR
 (4) CONTROL VALVES IN A FIRE-RATED STAIR ENCLOSURE
 ACCESSIBLE FROM THE EXTERIOR AS PERMITTED BY THE
 AUTHORITY HAVING JURISDICTION
  
 SHEET A0.01: PROJECT DATA BUILDING DESCRIPTION
 INDICATES THIS IS A 6-STORY MID-RISE BUILDING IN LIEU
 OF A HIGH-RISE BUILDING.
  
 SHEET A1.12: ONE FIRE OR OTHER EMERGENCY EVENT HAS THE
 ABILITY TO PROHIBIT THE USAGE OF STAIR #2 AND STAIR #3
 SIMULTANEOUSLY. PER SECTION 7.5.1.3.1 WHERE MORE THAN
 ONE EXIT, EXIT ACCESS, OR EXIT DISCHARGE IS REQUIRED
 FROM A BUILDING OR PORTION THEREOF, SUCH EXITS, EXIT
 ACCESSES, OR EXIT DISCHARGES SHALL BE REMOTELY LOCATED
 FROM EACH OTHER AND BE ARRANGED TO MINIMIZE THE
 POSSIBILITY THAT MORE THAN ONE HAS THE POTENTIAL TO BE
 BLOCKED BY ANY ONE FIRE OR OTHER EMERGENCY CONDITION.
  
 SHEET A1.12: STAIR #3 ONLY INDICATES TWO OF THE FOUR
 WALLS HAVE A FIRE RESISTANCE RATING.
  
 SHEET A1.12 & A8.05: PLANS INDICATE THE USE OF TYCO
 WINDOW SPRINKLERS (WINDOW TYPES UU, WW & YY) IN LIEU OF
 FIRE RATED GLAZING. PROVIDE A SPRINKLER INSTALLATION
 WINDOW DETAIL ACCORDING TO THE MANUFACTURER'S LISTING
 CRITERIA. THE SPRINKLER LISTING DETAILS ARE VERY
 PARTICULAR AND REQUIRE SPRINKLERS ON BOTH SIDES OF THE
 GLAZING. THE MAXIMUM GLAZING HEIGHT IS LIMITED TO 13
 FEET. THE GLASS CURTAIN WALL NEEDS TO BE ATTACHED TO A
 THREE FOOT HIGH PONY WALL TO KEEP COMBUSTIBLE MATERIALS
 AT LEAST TWO-INCHES AWAY FROM THE GLAZING. VERTICAL
 MULLIONS SHALL BE OF A DEPTH THAT PREVENTS COLD
 SOLDERING OF ADJACENT SPRINKLERS. THE SPRINKLER DESIGN
 SHOULD INDICATE WHICH WINDOW SPRINKLER MODEL WILL BE
 USED (HORIZONTAL SIDEWALL OR PENDENT VERTICAL SIDEWALL)
 AS THIS WILL AFFECT HOW DEEP THE VERTICAL MULLIONS NEED
 TO BE. A MULLION WILL ACT AS A BAFFLE WHEN THE MULLION
 EXTENDS TO THE BACK OF SPRINKLER DEFLECTOR (PENDENT
 VERTICAL SIDEWALL) OR WHEN THE MULLION EXTENDS TO THE
 SPRINKLER WRENCH FLAT (HORIZONTAL SIDEWALL).
  
 SHEET A1.16: CORRIDOR DOORS USED TO SHRINK THE DEAD-END
 TRAVEL SHALL BE MARKED WITH OBVIOUS SIGNAGE STATING "NO
 EXIT." TYPICAL.
  
 SHEET A1.20: STAIR #2 MISSING THE FIRE RESISTANCE
 RATING.
  
 SHEET ID-210.C: THE TABLES AND CHAIRS COMPLETELY
 OBSTRUCT THE TWO SECONDARY MEANS OF EGRESS IN MEETING
 ROOM 1B (#218).
  
 SHEET ID-230.C: COORDINATION IS NEEDED BETWEEN THE
 FURNITURE PLAN AND THE LIFE SAFETY EGRESS PLAN.
  
 SHEET P2.02: GAS AND WATER PIPE SHALL NOT BE ROUTED
 THROUGH THE FIRE RATED EXIT STAIR ENCLOSURE OF STAIR
 #1. THIS IS PROHIBITED BY NFPA 101.
  
 SHEET M2.01: DUCTWORK, NOT ESSENTIAL TO THE FUNCTION OF
 THE STAIR, IS ROUTED THROUGH THE FIRE RATED EXIT
 PASSAGEWAY OF STAIR #1. THIS IS PROHIBITED BY NFPA 101.
  
 SHEET M2.01: KITCHEN SUPPLY FAN DUCTWORK IS ROUTED
 THROUGH THE FIRE PUMP ROOM. THIS IS PROHIBITED BY NFPA
 20.
  
 SHEET M2.01: THE THREE KITCHEN EXHAUST FANS INDICATE
 SIDEWALL DISCHARGE; HOWEVER, THE AIR LOUVERS FOR THE
 GARAGE APPEAR TO BE LOCATED WITHIN 32 FEET OF THE
 GREASE DUCT DISCHARGE PER NFPA 96 SECTION 7.8.3.
  
 SHEET M2.06: MECHANICAL PLANS INDICATE A 2-HOUR FIRE
 RATED CEILING IS NEEDED TO CONCEAL DUCTWORK IN STAIR
 #1. THIS IS NOT COORDINATED WITH THE ARCHITECTURAL
 DRAWINGS THAT SHOW THIS AREA AS NO CEILING - OPEN TO
 STRUCTURE.
  
 SHEET M8.01 - SMOKE CONTROL: PER SECTION 9.3.3
 ACCEPTANCE TESTING SHALL BE PERFORMED BY A SPECIAL
 INSPECTOR. SPECIAL INSPECTIONS AND TESTS SHALL BE
 PERFORMED TO VERIFY THE OPERATION OF THE FIRE
 PROTECTION SYSTEM IN ITS FINAL CONDITION FOR ACCEPTANCE
 BY THE AUTHORITY HAVING JURISDICTION. THE SPECIAL
 INSPECTOR'S RELEVANT EXPERIENCE IN THE DESIGN,
 INSTALLATION, AND TESTING OF THE FIRE PROTECTION
 SYSTEMS BEING TESTED SHALL BE DOCUMENTED. THE DESIGN
 DOCUMENTS SHALL PROVIDE THE PROCEDURES AND METHODS TO
 BE USED AND ITEMS SUBJECT TO SPECIAL INSPECTIONS AND
 TESTS. THE SPECIAL INSPECTOR SHALL SUBMIT AN INSPECTION
 AND TEST REPORT TO THE AUTHORITY HAVING JURISDICTION
 AND REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE
 CHARGE. PER FBC SECTION 909.18.8.2: SPECIAL INSPECTORS
 SHALL HAVE EXPERTISE IN FIRE PROTECTION ENGINEERING,
 MECHANICAL ENGINEERING AND CERTIFICATION AS AIR
 BALANCERS. DEVICES USED FOR SMOKE CONTROL SHALL HAVE AN
 APPROVED IDENTIFYING TAG OR MARK ON THEM INDICATING THE
 LAST TIME THEY WERE TESTED AND BY WHOM.
  
 SHEET E2.02A: CONFIRM EMERGENCY LIGHTING HAS BEEN
 PROVIDED ALONG THE MEANS OF EGRESS PATHS INSIDE THE
 ASSEMBLY OCCUPANCY MEETING ROOMS.
  
 SHEET E2.06: NO ILLUMINATED EXIT SIGNS PROVIDED FOR
 OPEN-AIR TERRACE #634 OR ON FAR WEST CORRIDOR DOOR NEAR
 COLUMN LINE 8.
  
 SHEET E2.07: NO ILLUMINATED EXIT SIGNS PROVIDED IN FIRE
 SERVICE ELEVATOR LEADING INTO EXIT STAIR #1. TYPICAL.
  
 SHEET E2.09: INSUFFICIENT QUANTITY OF ILLUMINATED EXIT
 SIGNS PROVIDED. WITHOUT ADDITIONAL SIGNAGE, THE CURRENT
 SIGNS CANNOT BE READILY VIEWED BY MOST OCCUPANTS IN THE
 POOL DECK AND BAR AREAS.
  
 SHEET E4.01: PLANS INDICATE TO PROVIDE PANIC HARDWARE
 ON THE EXIT DOOR FOR EMERGENCY POWER #107; HOWEVER,
 THIS DOOR SWING WILL NEED TO BE REVERSED FOR PANIC
 HARDWARE USAGE.
  
 SHEET E4.02: COULD NOT LOCATE THE FOLLOWING: THE
 FIRE-FIGHTERS' SMOKE CONTROL PANEL, GENERATOR MANUAL
 START/TRANSFER, STATUS INDICATORS AND CONTROLS FOR AIR
 DISTRIBUTION SYSTEM AND ELEVATOR RECALL SWITCHES WITH
 POWER SELECTOR SWITCHES.
  
 FIRE COMMAND CENTER:
 PER FFPC SECTION 11.9.4 AND FBC SECTION 911.1.5 - THE
 FIRE COMMAND CENTER SHALL COMPLY WITH NFPA 72 AND SHALL
 CONTAIN THE FOLLOWING FEATURES:
 1. THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM
 CONTROL UNIT.
 2. THE FIRE DEPARTMENT COMMUNICATIONS SYSTEM.
 3. FIRE DETECTION AND ALARM SYSTEM ANNUNCIATOR.
 4. ANNUNCIATOR UNIT VISUALLY INDICATING THE LOCATION OF
 THE ELEVATORS AND WHETHER THEY ARE OPERATIONAL.
 5. STATUS INDICATORS AND CONTROLS FOR AIR DISTRIBUTION
 SYSTEMS.
 6. THE FIRE-FIGHTERS' CONTROL PANEL REQUIRED BY SECTION
 909.16 FOR SMOKE CONTROL SYSTEMS INSTALLED IN THE
 BUILDING.
 7. CONTROLS FOR UNLOCKING STAIRWAY DOORS
 SIMULTANEOUSLY.
 8. SPRINKLER VALVE AND WATERFLOW DETECTOR DISPLAY
 PANELS
 9. EMERGENCY AND STANDBY POWER STATUS INDICATORS.
 10. A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED
 ACCESS TO THE PUBLIC TELEPHONE SYSTEM.
 11. FIRE PUMP STATUS INDICATORS.
 12. SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL
 FLOOR PLAN AND DETAILING THE BUILDING CORE, MEANS OF
 EGRESS, FIRE PROTECTION SYSTEMS, FIRE-FIGHTING
 EQUIPMENT AND FIRE DEPARTMENT ACCESS AND THE LOCATION
 OF FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE
 BARRIERS AND SMOKE PARTITIONS.
 13. WORK TABLE.
 14. GENERATOR SUPERVISION DEVICES, MANUAL START AND
 TRANSFER FEATURES.
 15. PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED
 BY OTHER SECTIONS OF THIS CODE.
 16. ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME
 A17.1.
 17. ELEVATOR EMERGENCY OR STANDBY POWER SELECTOR
 SWITCH(ES), WHERE EMERGENCY OR STANDBY POWER IS
 PROVIDED.
  
 SHEET E5.01: FEEDER SCHEDULE INDICATES F-10 AS A 2-INCH
 CONCRETE ENCASEMENT OF CONDUCTORS FOR THE FIRE PUMP;
 HOWEVER, THIS SYMBOL IS NOT LOCATED ON THE PLAN.
  
 SHEET E5.01: COULD NOT LOCATE THE FIRE PROTECTION
 JOCKEY PUMP AND ASSOCIATED CONTROL PANEL.
  
 SHEET E5.01: RISER DIAGRAM INDICATES RISER KEY NOTE #15
 ON THE FIRE PUMP CONTROL PANEL; HOWEVER, THE DRAWING
 KEYNOT SCHEDULE STOPS AT #12.
  
 SHEET FP2.02: ARCHITECTURAL PLANS INDICATE THE USE OF
 TYCO WINDOW SPRINKLERS FOR THE GLASS CURTAINWALL;
 HOWEVER, THIS DESIGN CONCEPT IS NOT DEPICTED ON THE
 FIRE PROTECTION ENGINEERING DRAWINGS.
  
 SHEET FP4.01: SPRINKLER AND STANDPIPE SYSTEM PRESSURES
 APPEAR TO EXCEED 165PSIG AND 175PSIG RESPECTIVELY WITH
 NO MEASURES OF CONTROL.
  
 SHEET FA2.01: INFORMATION TEXT BOX IS CUT OFF NEAR THE
 FIRE PUMP ROOM.
  
 SHEET FA4.02: CONFIRM THE USE OF A BIDIRECTIONAL
 AMPLIFIER RADIO SYSTEM (BDA) WITH FIREFIGHTER PHONE
 JACKS AS A BACK-UP.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  