Plan Review Notes
Plan Review Notes For Permit 16061443
Permit Number 16061443
Review Stop B
Sequence Number 1
Notes
Date Text
2016-07-18 06:27:44BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16061443
 ADD: 718 S. DIXIE HWY. / CANOPY BY HILTON
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-718-5987 / MARGARET LEON
 E-MAIL: MLEONDADLP.COM
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: THURS. JULY 14/2016 - MON. JULY 18/2016
 ACTION: DENIED
  
 1) DISCREPANCY IN PLANS AND THE PERMIT APPLICATION. THE
 AMOUNT OF STORIES IN THIS PROJECT? THE PERMIT
 APPLICATION INDICATES THIS IS A 17 STORY HOTEL . SEE
 SHEET A0.01. INDICATES UNDER THE BUILDING DESCRIPTION
 THIS A 6 STORY MID-RISE. WHEN YOU REVIEW THE SHEET
 INDEX, THERE ARE 13 STORIES INCLUDING THE HABITABLE
 POOL, POOL DECK AND A2 DELI/ RESTAURANT AREAS.
  
 2) ART IN PUBLIC PLACES. THE CITY OF WEST PALM BEACH
 ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES
 TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH
 THE PERMIT APPLICATION WAS SUBMITTED AFTER 6/29/2014,
 AND THE TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO
 OR GREATER THAN $750,000 WILL NEED TO COMPLY WITH THIS
 ORDINANCE.
 PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND
 CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V,
 ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION
 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL
 PROJECT CONSTRUCTION COST.
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
 FOR CONTACT INFORMATION PLEASE CONTACT:
 MS. SYBILLE WELTER
 ART IN PUBLIC PLACES COORDINATOR
 TEL: 822-1515
 E-MAIL: [email protected]
 WEBSITE: WPB.ORG/AIPP/
  
  
 3) THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR
 THE MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS.
 WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING
 PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE
 QUALIFIER AND OWNER AND BRINGS IN THE LISTED
 SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE
 QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND
 LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE
 FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN
 LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR
 EACH PERMIT.
  
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, EXHAUST
 HOODS, ANSUL SYSTEMS OR ALTERNATIVE AUTOMATIC
 FIRE-EXTINGUISHING SYSTEMS , WALK IN COOLERS &
 FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL
 TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED
 SUB-PERMITS, AWNING, CANOPY, FENCE, LANDSCAPE ,
 IRRIGATION, TEST PILE, AUGER CAST PILE AND OR
 FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE
 REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT.
 PLEASE LIST AND SUBTRACT THESE LINE ITEMS AND THEIR
 VALUE FROM THE OVERALL BUILDING VALUE OF
 $33,000,000.00. THE REMAINING BALANCE WILL BE
 AFFECTIVELY THE VALUE OF THE BUILDING YOU WILL BE
 PAYING FOR THIS PERMIT. THE BUILDING DOES NOT WANT TO
 COLLECT TWICE FOR THE VALUE OF THESE SUB-PERMITS NOT
 COVERED UNDER THE PRIME OR MASTER PERMIT.
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 108.3 BUILDING PERMIT VALUATION.
  
 4) PLEASE SHOW ENERGY CODE COMPLIANCE, MISSING
 DOCUMENTATION. SHOW COMPLIANCE BY THE 2014 FBC-ENERGY
 CODE C401.2 APPLICATION.
 COMMERCIAL BUILDINGS SHALL COMPLY WITH ONE OF THE
 FOLLOWING:
 1. THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1.
 2. THE REQUIREMENTS OF SECTIONS C402, C403, C404 AND
 C405. IN ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY
 WITH EITHER SECTION C406.2, C406.3 OR C406.4.
 3. THE REQUIREMENTS OF SECTION C407, C402.4, C403.2,
 C404, C405.2, C405.3, C405.4, C405.6 AND C405.7. THE
 BUILDING ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85
 PERCENT OF THE STANDARD REFERENCE DESIGN BUILDING.
  
 5) THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING.
 THRESHOLD BUILDING / FL S. S. 553.71(7) ?THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 5A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
 SHEET S1.02 IS LABELED STRUCTURAL INSPECTION PLAN THIS
 SHEET MAY NEED TO BE RENAMED TO THRESHOLD INSPECTION
 PLAN TO MEET THE COMMENT 3A.
  
 5B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUESTS FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE.
  
 5C) COMPLIED FOUND ON ARCHITECTURAL AND STRUCTURAL
 SHEETS. THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 5D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED.
  
 5E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION. THRESHOLD
 INSPECTION FORMS , GUIDELINES AND POLICIES FOR PROJECTS
 WERE E-MAILED TO:
 [email protected], PLEASE NOTE THIS E-MAIL ADDRESS CAME
 BACK UNDELIVERABLE. 07/14/2016 11:35 AM.
 [email protected]
  
 5F) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE..
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
  
 5G) 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
 5H) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 5I) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
  
 6) SHEET C-01 INDICATES THE PROPOSED SITE IS MADE UP OF
 4 LOTS. UNDER THE 2014 FBC-B TABLE 602, BUILDINGS
 CANNOT BE BUILT OVER PROPERTY LINES. EITHER A REPLAT OF
 THE 4 LOTS WILL NEED TO OCCUR OR A UNITY OF TITLE.
 UNITY OF TITLE. THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE LOTS
 WHICH COMBINE TO FORM 'THE SITE'. A 'UNITY OF TITLE'
 SHALL BE RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A
 COPY OF THE RECORDED 'UNITY OF TITLE' DOCUMENT SO THAT
 FBC TABLE 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED
 NOT APPLICABLE. SEE WEBSITE FOR APPLICATION:
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
 "APPLICATION FOR UNITY OF TITLE"
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
 VINCENT J NOEL
 SURVEYOR/REAL ESTATE SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1096
 FAX: 494-1116
 E-MAIL: [email protected]
 *********************************************
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 7) PERIMETER FENCING UNDER A SEPARATE PERMIT. PLEASE
 PROVIDE COMPLIANCE WITH: 2014 FBC-B 3306.5 BARRIERS.
 BARRIERS SHALL BE A MINIMUM OF 8 FEET (2438 MM) IN
 HEIGHT AND SHALL BE PLACED ON THE SIDE OF THE WALKWAY
 NEAREST THE CONSTRUCTION. BARRIERS SHALL EXTEND THE
 ENTIRE LENGTH OF THE CONSTRUCTION SITE.
  
 8) 2014 FBC0B 3306.2 WALKWAYS. A WALKWAY SHALL BE
 PROVIDED FOR PEDESTRIAN TRAVEL IN FRONT OF EVERY
 CONSTRUCTION AND DEMOLITION SITE UNLESS THE APPLICABLE
 GOVERNING AUTHORITY AUTHORIZES THE SIDEWALK TO BE
 FENCED OR CLOSED. WALKWAYS SHALL BE OF SUFFICIENT WIDTH
 TO ACCOMMODATE THE PEDESTRIAN TRAFFIC, BUT IN NO CASE
 SHALL THEY BE LESS THAN 4 FEET (1219 MM) IN WIDTH.
 WALKWAYS SHALL BE PROVIDED WITH A DURABLE WALKING
 SURFACE. WALKWAYS SHALL BE ACCESSIBLE IN ACCORDANCE
 WITH CHAPTER 11 AND SHALL BE DESIGNED TO SUPPORT ALL
 IMPOSED LOADS AND IN NO CASE SHALL THE DESIGN LIVE LOAD
 BE LESS THAN 150 POUNDS PER SQUARE FOOT (PSF). WILL THE
 WALKWAYS ON THE SOUTH SIDE OF TRINITY PLACE BE CLOSED?
  
 9) 2014 FBC-B 3306.7 COVERED WALKWAYS. COVERED WALKWAYS
 SHALL HAVE A CLEAR HEIGHT OF NOT LESS THAN 8 FEET (2438
 MM) AS MEASURED FROM THE FLOOR SURFACE TO THE CANOPY
 OVERHEAD. ADEQUATE LIGHTING SHALL BE PROVIDED AT ALL
 TIMES. COVERED WALKWAYS SHALL BE DESIGNED TO SUPPORT
 ALL IMPOSED LOADS. IN NO CASE SHALL THE DESIGN LIVE
 LOAD BE LESS THAN 150 PSF FOR THE ENTIRE STRUCTURE.
  
 10) PLEASE PROVIDE COMPLIANCE WITH: POLLUTION
 PREVENTION PLAN. 2014 FBC-B 3307.1 PROTECTION REQUIRED.
 ADJOINING PUBLIC AND PRIVATE PROPERTY SHALL BE
 PROTECTED FROM DAMAGE DURING CONSTRUCTION, REMODELING
 AND DEMOLITION WORK. PROVISIONS SHALL BE MADE TO
 CONTROL WATER RUNOFF AND EROSION DURING CONSTRUCTION OR
 DEMOLITION ACTIVITIES. THE PERSON MAKING OR CAUSING AN
 EXCAVATION TO BE MADE SHALL PROVIDE WRITTEN NOTICE TO
 THE OWNERS OF ADJOINING BUILDINGS ADVISING THEM THAT
 THE EXCAVATION IS TO BE MADE AND THAT THE ADJOINING
 BUILDINGS SHOULD BE PROTECTED. SAID NOTIFICATION SHALL
 BE DELIVERED NOT LESS THAN 10 DAYS PRIOR TO THE
 SCHEDULED STARTING DATE OF THE EXCAVATION.
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 109.3.10 IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL BE
 PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS
 PERMITTED TO AFFECT SAID PROPERTY PURSUANT TO CONSENT
 BY THE APPLICABLE PROPERTY OWNER, UNDER TERMS &
 CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY OWNER.
 THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS
 OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS, PATIOS,
 DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ.
 FT. OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 11) PLEASE PROVIDE DETAILS SHOWING HOW COMPLIANCE WITH
 2014 FBC-B 3306.9 ADJACENT TO EXCAVATIONS.
 EVERY EXCAVATION ON A SITE LOCATED 5 FEET (1524 MM) OR
 LESS FROM THE STREET LOT LINE SHALL BE ENCLOSED WITH A
 BARRIER NOT LESS THAN 6 FEET (1829 MM) IN HEIGHT. WHERE
 LOCATED MORE THAN 5 FEET (1524 MM) FROM THE STREET LOT
 LINE, A BARRIER SHALL BE ERECTED WHERE REQUIRED BY THE
 BUILDING OFFICIAL. BARRIERS SHALL BE OF ADEQUATE
 STRENGTH TO RESIST WIND PRESSURE AS SPECIFIED IN
 CHAPTER 16.
  
 11A) PLEASE PROVIDE DETAILS SHOWING COMPLIANCE WITH
 2014 FBC-B 3307.1 PROTECTION REQUIRED. ADJOINING PUBLIC
 AND PRIVATE PROPERTY SHALL BE PROTECTED FROM DAMAGE
 DURING CONSTRUCTION AND DEMOLITION WORK. PROTECTION
 SHALL BE PROVIDED FOR FOOTINGS, FOUNDATIONS, PARTY
 WALLS, CHIMNEYS, SKYLIGHTS AND ROOFS. WITH THE
 EXCAVATION AND AUGER CAST PILE HOW WILL THE BUILDING TO
 THE SOUTH BE PROTECTED FROM SETTLEMENT?
  
 11B) 2014 FBC-B 3307.1 THE PERSON MAKING OR CAUSING AN
 EXCAVATION TO BE MADE SHALL PROVIDE WRITTEN NOTICE TO
 THE OWNERS OF ADJOINING BUILDINGS ADVISING THEM THAT
 THE EXCAVATION IS TO BE MADE AND THAT THE ADJOINING
 BUILDINGS SHOULD BE PROTECTED. SAID NOTIFICATION SHALL
 BE DELIVERED NOT LESS THAN 10 DAYS PRIOR TO THE
 SCHEDULED STARTING DATE OF THE EXCAVATION.
  
 12) WHEN EXCAVATING WILL THE EXCESS SOILS BE STORED ON
 SITE? 2014 FBC-B 3304.1.2 SURCHARGE. NO FILL OR OTHER
 SURCHARGE LOADS SHALL BE PLACED ADJACENT TO ANY
 BUILDING OR STRUCTURE UNLESS SUCH BUILDING OR STRUCTURE
 IS CAPABLE OF WITHSTANDING THE ADDITIONAL LOADS CAUSED
 BY THE FILL OR SURCHARGE. EXISTING FOOTINGS OR
 FOUNDATIONS WHICH CAN BE AFFECTED BY ANY EXCAVATION
 SHALL BE UNDERPINNED ADEQUATELY OR OTHERWISE PROTECTED
 AGAINST SETTLEMENT AND SHALL BE PROTECTED AGAINST LATER
 MOVEMENT.
  
 13) PLEASE DOCUMENT COMPLIANCE WITH: 2014 FBC-B 3313.1
 WHERE REQUIRED. AN APPROVED WATER SUPPLY FOR FIRE
 PROTECTION, EITHER TEMPORARY OR PERMANENT, SHALL BE
 MADE AVAILABLE AS SOON AS COMBUSTIBLE MATERIAL ARRIVES
 ON THE SITE. PLEASE PROVIDE WHERE THIS CONNECTION WILL
 BE MADE.
  
 14) NOTICE: 2014 FBC-B [F] 3311.1 WHERE REQUIRED. IN
 BUILDINGS REQUIRED TO HAVE STANDPIPES BY SECTION
 905.3.1, NOT LESS THAN ONE STANDPIPE SHALL BE PROVIDED
 FOR USE DURING CONSTRUCTION. SUCH STANDPIPES SHALL BE
 INSTALLED WHEN THE PROGRESS OF CONSTRUCTION IS NOT MORE
 THAN 40 FEET (12 192 MM) IN HEIGHT ABOVE THE LOWEST
 LEVEL OF FIRE DEPARTMENT VEHICLE ACCESS. SUCH STANDPIPE
 SHALL BE PROVIDED WITH FIRE DEPARTMENT HOSE CONNECTIONS
 AT ACCESSIBLE LOCATIONS ADJACENT TO USABLE STAIRS. SUCH
 STANDPIPES SHALL BE EXTENDED AS CONSTRUCTION PROGRESSES
 TO WITHIN ONE FLOOR OF THE HIGHEST POINT OF
 CONSTRUCTION HAVING SECURED DECKING OR FLOORING.
 15A) 2014 FBC-B [F] 3309.1 WHERE REQUIRED. ALL
 STRUCTURES UNDER CONSTRUCTION SHALL BE PROVIDED WITH
 NOT LESS THAN ONE APPROVED PORTABLE FIRE EXTINGUISHER
 IN ACCORDANCE WITH SECTION 906 AND SIZED FOR NOT LESS
 THAN ORDINARY HAZARD AS FOLLOWS:
 1. AT EACH STAIRWAY ON ALL FLOOR LEVELS WHERE
 COMBUSTIBLE MATERIALS HAVE ACCUMULATED.
 2. IN EVERY STORAGE AND CONSTRUCTION SHED.
 3. ADDITIONAL PORTABLE FIRE EXTINGUISHERS SHALL BE
 PROVIDED WHERE SPECIAL HAZARDS EXIST, SUCH AS THE
 STORAGE AND USE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS.
  
 15B) 2014 FBC-B 3309.2 FIRE HAZARDS. THE PROVISIONS OF
 THIS CODE AND THE FLORIDA FIRE PREVENTION CODE SHALL BE
 STRICTLY OBSERVED TO SAFEGUARD AGAINST ALL FIRE HAZARDS
 ATTENDANT UPON CONSTRUCTION OPERATIONS.
  
 16) 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 109.3.10.1 HURRICANE PROTECTION. IT
 SHALL BE UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION
 RELATED MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE
 OR OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24
 HRS. AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO COMPLY TO REMOVE OR
 SECURE THE CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS
 WITHIN 24 HRS. AFTER A HURRICANE WATCH HAS BEEN ISSUED
 SHALL BE SUBJECT TO A FINE NOT TO EXCEED $500.00. IN
 ADDITION TO THE ABOVE, A LICENSED CONTRACTOR WHO
 VIOLATES THIS SECTION SHALL BE SUBJECT TO DISCIPLINE
 PURSUANT TO SECTION 113 OF THIS CHAPTER.
 17) STRUCTURAL SHEET S1.01 UNDER THE HEADING OF AUGER
 CAST PILE INDICATES THERE WAS A GEOTECHNICAL STUDY
 COMPLETED BY LANGAN ENGINEERING & ENVIRONMENTAL
 SERVICES MAY 21/ 2015 REPORT # 300176801. PLEASE
 PROVIDE 3 SIGNED AND SEALED ORIGINAL REPORTS. 2014
 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE
 CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL
 IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO
 THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
 18) SUBMIT PLANS FOR TEST PILE UNDER A SEPARATE PERMIT.
 COMPLIANCE WITH 2014 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 SECTION 117 TESTS. THE BUILDING OFFICIAL MAY REQUIRE
 TESTS OR TEST REPORTS AS PROOF OF COMPLIANCE. REQUIRED
 TESTS ARE TO BE MADE AT THE EXPENSE OF THE OWNER, OR
 AGENT, BY AN APPROVED TESTING LABORATORY OR OTHER
 APPROVED AGENCY, PLEASE PROVIDE WHAT AGENCY WILL BE
 MONITORING OF THE TEST AND PRODUCTION PILE?
 19) WITH NO SOILS REPORT SUBMITTED PLEASE PROVIDE
 COMPLIANCE WITH 2014 FBC-B 1803.5.4 GROUND-WATER TABLE.
 A SUBSURFACE SOIL INVESTIGATION SHALL BE PERFORMED TO
 DETERMINE WHETHER THE EXISTING GROUND-WATER TABLE IS
 ABOVE OR WITHIN 5 FEET (1524 MM) BELOW THE ELEVATION OF
 THE LOWEST FLOOR LEVEL WHERE SUCH FLOOR IS LOCATED
 BELOW THE FINISHED GROUND LEVEL ADJACENT TO THE
 FOUNDATION. WILL A DEWATERING PLAN BE NECESSARY FOR
 THIS LOCATION?
 20) SHEET A0.01;
 20A) FIRE RESISTANCE RATINGS PER TABLE 601, THE
 DESIGNER OF RECORD DECIARES A REDUCTION IN HOUR RATING
 OF FIRE RATING PER FBC-B 403.2.1.1 FOR EXTERIOR BEARING
 WALLS, INTERIOR BEARING WALLS & THE PRIMARY STRUCTURAL
 FRAME. THE MATRIX DOES NOT SHOW A SEPARATE LINE ITEM
 FOR COLUMNS, UNDER SECTION
 B-403.2.1.1 THE EXCEPTION DOES NOT ALLOW THE REDUCTION
 OF COLUMNS SUPPORTING FLOORS. THE ONLY REDUCTION THAT
 CAN BE TAKEN WOULD BE UNDER FOOTNOTE ?A?.
  
 20B) THE BUILDING INSULATION VALUES MAY VERY FROM WHAT
 IS LISTED SINCE THE ENERGY CALCULATIONS WERE NOT
 PROVIDED NOR THE METHOD OF COMPLIANCE UNDER THE ENERGY
 CODE IS A UNKNOWN. 2014 FBC-ENERGY CODE C401.2
 APPLICATION.
  
 20C) UNDER THE HEADING BUILDING MATERIALS THE STATEMENT
 STATES ALL APPROVALS FOR WINDOWS AND DOORS ARE REQUIRED
 TO BE APPROVED BY MIAMI/DADE COUNTY REQUIREMENTS FOR
 HIGH VELOCITY HURRICANE ZONE REQUIREMENTS. PLEASE NOTE
 ONLY BROWARD AND MIAMI-DADE COUNTY ARE UNDER THE HIGH
 VELOCITY HURRICANE ZONE. SEE DEFINITIONS UNDER 202.
 HIGH-VELOCITY HURRICANE ZONE. THIS ZONE CONSISTS OF
 BROWARD AND DADE COUNTIES.
  
 20D) HEADING SUBMITTALS. PRODUCT APPROVALS LISTED BELOW
 CAN BE DEFERRED SUBMITTALS WITH THE APPROVAL OF EITHER
 THE DESIGNER OF RECORD OR CONTRACTOR ONCE THE WIND
 DESIGN CRITERIA IS REVIEWED AND APPROVED THEN THE
 SUBMITTALS CAN BE SUBMITTED AFTER PERMIT ISSUANCE.
  
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS, MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS,
 INTAKE AND EXHAUST FANS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G PRE-ENGINEERED A/C STANDS
  
 20E) IDENTIFY GLAZING/ MULLIONS. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION INFORMATION IF REQUIRED,
 ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING
 SIZE. 107.2.1 CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 20F) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF
 ZONES 2 & 3. IF SO RAS 117 CALCULATIONS ARE REQUIRED BY
 EITHER A FLORIDA ARCHITECT OR ENGINEER.
 2014 FBC-B 1603.1.4 WIND DESIGN DATA. 107.2.1.2 FOR
 ROOF ASSEMBLIES REQUIRED BY THE CODE, THE CONSTRUCTION
 DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND DELINEATE THE
 TYPE OF ROOFING SYSTEM, MATERIALS, FASTENING
 REQUIREMENTS, FLASHING REQUIREMENTS AND WIND RESISTANCE
 RATING THAT ARE REQUIRED TO BE
 INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL
 INDICATE COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR
 THE SPECIFIC SITE OR A STATEMENT BY AN ARCHITECT OR
 ENGINEER FOR THE SPECIFIC SITE MUST BE SUBMITTED WITH
 THE CONSTRUCTION DOCUMENTS.
  
 21) SITE PLAN A1.01 INDICATES THERE ARE 79 PARKING
 SPACES WITHIN THE BUILDING. SHEET A1.15 THE 5TH FLOOR
 LIFE SAFETY PLAN THE 3RD PARKING LEVEL SHOWS A TOTAL OF
 4 ACCESSIBLE PARKING SPACES, OF THE 4 ACCESSIBLE
 PARKING SPACES, (1) SPACE NEEDS TO COMPLY WITH THE
 VERTICAL ACCESSIBILITY REQUIREMENTS OF ACCESS. CODE
 502.5 VERTICAL CLEARANCES FROM THE ENTRY OF THE 1ST
 FLOOR, VEHICLE ELEVATORS INCOMING AND OUTGOING AND THE
 VEHICLE ROUTE SERVING THEM. SEE ACCESS. CODE 502.5.
 ADVISORY 502.5 VERTICAL CLEARANCE.
 SIGNS PROVIDED AT ENTRANCES TO PARKING FACILITIES
 INFORMING DRIVERS OF CLEARANCES AND THE LOCATION OF VAN
 ACCESSIBLE PARKING SPACES CAN PROVIDE USEFUL CUSTOMER
 ASSISTANCE.
  
 FLORIDA LAW, S.553.511, F.S., REQUIRES SIGNS BE POSTED
 THAT WILL WARN HANDICAPPED-EQUIPPED VAN OPERATORS OF
 HEIGHT LIMITATIONS SO THEY WILL NOT PASS BEYOND A POINT
 WHERE THE VAN CANNOT BE MANEUVERED.
  
 FLORIDA LAW ALSO PREEMPTS LOCAL GOVERNMENT HEIGHT
 RESTRICTION ORDINANCES THAT WOULD PROHIBIT COMPLIANCE
 WITH THE MINIMUM HEIGHT REQUIREMENTS OF THIS SECTION.
 ALSO, ANY LOCAL OR STATE LAW OR REGULATION THAT
 PROHIBITS A COVERED ENTITY FROM COMPLYING WITH
 REQUIREMENTS OF THE ADA MAY RENDER SUCH JURISDICTION IN
 VIOLATION OF THE ADA.
  
 22) 2014 FBC-ACCESS. CODE ADVISORY 502.6
 IDENTIFICATION. THE REQUIRED ?VAN ACCESSIBLE?
 DESIGNATION IS INTENDED TO BE INFORMATIVE, NOT
 RESTRICTIVE, IN IDENTIFYING THOSE SPACES THAT ARE
 BETTER SUITED FOR VAN USE. ENFORCEMENT OF MOTOR VEHICLE
 LAWS, INCLUDING PARKING PRIVILEGES, IS A LOCAL MATTER.
 PARKING SPACE AND ACCESS AISLE CONFIGURATIONS REQUIRED
 FOR ALL ACCESSIBLE PARKING BY FLORIDA LAW, S.553.5041,
 F.S., MEET THE VAN ACCESSIBLE SPACE REQUIREMENTS OF THE
 ADA STANDARDS FOR ACCESSIBLE DESIGN. THEREFORE, NO
 ACCESSIBLE SPACE IS MORE SUITABLE THAN ANY OTHER
 ACCESSIBLE SPACE FOR ?VAN ACCESSIBLE? PARKING. FLORIDA
 LAW ONLY REQUIRES ?VAN ACCESSIBLE? PARKING SIGNS IN
 PARKING STRUCTURES WHERE VAN PARKING MAY BE LIMITED TO
 THE FIRST LEVEL ACCESSIBLE SPACES. FLORIDA ACCESSIBLE
 PARKING SIGNS MUST INCLUDE INDICATION OF THE PENALTY
 FOR ILLEGAL PARKING IN ADDITION TO THE ACCESSIBLE
 PARKING SYMBOL REQUIRED BY THE ADA STANDARDS FOR
 ACCESSIBLE DESIGN.
 23A) SHEET A1.11 GROUND FLOOR LIFE SAFETY PLAN VS.
 A2.01 GROUND FLOOR PLAN. THIS COMMENT WILL HOLD TRUE
 FOR ALL FLOORS, WITH THE EXCEPTION OF THE 3 PARKING
 FLOORS. NEITHER OF THESE PLANS HAVE LABELED, IDENTIFIED
 THE DOORS ON THE PLAN TO THE DOOR SCHEDULE FOUND ON
 A8.02. OPENING PROTECTIVES CANNOT BE REVIEWED UNDER
 FBC-B TABLE 716.5. EXAMPLE STAIR # 1 THERE ARE 3 DOORS
 ASSOCIATED WITH THE VERTICAL STAIR ENCLOSURE FOUND ON
 THE 1ST FLOOR.
 23B) PLEASE NOTE THE LIFE SAFETY SHEET A1.12 & A2.02
 THE OCCUPANT LOAD GIVEN FOR THIS FLOOR IS 581/ 3 EXIT
 STAIRWELLS IS 194 OCCUPANTS THROUGH THE 3 VERTICAL EXIT
 DOORWAYS. PLEASE NOTE THE LIFE SAFETY PLAN INDICATES
 CLEAR WIDTH FOR ALL 3 DOORS IS 34 INCHES WHICH CAN ONLY
 TAKE 170 OCCUPANTS AT EACH DOORWAY. THE TYPICAL EGRESS
 CAPACITY LEGEND FOUND ON THE SAME PAGE USES THE MEANS
 OF EGRESS CAPACITY FACTOR OF 0.2 INCHES PER OCCUPANT
 OVER THE ALLOWABLE 170 OCCUPANTS THROUGH A CLEAR
 OPENING OF 34 INCHES FOR ALL EGRESS DOORS ON THE 2
 AFFECTED FLOORS 1ST AND 2ND FLOOR.
 PLEASE ALSO REVIEW THE EXCEPTION TO FBC-B 1005.3.2 THAT
 REDUCES THE MEANS OF EGRESS LOAD FACTOR FOR DOORS TO
 0.15 INCH (3.8 MM) PER OCCUPANT IN BUILDINGS EQUIPPED
 THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM INSTALLED
 IN ACCORDANCE WITH SECTION 903.3.1.1 OR 903.3.1.2 AND
 AN EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM IN
 ACCORDANCE WITH SECTION 907.5.2.2.
 23C) ON THE 1ST FLOOR THE WORST CASE SCENARIO OF 194
 OCCUPANTS IS NOT FOUND AS THE OCCUPANT LOAD FOR THE
 WORST CASE SCENARIO EXITS THE BUILDING. FBC-B 1005.3.2.
 23B) THE A1.11 GROUND FLOOR LIFE SAFETY PLAN VS. A2.01
 GROUND FLOOR PLAN. COMMON COMMENT FOR ALL FLOORS.
 NEITHER OF THESE SHEETS SHOW WALL IDENTIFICATION TAGS
 THAT CORRELATE TO THE WALL RATING FOUND ON SHEET A9.01,
 EXCEPTION THE 3 PARKING FLOORS. 107.3.5.1.1 MINIMUM
 PLAN REVIEW CRITERIA FOR COMMERCIAL BUILDINGS. WALL
 RATINGS. EXTERIOR WALLS SECTION 705, FIRE BARRIERS 707,
 FIRE PARTITIONS 708, SMOKE BARRIERS, SHAFTS 713.
 23C)(1) THE A1.11 GROUND FLOOR LIFE SAFETY PLAN VS.
 A2.01 GROUND FLOOR PLAN. PLEASE NOTE THE VERTICAL EXIT
 DOES NOT END AT THE EXTERIOR OF THE BUILDING. THE PLANS
 SHOW A CONTINUATION OF THIS EXIT LABELED CORRIDOR # 109
 WITH A 3 HOUR FIRE RATED WALL ON ONE SIDE AND A 2 HOUR
 FIRE RATED WALL ON THE OTHER. PLEASE NOTE THIS
 EXTENSION OF THE VERTICAL EXIT NEEDS TO BE DEFINED AND
 BUILT AS A 2 HOUR EXIT PASSAGE WAY. 1022.10.1
 TERMINATION AND EXTENSION. A SMOKEPROOF ENCLOSURE OR
 PRESSURIZED STAIRWAY SHALL TERMINATE AT AN EXIT
 DISCHARGE OR A PUBLIC WAY.
 23C)(2) THE A1.11 GROUND FLOOR LIFE SAFETY PLAN VS.
 A2.01 GROUND FLOOR PLAN. THE EXTERIOR DOOR TO CORRIDOR
 # 120 LIST THE CLEAR OPENING AS 68 INCHES AND THE
 MAXIMUM OCCUPANCY THROUGH THIS DOOR AT 340 OCCUPANTS.
 THE DOOR APPEARS TO BE A 3 FOOT WIDE DOOR. SEE FBC-B
 1005.3.2.
 23D) THERE IS A DINING ELEMENT TO THE 1ST FLOOR PLEASE
 PROVIDE WHERE COMPLIANCE WITH 2014 FBC-ACCESS. CODE :
 902.1. DINING SURFACES AND WORK SURFACES SHALL COMPLY
 WITH 902.2 AND 902.3.
 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR SPACE
 COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH
 SHALL BE PROVIDED. KNEE AND TOE CLEARANCE COMPLYING
 WITH 306 SHALL BE PROVIDED.
 902.3 HEIGHT. THE TOPS OF DINING SURFACES SHALL BE 28
 INCHES (710 MM) MINIMUM AND 34 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND.
 904.5 FOOD SERVICE LINES. COUNTERS IN FOOD SERVICE
 LINES SHALL COMPLY WITH 904.5.
 904.5.1 SELF-SERVICE SHELVES AND DISPENSING DEVICES.
 SELF-SERVICE SHELVES AND DISPENSING DEVICES FOR
 TABLEWARE, DISHWARE, CONDIMENTS, FOOD AND BEVERAGES
 SHALL COMPLY WITH 308.
 904.5.2 TRAY SLIDES. THE TOPS OF TRAY SLIDES SHALL BE
 28 INCHES (710 MM) MINIMUM AND 34 INCHES (865 MM)
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
 23E) ACCESS. CODE 226.1 WHERE DINING SURFACES ARE
 PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST
 5 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT
 THE DINING SURFACES SHALL COMPLY WITH 902. IN ADDITION,
 WHERE WORK SURFACES ARE PROVIDED FOR USE BY OTHER THAN
 EMPLOYEES, AT LEAST 5 PERCENT SHALL COMPLY WITH 902.
 23F) ACCESS. CODE 226.2 DISPERSION. DINING SURFACES AND
 WORK SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE
 DISPERSED THROUGHOUT THE SPACE OR FACILITY CONTAINING
 DINING SURFACES AND WORK SURFACES.
 23G) SHEET THE A1.11 GROUND FLOOR LIFE SAFETY PLAN VS.
 A2.01 GROUND FLOOR PLAN. ON THE SOUTH PROPERTY LINE
 WALL THERE ARE PORTIONS OF THE WALL THAT ARE 1 HOUR
 FIRE RATED AND SOME PORTIONS RATED FOR 2 HOURS. FBC-B
 TABLE 601 LIST A 2 HOUR FIRE RATING FOR EXTERIOR FIRE
 BEARING WALLS. ADDITIONAL INFORMATION REQUIRED. IF
 THESE WALLS ARE GOING TO BE IN FILE NONBEARING WALLS
 HOW WILL THE WALL RATING BE MAINTAINED AT THE JOINT
 LINE TOP COURSE OF BLOCK WHERE THE BEAM WOULD ALREADY
 BE IN PLACE?
 24) SHEET A1.12 LIFE SAFETY 2ND FLOOR VS. A2.02 2ND
 FLOOR PLAN:
 24A) EXITS STAIRS 1,2 &3 ALL INDICATE THEY ARE 57
 INCHES WIDE. THE PROPOSED OCCUPANT LOAD FOR THE ENTIRE
 FLOOR IS 581 OCCUPANTS. 581 OCCUPANTS DIVIDE BY 3= 194
 OCCUPANTS PER STAIR. WHEN YOU DIVIDE THE 57 INCHES OF
 STAIR WIDTH BY THE 0.3 = 190 OCCUPANTS. THE PLANS ARE
 DEFICIENT BY 4 OCCUPANTS PER STAIRWELL. SEE FBC-B
 1005.3.1. THE CAPACITY, IN INCHES (MM), OF MEANS OF
 EGRESS STAIRWAYS SHALL BE CALCULATED BY MULTIPLYING THE
 OCCUPANT LOAD SERVED BY SUCH STAIRWAY BY A MEANS OF
 EGRESS CAPACITY FACTOR OF 0.3 INCH (7.6 MM) PER
 OCCUPANT.
 24B) SHEET A1.12 LIFE SAFETY 2ND FLOOR VS. A2.02 2ND
 FLOOR PLAN SHOWS AN OCCUPANT LOAD OF 581 OCCUPANTS AND
 TABLE 1021.1 REQUIRES 3 EXITS THERE IS AN ISSUE WITH
 FBC-B SECTION 1028.2 FOR THE 2ND FLOOR PLEASE DEFINE
 THE MAIN EXIT. 1028.2 ASSEMBLY MAIN EXIT. IN A
 BUILDING, ROOM OR SPACE USED FOR ASSEMBLY PURPOSES THAT
 HAS AN OCCUPANT LOAD OF GREATER THAN 300 AND IS
 PROVIDED WITH A MAIN EXIT, THE MAIN EXIT SHALL BE OF
 SUFFICIENT WIDTH TO ACCOMMODATE NOT LESS THAN ONE-HALF
 OF THE OCCUPANT LOAD, BUT SUCH WIDTH SHALL NOT BE LESS
 THAN THE TOTAL REQUIRED WIDTH OF ALL MEANS OF EGRESS
 LEADING TO THE EXIT. WHERE THE BUILDING IS CLASSIFIED
 AS A GROUP A OCCUPANCY, THE MAIN EXIT SHALL FRONT ON AT
 LEAST ONE STREET OR AN UNOCCUPIED SPACE OF NOT LESS
 THAN 10 FEET (3048 MM) IN WIDTH THAT ADJOINS A STREET
 OR PUBLIC WAY. IN A BUILDING, ROOM OR SPACE USED FOR
 ASSEMBLY PURPOSES WHERE THERE IS NO WELL-DEFINED MAIN
 EXIT OR WHERE MULTIPLE MAIN EXITS ARE PROVIDED, EXITS
 SHALL BE PERMITTED TO BE DISTRIBUTED AROUND THE
 PERIMETER OF THE BUILDING PROVIDED THAT THE TOTAL WIDTH
 OF EGRESS IS NOT LESS THAN 100 PERCENT OF THE REQUIRED
 WIDTH.
 THE ISSUE WITH THE 2 EXITS GROUPED ON THE WEST SIDE OF
 THE BUILDING IF A FIRE BLOCKS THE 2 WEST EXITS 50% OF
 THE OCCUPANT LOAD IS STILL SUPPOSED TO EXIT OUT OF THE
 REMAINING EXITS.
 1028.3 ASSEMBLY OTHER EXITS. IN ADDITION TO HAVING
 ACCESS TO A MAIN EXIT, EACH LEVEL IN A BUILDING USED
 FOR ASSEMBLY PURPOSES HAVING AN OCCUPANT LOAD GREATER
 THAN 300 AND PROVIDED WITH A MAIN EXIT, SHALL BE
 PROVIDED WITH ADDITIONAL MEANS OF EGRESS THAT SHALL
 PROVIDE AN EGRESS CAPACITY FOR AT LEAST ONE HALF OF THE
 TOTAL OCCUPANT LOAD SERVED BY THAT LEVEL AND SHALL
 COMPLY WITH SECTION 1015.2. IN A BUILDING USED FOR
 ASSEMBLY PURPOSES WHERE THERE IS NO WELL-DEFINED MAIN
 EXIT OR WHERE MULTIPLE MAIN EXITS ARE PROVIDED, EXITS
 FOR EACH LEVEL SHALL BE PERMITTED TO BE DISTRIBUTED
 AROUND THE PERIMETER OF THE BUILDING, PROVIDED THAT THE
 TOTAL WIDTH OF EGRESS IS NOT LESS THAN 100 PERCENT OF
 THE REQUIRED WIDTH.
 24C) PLEASE REVIEW THE MEETING ROOM # 3 THE ROOM HAS AN
 OCCUPANT LOAD OF 107 OCCUPANTS THE PLEASE SEE SIDE WALL
 BETWEEN ROOMS 220 & 221. THIS SECTION OF WALL HAS 2
 DOORS SWINGING IN OPPOSITE DIRECTIONS. THE REMAINDER OF
 THE MEETING ROOMS (217, 218 & 219) ALSO HAVE AN
 OCCUPANT LOAD GREATER THAN 50 REQUIRING A SECOND MEANS
 OF EGRESS WITH THE DOOR SWINGING IN THE DIRECTION OF
 TRAVEL. FBC-B 1008.1.2.
 24D) THERE IS A NOTE FOR S SMOKE PARTITION FOR THE 2
 STORY ATRIUM USING THE EXCEPTION #1 REQUIRING BOTH
 REQUIREMENTS OF 404.6 EXCEPTION 1.1 & 1.2 BE MET.
 PLEASE PROVIDE DETAILS FOR THE SPACING OF THE FIRE
 SPRINKLERS AND COMPLIANCE WITH 1.2 1.2. THE GLASS WALL
 SHALL BE INSTALLED IN A GASKETED FRAME IN A MANNER THAT
 THE FRAMING SYSTEM DEFLECTS WITHOUT BREAKING (LOADING)
 THE GLASS BEFORE THE SPRINKLER SYSTEM OPERATES.
 24E) THE DOOR SCHEDULE ON SHEET A8.02 INDICATES IN
 STAIRWELL 3 AN ACCESS HATCH IDENTIFIED AS S3, NOT
 IDENTIFIED ON THE FLOOR PLAN. FBC-B 1022.4. OPENINGS IN
 INTERIOR EXIT STAIRWAYS OTHER THAN UNPROTECTED EXTERIOR
 OPENINGS SHALL BE LIMITED TO THOSE NECESSARY FOR EXIT
 ACCESS TO THE ENCLOSURE FROM NORMALLY OCCUPIED SPACES
 AND FOR EGRESS FROM THE ENCLOSURE.
 25) SHEET A1.13 THE 3RD FLOOR PARKING & SHEET A2.03,
 THESE SHEETS WILL BE COMMON COMMENTS FOR THE 3RD,
 4TH AND 5TH FLOORS.
  
 25A) THIS WILL BE A COMMON COMMENT FOR ALL FLOORS. NONE
 OF THE FLOORS SHOW THE FIRE SERVICE ACCESS ELEVATOR
 LOBBY TO BE ENCLOSED BY A SMOKE BARRIER HAVING A FIRE
 RESISTANCE RATING OF NOT LESS THAN 1 HOUR. SEE FBC-B
 3007.7.2. THE FIRE SERVICE ACCESS ELEVATOR LOBBY SHALL
 BE ENCLOSED WITH A SMOKE BARRIER HAVING A
 FIRE-RESISTANCE RATING OF NOT LESS THAN 1 HOUR, EXCEPT
 THAT LOBBY DOORWAYS SHALL COMPLY WITH SECTION 3007.7.3.
 25B) COMMENT COMMON TO ALL FLOORS. THE FIRE SERVICE
 ACCESS ELEVATOR LOBBY ENTRY DOORS IN THE DOOR
 SCHEDULEA8.02 ARE NOT FIRE RATED. 3007.7.3 LOBBY
 DOORWAYS. OTHER THAN THE DOOR TO THE HOIST WAY, EACH
 DOORWAY TO A FIRE SERVICE ACCESS ELEVATOR LOBBY SHALL
 BE PROVIDED WITH A 3/4-HOUR FIRE DOOR ASSEMBLY
 COMPLYING WITH SECTION 716.5. THE FIRE DOOR ASSEMBLY
 SHALL ALSO COMPLY WITH THE SMOKE AND DRAFT CONTROL DOOR
 ASSEMBLY REQUIREMENTS OF SECTION 716.5.3.1 WITH THE UL
 1784 TEST CONDUCTED WITHOUT THE ARTIFICIAL BOTTOM SEAL.
 25C) COMMENT COMMON TO THE 3 PARKING GARAGE FLOORS.
 DOOR 303A DOES NOT HAVE 18 INCHES FOR MANEUVERING
 CLEARANCES ON THE LATCH SIDE OF THE DOOR. SEE
 FBC-ACCESS. CODE 404.2.4.
 25D) NEITHER THE GENERATOR ROOM NOR THE DOOR TO THE
 GENERATOR ROOM SHOW A FIRE RATING. 2014 FBC-B 403.4.8.1
 REQUIRES 2 HOUR FIRE RATED WALLS WITH 1 ? HOUR OPENING
 PROTECTIVES. TABLE 716.5.
 25E) THIS COMMENT IS A COMMON FOR THE 3 PARKING FLOORS
 AND THE 1ST FLOOR. THE PLANS INDICATE TO PROVIDE FALL
 PROTECTION AT THE ENTRY OF THE AUTOMOBILE ELEVATOR.
 PLEASE PROVIDE COMPLIANCE WITH 2014 FBC-B 1013.2 GUARDS
 SHALL BE LOCATED ALONG OPEN-SIDED, EQUIPMENT PLATFORMS,
 STAIRS, RAMPS AND LANDINGS THAT ARE LOCATED MORE THAN
 30 INCHES (762 MM) MEASURED VERTICALLY TO THE FLOOR OR
 GRADE BELOW AT ANY POINT WITHIN 36 INCHES (914 MM)
 HORIZONTALLY TO THE EDGE OF THE OPEN SIDE. GUARDS SHALL
 BE ADEQUATE IN STRENGTH AND ATTACHMENT IN ACCORDANCE
 WITH SECTION 1607.8.
  
 25F) THIS IS A COMMON COMMENT FOR THE 3 GARAGE PARKING
 FLOORS ALL EXTERIOR WALLS WHERE A VEHICLE COULD RUN
 INTO THE WALL AND THE COMMON WALL BETWEEN THE PARKING
 GARAGE AND ATRIUM WILL NEED TO SHOW COMPLIANCE WITH
 1607.8.3 VEHICLE BARRIERS. VEHICLE BARRIERS FOR
 PASSENGER VEHICLES SHALL BE DESIGNED TO RESIST A
 CONCENTRATED LOAD OF 6,000 POUNDS IN ACCORDANCE WITH
 SECTION 4.5.3 OF ASCE 7. ASCE 7-10 SECTION 4.5.3 FOR
 DESIGN OF THE SYSTEM, THE LOADS SHALL BE ASSUME TO ACT
 BETWEEN 1FT. 6 INCHES AND 2 FT. 3 INCHES ABOVE THE
 FINISH FLOOR SURFACE, LOCATED TO PRODUCE A MAXIMUM LOAD
 EFFECTS. THE LOAD SHALL BE APPLIED ON AN AREA NOT TO
 EXCEED 12 IN. BY 12 IN.
  
 25G) SHEET A2.05 LIFE SAFETY PLAN INDICATES 2
 ACCESSIBLE PARKING STALLS WITH COLUMNS IN THE ACCESS
 AISLE. PLEASE PROVIDE THE CLEAR WIDTH FROM THE COLUMN
 TO THE ACCESSIBLE PARKING STALL. FBC-ACCESSIBILITY CODE
 502.3.1 WIDTH. ACCESS AISLES SERVING CAR AND VAN
 PARKING SPACES SHALL BE 60 INCHES (1525 MM) WIDE
 MINIMUM.
 26) SHEET A1.16 6TH FLOOR LIFE SAFETY PLAN & A7.05 &
 A7.06 ENLARGED FLOOR PLAN 6TH FLOOR.
 26A) COMMON COMMENT ALL FLOORS. THERE IS A UNKNOWN WALL
 TYPE NO SHOWN ON EITHER PLANS WITHIN THE LINEN SHOOT
 ENCLOSURE, THE WALL IN COMMON WITH THE HOUSE KEEPING
 ROOM IS NOT IDENTIFIED. THIS WALL SHOULD BE A 2 HOUR
 FIRE RATED WALL, IT IS PART OF THE SHAFT ENCLOSURE.
 FBC-B 713.4 FIRE-RESISTANCE RARING.
  
 26B) COMMON COMMENT ALL FLOORS. THE DOOR TO GAIN ENTRY
 INTO THE HOUSE KEEPING ROOM IS LABELED X23.
 SHEET A8.02 THE DOOR SCHEDULE INDICATES UNDER NOTE 22
 THIS DOOR IS A ?DUTCH DOOR? THIS DOOR PROVIDE 2 LEAVES,
 ONE ABOVE THE OTHER. PLEASE PROVIDE THE TESTED ASSEMBLY
 FOR THIS TYPE OF CONFIGURATION, WHERE IS THE BREAK IN
 THE DOOR TO OCCUR, WHERE WILL THE LOCK SET BE LOCATED,
 WHAT ASSEMBLY IS TO HOLD THE DOOR TOGETHER, WILL THE
 TOP AND BOTTOM PORTIONS OF THE DOOR BE ON SPRING TYPE
 HINGES, WILL BOTH HALVES OF THE DOOR BE ON HOLD OPEN
 DEVISES THAT WILL ACTIVATE UPON FIRE AND OR SMOKE
 ALARM? NOTE 19 INDICATES A VIEW PANEL, HOW LARGE OF A
 VIEW PANEL. MISSING INFORMATION 107.2.1.3. TABLE 716.5/
 716.5.8 GLAZING MATERIAL. FIRE-PROTECTION-RATED GLAZING
 CONFORMING TO THE OPENING PROTECTION REQUIREMENTS IN
 SECTION 716.5 SHALL BE PERMITTED IN FIRE DOOR
 ASSEMBLIES.
 716.5.8.1 SIZE LIMITATIONS. FIRE-PROTECTION-RATED
 GLAZING SHALL COMPLY WITH THE SIZE LIMITATIONS OF NFPA
 80, AND AS PROVIDED IN SECTIONS 716.5.8.1.1 AND
 716.5.8.1.2.
  
 26C) SHEET A6.13 LINEN CHUTE DETAIL SHEET. PLEASE NOTE
 SECTION DETAILS OF THE LINEN CHUTE ARE MISSING 2
 DETAILS;
 26C)(1) THE DETAIL DOES NOT INCLUDE THE HOUSING OR NOTE
 FOR THE REQUIREMENT OF FBC-B 903.2.11.2 RUBBISH AND
 LINEN CHUTES.
 AN AUTOMATIC SPRINKLER SYSTEM SHALL BE INSTALLED AT THE
 TOP OF RUBBISH AND LINEN CHUTES AND IN THEIR TERMINAL
 ROOMS. CHUTES SHALL HAVE ADDITIONAL SPRINKLER HEADS
 INSTALLED AT ALTERNATE FLOORS AND AT THE LOWEST INTAKE.
 WHERE A RUBBISH CHUTE EXTENDS THROUGH A BUILDING MORE
 THAN ONE FLOOR BELOW THE LOWEST INTAKE, THE EXTENSION
 SHALL HAVE SPRINKLERS INSTALLED THAT ARE RECESSED FROM
 THE DROP AREA OF THE CHUTE AND PROTECTED FROM FREEZING
 IN ACCORDANCE WITH SECTION 903.3.1.1. SUCH SPRINKLERS
 SHALL BE INSTALLED AT ALTERNATE FLOORS, BEGINNING WITH
 THE SECOND LEVEL BELOW THE LAST INTAKE AND ENDING WITH
 THE FLOOR ABOVE THE DISCHARGE. CHUTE SPRINKLERS SHALL
 BE ACCESSIBLE FOR SERVICING. ACCESS DOOR REQUIRED.
  
 26C)(2) MISSING DETAIL FOR THE ACCESS DOOR INTO THE
 CHUTE ITSELF AND NOTE FOR THE FIRE RATING OF THE
 ASSEMBLY. FBC-B 713.13.1 REFUSE, RECYCLING AND LAUNDRY
 CHUTE ENCLOSURES. OPENINGS INTO THE SHAFT, INCLUDING
 THOSE FROM ACCESS ROOMS AND TERMINATION ROOMS, SHALL BE
 PROTECTED IN ACCORDANCE WITH THIS SECTION AND SECTION
 716. OPENINGS INTO CHUTES SHALL NOT BE LOCATED IN
 CORRIDORS. DOORS SHALL BE SELF- OR AUTOMATIC-CLOSING
 UPON THE ACTUATION OF A SMOKE DETECTOR IN ACCORDANCE
 WITH SECTION 716.5.9.3.
  
 26D) COMMON COMMENT FOR 6-12 FLOORS THE 2 HOUR FIRE
 RATED SHAFT BEHIND THE SERVICE ELEVATOR AND P1 ELEVATOR
 DO NOT HAVE THE WALL IDENTIFICATION TAGS. 107.2.1.3.
 ADDITIONAL INFORMATION REQUIRED.
  
 26E) PLEASE PROVIDE IF THERE ARE ANY DWELLING UNITS
 WITHIN THE FLOORS 6-12? DEFINITION:
 DWELLING UNIT. A SINGLE UNIT PROVIDING COMPLETE,
 INDEPENDENT LIVING FACILITIES FOR ONE OR MORE PERSONS,
 INCLUDING PERMANENT PROVISIONS FOR LIVING, SLEEPING,
 EATING, COOKING AND SANITATION.
  
 SLEEPING UNIT. A ROOM OR SPACE IN WHICH PEOPLE SLEEP,
 WHICH CAN ALSO INCLUDE PERMANENT PROVISIONS FOR LIVING,
 EATING, AND EITHER SANITATION OR KITCHEN FACILITIES BUT
 NOT BOTH. SUCH ROOMS AND SPACES THAT ARE ALSO PART OF A
 DWELLING UNIT ARE NOT SLEEPING UNITS.
  
 IF THERE ARE DWELLING UNITS THEN CODE REQUIREMENTS FOR
 :
 FBC-B 2010 1207.2 AIR-BORNE SOUND.
 FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2. FLOOR
 INSULATION. INSULATION INSTALLED BETWEEN A
 FINISHED FLOOR AND SOLID DECKING WITHOUT INTERVENING
 AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME
 SPREAD INDEX OF NOT MORE THAN 200.
  
 26F) BUILDING PROVISO/ DEFERRED SUBMITTAL: OPEN AIR
 TERRACE WATERPROOFING MATERIAL AND DETAILS. SHEET 5.11.
 ADMINISTRATION 107.3.4 DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE
 FOR REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS
 PREPARED BY OTHERS, INCLUDING PHASED AND DEFERRED
 SUBMITTAL ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF
 THE BUILDING. PRODUCTS SHALL BE REVIEWED AND APPROVED
 IN WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 26G) BUILDING PROVISO/ DEFERRED SUBMITTALS: OPEN AIR
 TERRACE VIVA BLADE GUARD RAIL SYSTEM. SHEET 5.11.
 ADMINISTRATION 107.3.4 DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE
 FOR REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS
 PREPARED BY OTHERS, INCLUDING PHASED AND DEFERRED
 SUBMITTAL ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF
 THE BUILDING. PRODUCTS SHALL BE REVIEWED AND APPROVED
 IN WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 26H) ** COMMON COMMENT FOR ALL FLOORS (6-12) WHERE THE
 ALLOWABLE COMMON PATH OF TRAVEL IS EXCEEDED. EXAMPLE:
 ROOMS 604 & 605 FROM THE MOST REMOTE POINT IN THE SUITE
 TO THE NEAREST VERTICAL EXIT IS OVER THE ALLOWABLE 75
 FT. TO ACHIEVE THE ALLOWABLE 75 FT. A RATED WALL IS
 INSTALLED IN THE EXIT ACCESS CORRIDOR, ON THE DOOR
 SCHEDULE THIS DOOR IS NOT FIRE RATED. PLEASE PROVIDE A
 CODE SECTION WHERE THIS IS ALLOWED TO BE CONSIDERED
 CODE COMPLIANT. 2014 FBC-B TABLE 1014.3. DEFINITION:
 COMMON PATH OF EGRESS TRAVEL. THAT PORTION OF EXIT
 ACCESS WHICH THE OCCUPANTS ARE REQUIRED TO TRAVERSE
 BEFORE TWO SEPARATE AND DISTINCT PATHS OF EGRESS TRAVEL
 TO TWO EXITS ARE AVAILABLE. PATHS THAT MERGE ARE COMMON
 PATHS OF TRAVEL. COMMON PATHS OF EGRESS TRAVEL SHALL BE
 INCLUDED WITHIN THE PERMITTED TRAVEL DISTANCE.
  
 27) SHEET A1.18 & A7.09 & A7.10. THE 8TH, 10TH & 12TH
 FLOORS. THIS COMMENT FOR THE ROOMS 818,819,1018,
 1019,1218 & 1219 ALL EXCEED THE ALLOWABLE 75 FT.
 ALLOWABLE COMMON PATH OF TRAVEL OF 75 FT. 2014 FBC-B
 TABLE 1014.3
  
 28) SHEET A2.08A THE INTERSTITIAL SPACE FLOOR PLAN. IN
 BOTH VERTICAL EXIT STAIR TOWERS 1 & 2 THERE IS A NOTE
 OF A DOOR LABELED S3 AND NOTE TO THE SIDE TO PROVIDE A
 3 FT. X 4 FT. ACCESS HATCH. THIS DOOR/ ACCESS HATCH IS
 WITHIN THE VERTICAL EXIT AND LEADS TO THE INTERSTITIAL
 SPACE BETWEEN FLOORS. PLEASE FIND ANOTHER WAY TO ACCESS
 THE INTERSTITIAL SPACE BETWEEN FLOORS. CODE COMPLIANCE
 FOR THE VERTICAL EXIT STAIRS CANNOT BE MET WITH THIS
 OPENING WITHIN THE STAIRS. PLEASE SEE THE 2014 FBC-B
 SECTION 1022.4 OPENINGS.
 INTERIOR EXIT STAIRWAY AND RAMP OPENING PROTECTIVES
 SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION
 716. OPENINGS IN INTERIOR EXIT STAIRWAYS AND RAMPS
 OTHER THAN UNPROTECTED EXTERIOR OPENINGS SHALL BE
 LIMITED TO THOSE NECESSARY FOR EXIT ACCESS TO THE
 ENCLOSURE FROM NORMALLY OCCUPIED SPACES AND FOR EGRESS
 FROM THE ENCLOSURE.
  
 29) SHEET A2.09 & A7.41 13TH FLOOR ROOFTOP GARDEN:
 29A) THIS SHEET INDICATES A SECTION FOR RESTROOM 1321 &
 1322, PAGE A7.41 SECTION 04. PLEASE SEE ON THIS SHEET
 THE DETAIL IS MISSING. 107.2.1.3. ADDITIONAL
 INFORMATION IS REQUIRED.
  
 29B) DOORS 1322, 1323,1324, 1325 & 1326 ARE MISSING
 FROM THE DOOR SCHEDULE FOUND ON SHEET A8.02, CANNOT BE
 CHECKED FOR SIZE, TYPE NOR FIRE RATING. 2014 FBC-B
 1008.1.1, TABLE 716.5.
  
 29C) DOORS NOT NUMBERS, THE DOOR ALL THE WAY TO THE
 LEFT OF THE PAGE SEPARATING AREAS 1313 & 1314 SWINGS
 AGAINST THE DIRECTION OF EGRESS TRAVEL WHERE SERVING A
 ROOM OR AREA CONTAINING AN OCCUPANT LOAD OF 50 OR MORE
 PERSONS OR A GROUP H OCCUPANCY. FBC-B 1008.1.2.
 29D) BARS 1311 AND 1312 WILL NEED TO SHOW COMPLIANCE
 WITH; 2014 FBC-ACCESS. CODE 902.3 HEIGHT. THE TOPS OF
 DINING SURFACES SHALL BE 28 INCHES MINIMUM AND 34
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
 29E) THE AREAS ROOF LOUNGE AND LOBBY, 1313 & 1314 MAY
 NEED TO COMPLY WITH ACCESS. CODE 902.3 IF THERE ARE
 TABLES PRESENT. THIS PLAN DOES NOT SHOW A SEATING
 ARRANGEMENT IN THE ROOF LOUNGE 1314.
  
 29F) STAIRWELL # 1 SHOWS A LADDER TO GAIN ACCESS TO THE
 ROOF TOP EQUIPMENT. PLEASE REVIEW :
 2014 FBC-B SECTION 1022.4 OPENINGS. INTERIOR EXIT
 STAIRWAY AND RAMP OPENING PROTECTIVES SHALL BE IN
 ACCORDANCE WITH THE REQUIREMENTS OF SECTION 716.
 OPENINGS IN INTERIOR EXIT STAIRWAYS AND RAMPS OTHER
 THAN UNPROTECTED EXTERIOR OPENINGS SHALL BE LIMITED TO
 THOSE NECESSARY FOR EXIT ACCESS TO THE ENCLOSURE FROM
 NORMALLY OCCUPIED SPACES AND FOR EGRESS FROM THE
 ENCLOSURE.
 FBC-B 1022.5 PENETRATIONS. PENETRATIONS INTO AND
 OPENINGS THROUGH INTERIOR EXIT STAIRWAYS AND RAMPS ARE
 PROHIBITED EXCEPT FOR REQUIRED EXIT DOORS, EQUIPMENT
 AND DUCTWORK NECESSARY FOR INDEPENDENT VENTILATION OR
 PRESSURIZATION, SPRINKLER PIPING, STANDPIPES,
 ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION
 SYSTEMS AND ELECTRICAL RACEWAY SERVING THE INTERIOR
 EXIT STAIRWAY AND RAMP AND TERMINATING AT A STEEL BOX
 NOT EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH
 PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH
 SECTION 714.
  
 30) POOL AND JACUZZI ARE NOT PART OF THIS PERMIT, WILL
 REQUIRE A SEPARATE PERMIT, REVIEW AND ASSOCIATED FEES.
  
 31) FENCING AND GATES AROUND THE POOL WILL REQUIRE A
 SEPARATE PERMIT, REVIEW AND ASSOCIATED FEES.
  
 32) SHEET A2.10 SHOWS AS HIDDEN LINES VARIOUS ROOF TOP
 EQUIPMENT. SHEET M2.10 SHOWS GENERIC ROOF TOP EQUIPMENT
 TIE DOWNS. DETAILS WILL NEED TO BE SPECIFIC FOR EACH
 TYPE AND SIZE OF ROOF TOP EQUIPMENT. FOR ALL ROOF TOP
 EQUIPMENT, CURBS OR A/C STANDS, DETAILED ATTACHMENT TO
 THE ROOF FRAMING & DECK AS WELL AS FROM THE CURB OR
 ROOF STAND TO THE EQUIPMENT ABOVE.
  
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS?
 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.
  
 33) SHEET A2.10 PLEASE SHOW COMPLIANCE WITH: FBC-B 2014
 1509.6 MECHANICAL EQUIPMENT SCREENS.
 MECHANICAL EQUIPMENT SCREENS SHALL BE CONSTRUCTED OF
 THE MATERIALS SPECIFIED FOR THE EXTERIOR WALLS IN
 ACCORDANCE WITH THE TYPE OF CONSTRUCTION OF THE
 BUILDING. WHERE THE FIRE SEPARATION DISTANCE IS GREATER
 THAN 5 FEET (1524 MM), MECHANICAL EQUIPMENT SCREENS
 SHALL NOT BE REQUIRED TO COMPLY WITH THE
 FIRE-RESISTANCE RATING REQUIREMENTS.
  
 34) A.600 SERIES DRAWINGS FOR STAIRWELL 1, 2 & 3.
 PLEASE PROVIDE COMPLIANCE WITH THE 2014 FBC-ACCESS.
 CODE SECTION 307.4 AND VIEW FIGURE 307.4 FOR VERTICAL
 CLEARANCES.
  
 35) BUILDING PROVISO: DEFERRED SUBMITTAL. SHEETS A6.02
 & A6.03 STAIR GUARDRAIL/ HANDRAILS . ADMINISTRATION
 107.3.4 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE. THE
 REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE
 FOR REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS
 PREPARED BY OTHERS, INCLUDING PHASED AND DEFERRED
 SUBMITTAL ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF
 THE BUILDING.
 FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL
 FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE
 ENGINEER OF RECORD FOR REVIEW.
 36) SHEET A4.01 SHOWS A NORTH ELEVATION WITH A NOTE FOR
 CONCRETE CANOPY WITH WOOD COMPOSITE UNDERNEATH FINISH.
 THE STRUCTURAL SHEET S5.21 DETAIL PROVIDES STRUCTURAL
 DETAILS AS TO THE THICKNESS OF THIS CANOPY, AND THE
 PLACEMENT OF REINFORCEMENT. THERE ARE 2 AREAS OF
 CONCERN:
  
 36A) THE NOTE FOUND ON A4.01 INDICATES THE UNDERNEATH
 SIDE OF THE CANOPY IS TO BE FINISHED WITH A WOOD
 COMPOSITE MATERIAL. WE FIND THIS SAME NOTE AT AROUND
 THE 155 FT. & 173.5 FT. ELEVATION. PLEASE PROVIDE
 PRODUCT LITERATURE ON THIS PRODUCT TO SEE HOW THIS
 MATERIAL WAS TESTED, TO WHAT STANDARD? DOES IT MEET THE
 DEFINITION OF A COMPOSITE MATERIAL.
  
 DEFINITION OF COMPOSITE MATERIAL: 703.5.2 COMPOSITE
 MATERIALS. MATERIALS HAVING A STRUCTURAL BASE OF
 NONCOMBUSTIBLE MATERIAL AS DETERMINED IN ACCORDANCE
 WITH SECTION 703.5.1 WITH A SURFACING NOT MORE THAN
 0.125 INCH (3.18 MM) THICK THAT HAS A FLAME SPREAD
 INDEX NOT GREATER THAN 50 WHEN TESTED IN ACCORDANCE
 WITH ASTM E 84 OR UL 723 SHALL BE ACCEPTABLE AS
 NONCOMBUSTIBLE MATERIALS.
  
 2014 FBC-B 1406.2.1 TYPE I, II, III AND IV
 CONSTRUCTION. ON BUILDINGS OF TYPE I, II, III AND IV
 CONSTRUCTION, EXTERIOR WALL COVERINGS SHALL BE
 PERMITTED TO BE CONSTRUCTED OF COMBUSTIBLE MATERIALS,
 COMPLYING WITH THE FOLLOWING LIMITATIONS:
 1. COMBUSTIBLE EXTERIOR WALL COVERINGS SHALL NOT EXCEED
 10 PERCENT OF AN EXTERIOR WALL SURFACE AREA WHERE THE
 FIRE SEPARATION DISTANCE IS 5 FEET (1524 MM) OR LESS.
 2. COMBUSTIBLE EXTERIOR WALL COVERINGS SHALL BE LIMITED
 TO 40 FEET (12 192 MM) IN HEIGHT ABOVE GRADE PLANE.
 3. COMBUSTIBLE EXTERIOR WALL COVERINGS CONSTRUCTED OF
 FIRE-RETARDANT-TREATED WOOD COMPLYING WITH SECTION
 2303.2 FOR EXTERIOR INSTALLATION SHALL NOT BE LIMITED
 IN WALL SURFACE AREA WHERE THE FIRE SEPARATION DISTANCE
 IS 5 FEET (1524 MM) OR LESS AND SHALL BE PERMITTED UP
 TO 60 FEET (18 288 MM) IN HEIGHT ABOVE GRADE PLANE
 REGARDLESS OF THE FIRE SEPARATION DISTANCE.
 4. WOOD VENEERS SHALL COMPLY WITH SECTION 1405.5.
 1406.2.1.1.2 FIRE SEPARATION GREATER THAN 5 FEET. FOR
 FIRE SEPARATION DISTANCES GREATER THAN 5 FEET (1524
 MM), ANY EXTERIOR WALL COVERING SHALL BE PERMITTED THAT
 HAS BEEN EXPOSED TO A REDUCED LEVEL OF INCIDENT RADIANT
 HEAT FLUX IN ACCORDANCE WITH THE NFPA 268 TEST METHOD
 WITHOUT EXHIBITING SUSTAINED FLAMING. THE MINIMUM FIRE
 SEPARATION DISTANCE REQUIRED FOR THE EXTERIOR WALL
 COVERING SHALL BE DETERMINED FROM TABLE 1406.2.1.1.2
 BASED ON THE MAXIMUM TOLERABLE LEVEL OF INCIDENT
 RADIANT HEAT FLUX THAT DOES NOT CAUSE SUSTAINED FLAMING
 OF THE EXTERIOR WALL COVERING.
  
 36B) THE WOOD COMPOSITE MATERIAL, PLEASE PROVIDE HOW
 THIS MATERIAL WILL BE ATTACHED TO THE SUB-STRUCTURE,
 ADHERED, PINNED? 107.2.1.3 ADDITIONAL INFORMATION
 REQUIRED.
  
 36C) ON THE TOP OF THE 8 FT. CONCRETE CANOPY WHAT
 PRODUCT WILL BE USED TO KEEP MOISTURE FROM SEEPING INTO
 THE CONCRETE SLAB AND REINFORCEMENT?
  
 37) SHEET A4.01 THE NORTH WALL ELEVATION ON THE GARAGE
 LEVELS 3-5 THE PLANS SHOW PERFORATED ALUMINUM PANEL
 SYSTEM. PLEASE PROVIDE PRODUCT LITERATURE, AND
 ENGINEERING ANALYSIS OF THE SYSTEM, WITH THE WIND
 DESIGN CRITERIA AND ANCHORING SYSTEMS REVIEWED BY THE
 ENGINEER OF RECORD. FL 61G-15-30.006 (3) THE DELEGATED
 ENGINEER SHALL FORWARD THE DELEGATED ENGINEERING
 DOCUMENTS TO THE ENGINEER OF RECORD FOR REVIEW. 2014
 FBC-B 1503.1 ROOF DECKS SHALL BE COVERED WITH APPROVED
 ROOF COVERINGS SECURED TO THE BUILDING OR STRUCTURE IN
 ACCORDANCE WITH THE PROVISIONS OF THIS CHAPTER. ROOF
 COVERINGS SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE
 WITH THIS CODE AND THE APPROVED MANUFACTURER?S
 INSTRUCTIONS SUCH THAT THE ROOF COVERING SHALL SERVE TO
 PROTECT THE BUILDING OR STRUCTURE.
 38) SHEET A1.11 AND A2.01 BOTH SHOW THE 1ST FLOOR, BUT
 THERE ARE NO DIMENSIONS FOR SIZING OF THE FIRE COMMAND
 CENTER. THE FIRE COMMAND ROOM IS FOUND ON THIS FLOOR.
 FBC-B403.4.6 FIRE COMMAND. A FIRE COMMAND CENTER
 COMPLYING WITH SECTION 911 SHALL BE PROVIDED IN A
 LOCATION APPROVED BY THE FIRE DEPARTMENT.
 38A) PLEASE SHOW COMPLIANCE WITH FBC-B 911.1.4. LAYOUT
 APPROVAL. A LAYOUT OF THE FIRE COMMAND CENTER AND ALL
 FEATURES REQUIRED BY THIS SECTION TO BE CONTAINED
 THEREIN SHALL BE SUBMITTED FOR APPROVAL PRIOR TO
 INSTALLATION.
 38B) 911.1.5 REQUIRED FEATURES.
 THE FIRE COMMAND CENTER SHALL COMPLY WITH NFPA 72 AND
 SHALL CONTAIN THE FOLLOWING FEATURES:
  
 1. THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM
 CONTROL UNIT.
  
 2. THE FIRE DEPARTMENT COMMUNICATIONS SYSTEM.
  
 3. FIRE DETECTION AND ALARM SYSTEM ANNUNCIATOR.
  
 4. ANNUNCIATOR UNIT VISUALLY INDICATING THE LOCATION OF
 THE ELEVATORS AND WHETHER THEY ARE OPERATIONAL.
  
 5. STATUS INDICATORS AND CONTROLS FOR AIR DISTRIBUTION
 SYSTEMS.
  
 6. THE FIRE-FIGHTER?S CONTROL PANEL REQUIRED BY SECTION
 909.16 FOR SMOKE CONTROL SYSTEMS INSTALLED IN THE
 BUILDING.
  
 7. CONTROLS FOR UNLOCKING STAIRWAY DOORS
 SIMULTANEOUSLY.
  
 8. SPRINKLER VALVE AND WATERFLOW DETECTOR DISPLAY
 PANELS.
  
 9. EMERGENCY AND STANDBY POWER STATUS INDICATORS.
  
 10. A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED
 ACCESS TO THE PUBLIC TELEPHONE SYSTEM.
  
 11. FIRE PUMP STATUS INDICATORS.
  
 12. SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL
 FLOOR PLAN AND DETAILING THE BUILDING CORE, MEANS OF
 EGRESS, FIRE PROTECTION SYSTEMS, FIRE-FIGHTING
 EQUIPMENT AND FIRE DEPARTMENT ACCESS AND THE LOCATION
 OF FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE
 BARRIERS AND SMOKE PARTITIONS.
  
 13. AN APPROVED BUILDING INFORMATION CARD THAT
 CONTAINS, BUT IS NOT LIMITED TO, THE FOLLOWING
 INFORMATION:
  
 13.1. GENERAL BUILDING INFORMATION THAT INCLUDES:
 PROPERTY NAME, ADDRESS, THE NUMBER OF FLOORS IN THE
 BUILDING (ABOVE AND BELOW GRADE), USE AND OCCUPANCY
 CLASSIFICATION (FOR MIXED USES, IDENTIFY THE DIFFERENT
 TYPES OF OCCUPANCIES ON EACH FLOOR), ESTIMATED BUILDING
 POPULATION (I.E., DAY, NIGHT, WEEKEND);
  
 13.2. BUILDING EMERGENCY CONTACT INFORMATION THAT
 INCLUDES: A LIST OF THE BUILDING?S EMERGENCY CONTACTS
 (E.G., BUILDING MANAGER, BUILDING ENGINEER, ETC.) AND
 THEIR RESPECTIVE WORK PHONE NUMBER, CELL PHONE NUMBER,
 EMAIL ADDRESS;
  
 13.3. BUILDING CONSTRUCTION INFORMATION THAT INCLUDES:
 THE TYPE OF BUILDING CONSTRUCTION (E.G., FLOORS, WALLS,
 COLUMNS, AND ROOF ASSEMBLY);
  
 13.4. EXIT STAIR INFORMATION THAT INCLUDES: NUMBER OF
 EXIT STAIRS IN BUILDING, EACH EXIT STAIR DESIGNATION
 AND FLOORS SERVED, LOCATION WHERE EACH EXIT STAIR
 DISCHARGES, EXIT STAIRS THAT ARE PRESSURIZED, EXIT
 STAIRS PROVIDED WITH EMERGENCY LIGHTING, EACH EXIT
 STAIR THAT ALLOWS REENTRY, EXIT STAIRS PROVIDING ROOF
 ACCESS; ELEVATOR INFORMATION THAT INCLUDES: NUMBER OF
 ELEVATOR BANKS, ELEVATOR BANK DESIGNATION, ELEVATOR CAR
 NUMBERS AND RESPECTIVE FLOORS THAT THEY SERVE, LOCATION
 OF ELEVATOR MACHINE ROOMS, LOCATION OF SKY LOBBY,
 LOCATION OF FREIGHT ELEVATOR BANKS;
  
 13.5. BUILDING SERVICES AND SYSTEM INFORMATION THAT
 INCLUDES: LOCATION OF MECHANICAL ROOMS, LOCATION OF
 BUILDING MANAGEMENT SYSTEM, LOCATION AND CAPACITY OF
 ALL FUEL OIL TANKS, LOCATION OF EMERGENCY GENERATOR,
 LOCATION OF NATURAL GAS SERVICE;
  
 13.6. FIRE PROTECTION SYSTEM INFORMATION THAT INCLUDES:
 LOCATIONS OF STANDPIPES, LOCATION OF FIRE PUMP ROOM,
 LOCATION OF FIRE DEPARTMENT CONNECTIONS, FLOORS
 PROTECTED BY AUTOMATIC SPRINKLERS, LOCATION OF
 DIFFERENT TYPES OF SPRINKLER SYSTEMS INSTALLED (E.G.,
 DRY, WET, PRE-ACTION, ETC.); AND
  
 13.7 HAZARDOUS MATERIAL INFORMATION THAT INCLUDES:
 LOCATION OF HAZARDOUS MATERIAL, QUANTITY OF HAZARDOUS
 MATERIAL.
  
 14. WORK TABLE.
  
 15. GENERATOR SUPERVISION DEVICES, MANUAL START AND
 TRANSFER FEATURES.
  
 16. PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED
 BY OTHER SECTIONS OF THIS CODE.
  
 17. ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME
 A17.1.
  
 18. ELEVATOR EMERGENCY OR STANDBY POWER SELECTOR
 SWITCH(ES), WHERE EMERGENCY OR STANDBY POWER IS
 PROVIDED.
  
 39) 2014 FBC-B 403.5.3 STAIRWAY DOOR OPERATION.
 STAIRWAY DOORS OTHER THAN THE EXIT DISCHARGE DOORS
 SHALL BE PERMITTED TO BE LOCKED FROM THE STAIRWAY SIDE.
 STAIRWAY DOORS THAT ARE LOCKED FROM THE STAIRWAY SIDE
 SHALL BE CAPABLE OF BEING UNLOCKED SIMULTANEOUSLY
 WITHOUT UNLATCHING UPON A SIGNAL FROM THE FIRE COMMAND
 CENTER.
  
 40) PLEASE SUBMIT DOCUMENTATION FOR THE FOLLOWING:
 FBC-B 403.4.7 SMOKE REMOVAL./ 909.4 ANALYSIS.
 A RATIONAL ANALYSIS SUPPORTING THE TYPES OF SMOKE
 CONTROL SYSTEMS TO BE EMPLOYED, THEIR METHODS OF
 OPERATION, THE SYSTEMS SUPPORTING THEM AND THE METHODS
 OF CONSTRUCTION TO BE UTILIZED SHALL ACCOMPANY THE
 SUBMITTED CONSTRUCTION DOCUMENTS AND SHALL INCLUDE, BUT
 NOT BE LIMITED TO, THE ITEMS INDICATED IN SECTIONS
 909.4.1 THROUGH 909.4.6.
  
 41) PLEASE SHOW HOW COMPLIANCE WITH FBC-B 403.5.5
 LUMINOUS EGRESS PATH MARKINGS.
 LUMINOUS EGRESS PATH MARKINGS SHALL BE PROVIDED IN
 ACCORDANCE WITH SECTION 1024. FBC-B 1024.1 APPROVED
 LUMINOUS EGRESS PATH MARKINGS DELINEATING THE EXIT PATH
 SHALL BE PROVIDED IN HIGH-RISE BUILDINGS OF GROUP A, B,
 E, I, M, AND R-1 OCCUPANCIES IN ACCORDANCE WITH
 SECTIONS 1024.1 THROUGH 1024.5.
  
 42) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 43) FOR THE RESUBMISSION OF PLANS, PLEASE BREAK THE
 PLAN SETS DOWN TO SMALLER MANAGEABLE ROLLS. BUILDING
 AND ID DRAWINGS TOGETHER, STRUCTURAL BY ITSELF AND MEP
 TOGETHER.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  