2016-07-18 06:27:44 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16061443 |
| ADD: 718 S. DIXIE HWY. / CANOPY BY HILTON |
| CONT: TBD/ TO BE DETERMINED |
| TEL: 561-718-5987 / MARGARET LEON |
| E-MAIL: MLEONDADLP.COM |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 1ST REVIEW |
| DATE: THURS. JULY 14/2016 - MON. JULY 18/2016 |
| ACTION: DENIED |
| |
| 1) DISCREPANCY IN PLANS AND THE PERMIT APPLICATION. THE |
| AMOUNT OF STORIES IN THIS PROJECT? THE PERMIT |
| APPLICATION INDICATES THIS IS A 17 STORY HOTEL . SEE |
| SHEET A0.01. INDICATES UNDER THE BUILDING DESCRIPTION |
| THIS A 6 STORY MID-RISE. WHEN YOU REVIEW THE SHEET |
| INDEX, THERE ARE 13 STORIES INCLUDING THE HABITABLE |
| POOL, POOL DECK AND A2 DELI/ RESTAURANT AREAS. |
| |
| 2) ART IN PUBLIC PLACES. THE CITY OF WEST PALM BEACH |
| ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES |
| TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH |
| THE PERMIT APPLICATION WAS SUBMITTED AFTER 6/29/2014, |
| AND THE TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO |
| OR GREATER THAN $750,000 WILL NEED TO COMPLY WITH THIS |
| ORDINANCE. |
| PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND |
| CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V, |
| ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION |
| 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL |
| PROJECT CONSTRUCTION COST. |
| PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE |
| V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND |
| NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO |
| THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE |
| PROJECTS. |
| FOR CONTACT INFORMATION PLEASE CONTACT: |
| MS. SYBILLE WELTER |
| ART IN PUBLIC PLACES COORDINATOR |
| TEL: 822-1515 |
| E-MAIL: [email protected] |
| WEBSITE: WPB.ORG/AIPP/ |
| |
| |
| 3) THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR |
| THE MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS. |
| WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING |
| PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE |
| QUALIFIER AND OWNER AND BRINGS IN THE LISTED |
| SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE |
| QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND |
| LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE |
| FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN |
| LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR |
| EACH PERMIT. |
| |
| ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, EXHAUST |
| HOODS, ANSUL SYSTEMS OR ALTERNATIVE AUTOMATIC |
| FIRE-EXTINGUISHING SYSTEMS , WALK IN COOLERS & |
| FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL |
| TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED |
| SUB-PERMITS, AWNING, CANOPY, FENCE, LANDSCAPE , |
| IRRIGATION, TEST PILE, AUGER CAST PILE AND OR |
| FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE |
| REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT. |
| PLEASE LIST AND SUBTRACT THESE LINE ITEMS AND THEIR |
| VALUE FROM THE OVERALL BUILDING VALUE OF |
| $33,000,000.00. THE REMAINING BALANCE WILL BE |
| AFFECTIVELY THE VALUE OF THE BUILDING YOU WILL BE |
| PAYING FOR THIS PERMIT. THE BUILDING DOES NOT WANT TO |
| COLLECT TWICE FOR THE VALUE OF THESE SUB-PERMITS NOT |
| COVERED UNDER THE PRIME OR MASTER PERMIT. |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION 108.3 BUILDING PERMIT VALUATION. |
| |
| 4) PLEASE SHOW ENERGY CODE COMPLIANCE, MISSING |
| DOCUMENTATION. SHOW COMPLIANCE BY THE 2014 FBC-ENERGY |
| CODE C401.2 APPLICATION. |
| COMMERCIAL BUILDINGS SHALL COMPLY WITH ONE OF THE |
| FOLLOWING: |
| 1. THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1. |
| 2. THE REQUIREMENTS OF SECTIONS C402, C403, C404 AND |
| C405. IN ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY |
| WITH EITHER SECTION C406.2, C406.3 OR C406.4. |
| 3. THE REQUIREMENTS OF SECTION C407, C402.4, C403.2, |
| C404, C405.2, C405.3, C405.4, C405.6 AND C405.7. THE |
| BUILDING ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85 |
| PERCENT OF THE STANDARD REFERENCE DESIGN BUILDING. |
| |
| 5) THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING. |
| THRESHOLD BUILDING / FL S. S. 553.71(7) ?THRESHOLD |
| BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN |
| (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN |
| ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE |
| FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN |
| AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| PERSONS. |
| |
| 5A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING |
| AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL |
| INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A |
| THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION |
| PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL |
| INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING |
| AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR |
| THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE |
| OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE |
| SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT |
| THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| WITH THE PERMITTED DOCUMENTS. |
| SHEET S1.02 IS LABELED STRUCTURAL INSPECTION PLAN THIS |
| SHEET MAY NEED TO BE RENAMED TO THRESHOLD INSPECTION |
| PLAN TO MEET THE COMMENT 3A. |
| |
| 5B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. |
| CONSTRUCTION SERVICES DEPARTMENT REQUESTS FOR THRESHOLD |
| BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S |
| 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS |
| REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS |
| ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH |
| INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND |
| REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE |
| PLACE. |
| |
| 5C) COMPLIED FOUND ON ARCHITECTURAL AND STRUCTURAL |
| SHEETS. THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B. |
| AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH |
| ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT |
| OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE |
| BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE |
| PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE |
| FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| FLORIDA STATUTE. |
| |
| 5D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' |
| OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE |
| RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| AN INTERVIEW WILL BE SCHEDULED. |
| |
| 5E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| HISTORY FOR THIS TYPE OF CONSTRUCTION. THRESHOLD |
| INSPECTION FORMS , GUIDELINES AND POLICIES FOR PROJECTS |
| WERE E-MAILED TO: |
| [email protected], PLEASE NOTE THIS E-MAIL ADDRESS CAME |
| BACK UNDELIVERABLE. 07/14/2016 11:35 AM. |
| [email protected] |
| |
| 5F) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE |
| REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, |
| PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING |
| ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE |
| APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR |
| PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN |
| COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR |
| THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE |
| IN BLACK & WHITE.. |
| 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD |
| BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS |
| CONCERNING SPECIAL INSPECTORS. |
| |
| 5G) 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES, |
| PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT |
| AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING |
| INSTALLATION SHALL BE SUPERVISED, INSPECTED AND |
| CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING |
| DOCUMENTS BY THE CONTRACTOR. |
| 5H) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED |
| TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL |
| BUILDING INSPECTIONS FOR AUDITING OF JOBSITE |
| INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6 |
| MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. |
| |
| 5I) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES |
| FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER |
| HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE |
| MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR |
| WALLS AND CEILINGS. |
| |
| 6) SHEET C-01 INDICATES THE PROPOSED SITE IS MADE UP OF |
| 4 LOTS. UNDER THE 2014 FBC-B TABLE 602, BUILDINGS |
| CANNOT BE BUILT OVER PROPERTY LINES. EITHER A REPLAT OF |
| THE 4 LOTS WILL NEED TO OCCUR OR A UNITY OF TITLE. |
| UNITY OF TITLE. THE PROPOSED BUILDING STRUCTURE |
| TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE LOTS |
| WHICH COMBINE TO FORM 'THE SITE'. A 'UNITY OF TITLE' |
| SHALL BE RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A |
| COPY OF THE RECORDED 'UNITY OF TITLE' DOCUMENT SO THAT |
| FBC TABLE 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED |
| NOT APPLICABLE. SEE WEBSITE FOR APPLICATION: |
| HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP |
| "APPLICATION FOR UNITY OF TITLE" |
| HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45 |
| -38-UNITYOFTITLE3.PDF |
| VINCENT J NOEL |
| SURVEYOR/REAL ESTATE SUPERVISOR |
| ENGINEERING SERVICES DEPARTMENT |
| 401 CLEMATIS STREET |
| WEST PALM BEACH, FL 33401 |
| PHONE: 494-1040 EXT: 1096 |
| FAX: 494-1116 |
| E-MAIL: [email protected] |
| ********************************************* |
| MANUEL JULIAN GONZALEZ |
| ENGINEERING PROJECT COORDINATOR |
| ENGINEERING SERVICES DEPARTMENT |
| 401 CLEMATIS STREET, 4TH FLOOR |
| WEST PALM BEACH, FL 33401 |
| (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) |
| MAIN PHONE: (561) 822-1200 |
| DIRECT: (561) 494-1085 |
| FAX: (561) 494-1116 |
| MOBILE: (561) 644-7301 |
| EMAIL: [email protected] |
| WWW.WPB.ORG/ENGINEERING |
| |
| 7) PERIMETER FENCING UNDER A SEPARATE PERMIT. PLEASE |
| PROVIDE COMPLIANCE WITH: 2014 FBC-B 3306.5 BARRIERS. |
| BARRIERS SHALL BE A MINIMUM OF 8 FEET (2438 MM) IN |
| HEIGHT AND SHALL BE PLACED ON THE SIDE OF THE WALKWAY |
| NEAREST THE CONSTRUCTION. BARRIERS SHALL EXTEND THE |
| ENTIRE LENGTH OF THE CONSTRUCTION SITE. |
| |
| 8) 2014 FBC0B 3306.2 WALKWAYS. A WALKWAY SHALL BE |
| PROVIDED FOR PEDESTRIAN TRAVEL IN FRONT OF EVERY |
| CONSTRUCTION AND DEMOLITION SITE UNLESS THE APPLICABLE |
| GOVERNING AUTHORITY AUTHORIZES THE SIDEWALK TO BE |
| FENCED OR CLOSED. WALKWAYS SHALL BE OF SUFFICIENT WIDTH |
| TO ACCOMMODATE THE PEDESTRIAN TRAFFIC, BUT IN NO CASE |
| SHALL THEY BE LESS THAN 4 FEET (1219 MM) IN WIDTH. |
| WALKWAYS SHALL BE PROVIDED WITH A DURABLE WALKING |
| SURFACE. WALKWAYS SHALL BE ACCESSIBLE IN ACCORDANCE |
| WITH CHAPTER 11 AND SHALL BE DESIGNED TO SUPPORT ALL |
| IMPOSED LOADS AND IN NO CASE SHALL THE DESIGN LIVE LOAD |
| BE LESS THAN 150 POUNDS PER SQUARE FOOT (PSF). WILL THE |
| WALKWAYS ON THE SOUTH SIDE OF TRINITY PLACE BE CLOSED? |
| |
| 9) 2014 FBC-B 3306.7 COVERED WALKWAYS. COVERED WALKWAYS |
| SHALL HAVE A CLEAR HEIGHT OF NOT LESS THAN 8 FEET (2438 |
| MM) AS MEASURED FROM THE FLOOR SURFACE TO THE CANOPY |
| OVERHEAD. ADEQUATE LIGHTING SHALL BE PROVIDED AT ALL |
| TIMES. COVERED WALKWAYS SHALL BE DESIGNED TO SUPPORT |
| ALL IMPOSED LOADS. IN NO CASE SHALL THE DESIGN LIVE |
| LOAD BE LESS THAN 150 PSF FOR THE ENTIRE STRUCTURE. |
| |
| 10) PLEASE PROVIDE COMPLIANCE WITH: POLLUTION |
| PREVENTION PLAN. 2014 FBC-B 3307.1 PROTECTION REQUIRED. |
| ADJOINING PUBLIC AND PRIVATE PROPERTY SHALL BE |
| PROTECTED FROM DAMAGE DURING CONSTRUCTION, REMODELING |
| AND DEMOLITION WORK. PROVISIONS SHALL BE MADE TO |
| CONTROL WATER RUNOFF AND EROSION DURING CONSTRUCTION OR |
| DEMOLITION ACTIVITIES. THE PERSON MAKING OR CAUSING AN |
| EXCAVATION TO BE MADE SHALL PROVIDE WRITTEN NOTICE TO |
| THE OWNERS OF ADJOINING BUILDINGS ADVISING THEM THAT |
| THE EXCAVATION IS TO BE MADE AND THAT THE ADJOINING |
| BUILDINGS SHOULD BE PROTECTED. SAID NOTIFICATION SHALL |
| BE DELIVERED NOT LESS THAN 10 DAYS PRIOR TO THE |
| SCHEDULED STARTING DATE OF THE EXCAVATION. |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION 109.3.10 IMPACT OF CONSTRUCTION. ALL |
| CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL BE |
| PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT THE |
| CONDITION OF ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS |
| PERMITTED TO AFFECT SAID PROPERTY PURSUANT TO CONSENT |
| BY THE APPLICABLE PROPERTY OWNER, UNDER TERMS & |
| CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY OWNER. |
| THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF |
| DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE |
| STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION |
| ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE |
| WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY |
| REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH |
| ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS |
| OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS, |
| CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL |
| DEVELOPMENT, INCLUDING ADDITIONS, POOLS, PATIOS, |
| DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING |
| PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ. |
| FT. OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A |
| PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED |
| DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS |
| PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A |
| CERTIFICATION FROM A LICENSED ENGINEER SHALL BE |
| SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL |
| OF THE FINAL INSPECTION. |
| |
| 11) PLEASE PROVIDE DETAILS SHOWING HOW COMPLIANCE WITH |
| 2014 FBC-B 3306.9 ADJACENT TO EXCAVATIONS. |
| EVERY EXCAVATION ON A SITE LOCATED 5 FEET (1524 MM) OR |
| LESS FROM THE STREET LOT LINE SHALL BE ENCLOSED WITH A |
| BARRIER NOT LESS THAN 6 FEET (1829 MM) IN HEIGHT. WHERE |
| LOCATED MORE THAN 5 FEET (1524 MM) FROM THE STREET LOT |
| LINE, A BARRIER SHALL BE ERECTED WHERE REQUIRED BY THE |
| BUILDING OFFICIAL. BARRIERS SHALL BE OF ADEQUATE |
| STRENGTH TO RESIST WIND PRESSURE AS SPECIFIED IN |
| CHAPTER 16. |
| |
| 11A) PLEASE PROVIDE DETAILS SHOWING COMPLIANCE WITH |
| 2014 FBC-B 3307.1 PROTECTION REQUIRED. ADJOINING PUBLIC |
| AND PRIVATE PROPERTY SHALL BE PROTECTED FROM DAMAGE |
| DURING CONSTRUCTION AND DEMOLITION WORK. PROTECTION |
| SHALL BE PROVIDED FOR FOOTINGS, FOUNDATIONS, PARTY |
| WALLS, CHIMNEYS, SKYLIGHTS AND ROOFS. WITH THE |
| EXCAVATION AND AUGER CAST PILE HOW WILL THE BUILDING TO |
| THE SOUTH BE PROTECTED FROM SETTLEMENT? |
| |
| 11B) 2014 FBC-B 3307.1 THE PERSON MAKING OR CAUSING AN |
| EXCAVATION TO BE MADE SHALL PROVIDE WRITTEN NOTICE TO |
| THE OWNERS OF ADJOINING BUILDINGS ADVISING THEM THAT |
| THE EXCAVATION IS TO BE MADE AND THAT THE ADJOINING |
| BUILDINGS SHOULD BE PROTECTED. SAID NOTIFICATION SHALL |
| BE DELIVERED NOT LESS THAN 10 DAYS PRIOR TO THE |
| SCHEDULED STARTING DATE OF THE EXCAVATION. |
| |
| 12) WHEN EXCAVATING WILL THE EXCESS SOILS BE STORED ON |
| SITE? 2014 FBC-B 3304.1.2 SURCHARGE. NO FILL OR OTHER |
| SURCHARGE LOADS SHALL BE PLACED ADJACENT TO ANY |
| BUILDING OR STRUCTURE UNLESS SUCH BUILDING OR STRUCTURE |
| IS CAPABLE OF WITHSTANDING THE ADDITIONAL LOADS CAUSED |
| BY THE FILL OR SURCHARGE. EXISTING FOOTINGS OR |
| FOUNDATIONS WHICH CAN BE AFFECTED BY ANY EXCAVATION |
| SHALL BE UNDERPINNED ADEQUATELY OR OTHERWISE PROTECTED |
| AGAINST SETTLEMENT AND SHALL BE PROTECTED AGAINST LATER |
| MOVEMENT. |
| |
| 13) PLEASE DOCUMENT COMPLIANCE WITH: 2014 FBC-B 3313.1 |
| WHERE REQUIRED. AN APPROVED WATER SUPPLY FOR FIRE |
| PROTECTION, EITHER TEMPORARY OR PERMANENT, SHALL BE |
| MADE AVAILABLE AS SOON AS COMBUSTIBLE MATERIAL ARRIVES |
| ON THE SITE. PLEASE PROVIDE WHERE THIS CONNECTION WILL |
| BE MADE. |
| |
| 14) NOTICE: 2014 FBC-B [F] 3311.1 WHERE REQUIRED. IN |
| BUILDINGS REQUIRED TO HAVE STANDPIPES BY SECTION |
| 905.3.1, NOT LESS THAN ONE STANDPIPE SHALL BE PROVIDED |
| FOR USE DURING CONSTRUCTION. SUCH STANDPIPES SHALL BE |
| INSTALLED WHEN THE PROGRESS OF CONSTRUCTION IS NOT MORE |
| THAN 40 FEET (12 192 MM) IN HEIGHT ABOVE THE LOWEST |
| LEVEL OF FIRE DEPARTMENT VEHICLE ACCESS. SUCH STANDPIPE |
| SHALL BE PROVIDED WITH FIRE DEPARTMENT HOSE CONNECTIONS |
| AT ACCESSIBLE LOCATIONS ADJACENT TO USABLE STAIRS. SUCH |
| STANDPIPES SHALL BE EXTENDED AS CONSTRUCTION PROGRESSES |
| TO WITHIN ONE FLOOR OF THE HIGHEST POINT OF |
| CONSTRUCTION HAVING SECURED DECKING OR FLOORING. |
| 15A) 2014 FBC-B [F] 3309.1 WHERE REQUIRED. ALL |
| STRUCTURES UNDER CONSTRUCTION SHALL BE PROVIDED WITH |
| NOT LESS THAN ONE APPROVED PORTABLE FIRE EXTINGUISHER |
| IN ACCORDANCE WITH SECTION 906 AND SIZED FOR NOT LESS |
| THAN ORDINARY HAZARD AS FOLLOWS: |
| 1. AT EACH STAIRWAY ON ALL FLOOR LEVELS WHERE |
| COMBUSTIBLE MATERIALS HAVE ACCUMULATED. |
| 2. IN EVERY STORAGE AND CONSTRUCTION SHED. |
| 3. ADDITIONAL PORTABLE FIRE EXTINGUISHERS SHALL BE |
| PROVIDED WHERE SPECIAL HAZARDS EXIST, SUCH AS THE |
| STORAGE AND USE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS. |
| |
| 15B) 2014 FBC-B 3309.2 FIRE HAZARDS. THE PROVISIONS OF |
| THIS CODE AND THE FLORIDA FIRE PREVENTION CODE SHALL BE |
| STRICTLY OBSERVED TO SAFEGUARD AGAINST ALL FIRE HAZARDS |
| ATTENDANT UPON CONSTRUCTION OPERATIONS. |
| |
| 16) 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION 109.3.10.1 HURRICANE PROTECTION. IT |
| SHALL BE UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION |
| RELATED MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE |
| OR OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 |
| HRS. AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE |
| HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH |
| CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE |
| EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN |
| SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH |
| CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING |
| DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY |
| PERSONS WHO FAILS TO COMPLY TO COMPLY TO REMOVE OR |
| SECURE THE CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS |
| WITHIN 24 HRS. AFTER A HURRICANE WATCH HAS BEEN ISSUED |
| SHALL BE SUBJECT TO A FINE NOT TO EXCEED $500.00. IN |
| ADDITION TO THE ABOVE, A LICENSED CONTRACTOR WHO |
| VIOLATES THIS SECTION SHALL BE SUBJECT TO DISCIPLINE |
| PURSUANT TO SECTION 113 OF THIS CHAPTER. |
| 17) STRUCTURAL SHEET S1.01 UNDER THE HEADING OF AUGER |
| CAST PILE INDICATES THERE WAS A GEOTECHNICAL STUDY |
| COMPLETED BY LANGAN ENGINEERING & ENVIRONMENTAL |
| SERVICES MAY 21/ 2015 REPORT # 300176801. PLEASE |
| PROVIDE 3 SIGNED AND SEALED ORIGINAL REPORTS. 2014 |
| FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE |
| CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL |
| IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO |
| THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING |
| OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A |
| GEOTECHNICAL INVESTIGATION BE CONDUCTED. |
| 18) SUBMIT PLANS FOR TEST PILE UNDER A SEPARATE PERMIT. |
| COMPLIANCE WITH 2014 WEST PALM BEACH AMENDMENTS TO THE |
| FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION |
| SECTION 117 TESTS. THE BUILDING OFFICIAL MAY REQUIRE |
| TESTS OR TEST REPORTS AS PROOF OF COMPLIANCE. REQUIRED |
| TESTS ARE TO BE MADE AT THE EXPENSE OF THE OWNER, OR |
| AGENT, BY AN APPROVED TESTING LABORATORY OR OTHER |
| APPROVED AGENCY, PLEASE PROVIDE WHAT AGENCY WILL BE |
| MONITORING OF THE TEST AND PRODUCTION PILE? |
| 19) WITH NO SOILS REPORT SUBMITTED PLEASE PROVIDE |
| COMPLIANCE WITH 2014 FBC-B 1803.5.4 GROUND-WATER TABLE. |
| A SUBSURFACE SOIL INVESTIGATION SHALL BE PERFORMED TO |
| DETERMINE WHETHER THE EXISTING GROUND-WATER TABLE IS |
| ABOVE OR WITHIN 5 FEET (1524 MM) BELOW THE ELEVATION OF |
| THE LOWEST FLOOR LEVEL WHERE SUCH FLOOR IS LOCATED |
| BELOW THE FINISHED GROUND LEVEL ADJACENT TO THE |
| FOUNDATION. WILL A DEWATERING PLAN BE NECESSARY FOR |
| THIS LOCATION? |
| 20) SHEET A0.01; |
| 20A) FIRE RESISTANCE RATINGS PER TABLE 601, THE |
| DESIGNER OF RECORD DECIARES A REDUCTION IN HOUR RATING |
| OF FIRE RATING PER FBC-B 403.2.1.1 FOR EXTERIOR BEARING |
| WALLS, INTERIOR BEARING WALLS & THE PRIMARY STRUCTURAL |
| FRAME. THE MATRIX DOES NOT SHOW A SEPARATE LINE ITEM |
| FOR COLUMNS, UNDER SECTION |
| B-403.2.1.1 THE EXCEPTION DOES NOT ALLOW THE REDUCTION |
| OF COLUMNS SUPPORTING FLOORS. THE ONLY REDUCTION THAT |
| CAN BE TAKEN WOULD BE UNDER FOOTNOTE ?A?. |
| |
| 20B) THE BUILDING INSULATION VALUES MAY VERY FROM WHAT |
| IS LISTED SINCE THE ENERGY CALCULATIONS WERE NOT |
| PROVIDED NOR THE METHOD OF COMPLIANCE UNDER THE ENERGY |
| CODE IS A UNKNOWN. 2014 FBC-ENERGY CODE C401.2 |
| APPLICATION. |
| |
| 20C) UNDER THE HEADING BUILDING MATERIALS THE STATEMENT |
| STATES ALL APPROVALS FOR WINDOWS AND DOORS ARE REQUIRED |
| TO BE APPROVED BY MIAMI/DADE COUNTY REQUIREMENTS FOR |
| HIGH VELOCITY HURRICANE ZONE REQUIREMENTS. PLEASE NOTE |
| ONLY BROWARD AND MIAMI-DADE COUNTY ARE UNDER THE HIGH |
| VELOCITY HURRICANE ZONE. SEE DEFINITIONS UNDER 202. |
| HIGH-VELOCITY HURRICANE ZONE. THIS ZONE CONSISTS OF |
| BROWARD AND DADE COUNTIES. |
| |
| 20D) HEADING SUBMITTALS. PRODUCT APPROVALS LISTED BELOW |
| CAN BE DEFERRED SUBMITTALS WITH THE APPROVAL OF EITHER |
| THE DESIGNER OF RECORD OR CONTRACTOR ONCE THE WIND |
| DESIGN CRITERIA IS REVIEWED AND APPROVED THEN THE |
| SUBMITTALS CAN BE SUBMITTED AFTER PERMIT ISSUANCE. |
| |
| 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS |
| SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| FOR REVIEW BY THE BUILDING OFFICIAL. |
| |
| DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| OFFICIAL. |
| |
| 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (B) WINDOWS, MULLIONS |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, EFIS SYSTEMS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS, |
| INTAKE AND EXHAUST FANS |
| (E) SHUTTERS |
| (F) SKYLIGHTS |
| (G PRE-ENGINEERED A/C STANDS |
| |
| 20E) IDENTIFY GLAZING/ MULLIONS. FOR ALL PRODUCTS WITH |
| GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, |
| TYPE OF GLAZING, MULLION INFORMATION IF REQUIRED, |
| ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING |
| SIZE. 107.2.1 CONSTRUCTION DOCUMENTS SHALL BE OF |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| DETERMINED BY THE BUILDING OFFICIAL. |
| |
| 20F) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY |
| ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES |
| FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL |
| LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF |
| ZONES 2 & 3. IF SO RAS 117 CALCULATIONS ARE REQUIRED BY |
| EITHER A FLORIDA ARCHITECT OR ENGINEER. |
| 2014 FBC-B 1603.1.4 WIND DESIGN DATA. 107.2.1.2 FOR |
| ROOF ASSEMBLIES REQUIRED BY THE CODE, THE CONSTRUCTION |
| DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND DELINEATE THE |
| TYPE OF ROOFING SYSTEM, MATERIALS, FASTENING |
| REQUIREMENTS, FLASHING REQUIREMENTS AND WIND RESISTANCE |
| RATING THAT ARE REQUIRED TO BE |
| INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL |
| INDICATE COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR |
| THE SPECIFIC SITE OR A STATEMENT BY AN ARCHITECT OR |
| ENGINEER FOR THE SPECIFIC SITE MUST BE SUBMITTED WITH |
| THE CONSTRUCTION DOCUMENTS. |
| |
| 21) SITE PLAN A1.01 INDICATES THERE ARE 79 PARKING |
| SPACES WITHIN THE BUILDING. SHEET A1.15 THE 5TH FLOOR |
| LIFE SAFETY PLAN THE 3RD PARKING LEVEL SHOWS A TOTAL OF |
| 4 ACCESSIBLE PARKING SPACES, OF THE 4 ACCESSIBLE |
| PARKING SPACES, (1) SPACE NEEDS TO COMPLY WITH THE |
| VERTICAL ACCESSIBILITY REQUIREMENTS OF ACCESS. CODE |
| 502.5 VERTICAL CLEARANCES FROM THE ENTRY OF THE 1ST |
| FLOOR, VEHICLE ELEVATORS INCOMING AND OUTGOING AND THE |
| VEHICLE ROUTE SERVING THEM. SEE ACCESS. CODE 502.5. |
| ADVISORY 502.5 VERTICAL CLEARANCE. |
| SIGNS PROVIDED AT ENTRANCES TO PARKING FACILITIES |
| INFORMING DRIVERS OF CLEARANCES AND THE LOCATION OF VAN |
| ACCESSIBLE PARKING SPACES CAN PROVIDE USEFUL CUSTOMER |
| ASSISTANCE. |
| |
| FLORIDA LAW, S.553.511, F.S., REQUIRES SIGNS BE POSTED |
| THAT WILL WARN HANDICAPPED-EQUIPPED VAN OPERATORS OF |
| HEIGHT LIMITATIONS SO THEY WILL NOT PASS BEYOND A POINT |
| WHERE THE VAN CANNOT BE MANEUVERED. |
| |
| FLORIDA LAW ALSO PREEMPTS LOCAL GOVERNMENT HEIGHT |
| RESTRICTION ORDINANCES THAT WOULD PROHIBIT COMPLIANCE |
| WITH THE MINIMUM HEIGHT REQUIREMENTS OF THIS SECTION. |
| ALSO, ANY LOCAL OR STATE LAW OR REGULATION THAT |
| PROHIBITS A COVERED ENTITY FROM COMPLYING WITH |
| REQUIREMENTS OF THE ADA MAY RENDER SUCH JURISDICTION IN |
| VIOLATION OF THE ADA. |
| |
| 22) 2014 FBC-ACCESS. CODE ADVISORY 502.6 |
| IDENTIFICATION. THE REQUIRED ?VAN ACCESSIBLE? |
| DESIGNATION IS INTENDED TO BE INFORMATIVE, NOT |
| RESTRICTIVE, IN IDENTIFYING THOSE SPACES THAT ARE |
| BETTER SUITED FOR VAN USE. ENFORCEMENT OF MOTOR VEHICLE |
| LAWS, INCLUDING PARKING PRIVILEGES, IS A LOCAL MATTER. |
| PARKING SPACE AND ACCESS AISLE CONFIGURATIONS REQUIRED |
| FOR ALL ACCESSIBLE PARKING BY FLORIDA LAW, S.553.5041, |
| F.S., MEET THE VAN ACCESSIBLE SPACE REQUIREMENTS OF THE |
| ADA STANDARDS FOR ACCESSIBLE DESIGN. THEREFORE, NO |
| ACCESSIBLE SPACE IS MORE SUITABLE THAN ANY OTHER |
| ACCESSIBLE SPACE FOR ?VAN ACCESSIBLE? PARKING. FLORIDA |
| LAW ONLY REQUIRES ?VAN ACCESSIBLE? PARKING SIGNS IN |
| PARKING STRUCTURES WHERE VAN PARKING MAY BE LIMITED TO |
| THE FIRST LEVEL ACCESSIBLE SPACES. FLORIDA ACCESSIBLE |
| PARKING SIGNS MUST INCLUDE INDICATION OF THE PENALTY |
| FOR ILLEGAL PARKING IN ADDITION TO THE ACCESSIBLE |
| PARKING SYMBOL REQUIRED BY THE ADA STANDARDS FOR |
| ACCESSIBLE DESIGN. |
| 23A) SHEET A1.11 GROUND FLOOR LIFE SAFETY PLAN VS. |
| A2.01 GROUND FLOOR PLAN. THIS COMMENT WILL HOLD TRUE |
| FOR ALL FLOORS, WITH THE EXCEPTION OF THE 3 PARKING |
| FLOORS. NEITHER OF THESE PLANS HAVE LABELED, IDENTIFIED |
| THE DOORS ON THE PLAN TO THE DOOR SCHEDULE FOUND ON |
| A8.02. OPENING PROTECTIVES CANNOT BE REVIEWED UNDER |
| FBC-B TABLE 716.5. EXAMPLE STAIR # 1 THERE ARE 3 DOORS |
| ASSOCIATED WITH THE VERTICAL STAIR ENCLOSURE FOUND ON |
| THE 1ST FLOOR. |
| 23B) PLEASE NOTE THE LIFE SAFETY SHEET A1.12 & A2.02 |
| THE OCCUPANT LOAD GIVEN FOR THIS FLOOR IS 581/ 3 EXIT |
| STAIRWELLS IS 194 OCCUPANTS THROUGH THE 3 VERTICAL EXIT |
| DOORWAYS. PLEASE NOTE THE LIFE SAFETY PLAN INDICATES |
| CLEAR WIDTH FOR ALL 3 DOORS IS 34 INCHES WHICH CAN ONLY |
| TAKE 170 OCCUPANTS AT EACH DOORWAY. THE TYPICAL EGRESS |
| CAPACITY LEGEND FOUND ON THE SAME PAGE USES THE MEANS |
| OF EGRESS CAPACITY FACTOR OF 0.2 INCHES PER OCCUPANT |
| OVER THE ALLOWABLE 170 OCCUPANTS THROUGH A CLEAR |
| OPENING OF 34 INCHES FOR ALL EGRESS DOORS ON THE 2 |
| AFFECTED FLOORS 1ST AND 2ND FLOOR. |
| PLEASE ALSO REVIEW THE EXCEPTION TO FBC-B 1005.3.2 THAT |
| REDUCES THE MEANS OF EGRESS LOAD FACTOR FOR DOORS TO |
| 0.15 INCH (3.8 MM) PER OCCUPANT IN BUILDINGS EQUIPPED |
| THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM INSTALLED |
| IN ACCORDANCE WITH SECTION 903.3.1.1 OR 903.3.1.2 AND |
| AN EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM IN |
| ACCORDANCE WITH SECTION 907.5.2.2. |
| 23C) ON THE 1ST FLOOR THE WORST CASE SCENARIO OF 194 |
| OCCUPANTS IS NOT FOUND AS THE OCCUPANT LOAD FOR THE |
| WORST CASE SCENARIO EXITS THE BUILDING. FBC-B 1005.3.2. |
| 23B) THE A1.11 GROUND FLOOR LIFE SAFETY PLAN VS. A2.01 |
| GROUND FLOOR PLAN. COMMON COMMENT FOR ALL FLOORS. |
| NEITHER OF THESE SHEETS SHOW WALL IDENTIFICATION TAGS |
| THAT CORRELATE TO THE WALL RATING FOUND ON SHEET A9.01, |
| EXCEPTION THE 3 PARKING FLOORS. 107.3.5.1.1 MINIMUM |
| PLAN REVIEW CRITERIA FOR COMMERCIAL BUILDINGS. WALL |
| RATINGS. EXTERIOR WALLS SECTION 705, FIRE BARRIERS 707, |
| FIRE PARTITIONS 708, SMOKE BARRIERS, SHAFTS 713. |
| 23C)(1) THE A1.11 GROUND FLOOR LIFE SAFETY PLAN VS. |
| A2.01 GROUND FLOOR PLAN. PLEASE NOTE THE VERTICAL EXIT |
| DOES NOT END AT THE EXTERIOR OF THE BUILDING. THE PLANS |
| SHOW A CONTINUATION OF THIS EXIT LABELED CORRIDOR # 109 |
| WITH A 3 HOUR FIRE RATED WALL ON ONE SIDE AND A 2 HOUR |
| FIRE RATED WALL ON THE OTHER. PLEASE NOTE THIS |
| EXTENSION OF THE VERTICAL EXIT NEEDS TO BE DEFINED AND |
| BUILT AS A 2 HOUR EXIT PASSAGE WAY. 1022.10.1 |
| TERMINATION AND EXTENSION. A SMOKEPROOF ENCLOSURE OR |
| PRESSURIZED STAIRWAY SHALL TERMINATE AT AN EXIT |
| DISCHARGE OR A PUBLIC WAY. |
| 23C)(2) THE A1.11 GROUND FLOOR LIFE SAFETY PLAN VS. |
| A2.01 GROUND FLOOR PLAN. THE EXTERIOR DOOR TO CORRIDOR |
| # 120 LIST THE CLEAR OPENING AS 68 INCHES AND THE |
| MAXIMUM OCCUPANCY THROUGH THIS DOOR AT 340 OCCUPANTS. |
| THE DOOR APPEARS TO BE A 3 FOOT WIDE DOOR. SEE FBC-B |
| 1005.3.2. |
| 23D) THERE IS A DINING ELEMENT TO THE 1ST FLOOR PLEASE |
| PROVIDE WHERE COMPLIANCE WITH 2014 FBC-ACCESS. CODE : |
| 902.1. DINING SURFACES AND WORK SURFACES SHALL COMPLY |
| WITH 902.2 AND 902.3. |
| 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR SPACE |
| COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH |
| SHALL BE PROVIDED. KNEE AND TOE CLEARANCE COMPLYING |
| WITH 306 SHALL BE PROVIDED. |
| 902.3 HEIGHT. THE TOPS OF DINING SURFACES SHALL BE 28 |
| INCHES (710 MM) MINIMUM AND 34 INCHES MAXIMUM ABOVE THE |
| FINISH FLOOR OR GROUND. |
| 904.5 FOOD SERVICE LINES. COUNTERS IN FOOD SERVICE |
| LINES SHALL COMPLY WITH 904.5. |
| 904.5.1 SELF-SERVICE SHELVES AND DISPENSING DEVICES. |
| SELF-SERVICE SHELVES AND DISPENSING DEVICES FOR |
| TABLEWARE, DISHWARE, CONDIMENTS, FOOD AND BEVERAGES |
| SHALL COMPLY WITH 308. |
| 904.5.2 TRAY SLIDES. THE TOPS OF TRAY SLIDES SHALL BE |
| 28 INCHES (710 MM) MINIMUM AND 34 INCHES (865 MM) |
| MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| 23E) ACCESS. CODE 226.1 WHERE DINING SURFACES ARE |
| PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST |
| 5 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT |
| THE DINING SURFACES SHALL COMPLY WITH 902. IN ADDITION, |
| WHERE WORK SURFACES ARE PROVIDED FOR USE BY OTHER THAN |
| EMPLOYEES, AT LEAST 5 PERCENT SHALL COMPLY WITH 902. |
| 23F) ACCESS. CODE 226.2 DISPERSION. DINING SURFACES AND |
| WORK SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE |
| DISPERSED THROUGHOUT THE SPACE OR FACILITY CONTAINING |
| DINING SURFACES AND WORK SURFACES. |
| 23G) SHEET THE A1.11 GROUND FLOOR LIFE SAFETY PLAN VS. |
| A2.01 GROUND FLOOR PLAN. ON THE SOUTH PROPERTY LINE |
| WALL THERE ARE PORTIONS OF THE WALL THAT ARE 1 HOUR |
| FIRE RATED AND SOME PORTIONS RATED FOR 2 HOURS. FBC-B |
| TABLE 601 LIST A 2 HOUR FIRE RATING FOR EXTERIOR FIRE |
| BEARING WALLS. ADDITIONAL INFORMATION REQUIRED. IF |
| THESE WALLS ARE GOING TO BE IN FILE NONBEARING WALLS |
| HOW WILL THE WALL RATING BE MAINTAINED AT THE JOINT |
| LINE TOP COURSE OF BLOCK WHERE THE BEAM WOULD ALREADY |
| BE IN PLACE? |
| 24) SHEET A1.12 LIFE SAFETY 2ND FLOOR VS. A2.02 2ND |
| FLOOR PLAN: |
| 24A) EXITS STAIRS 1,2 &3 ALL INDICATE THEY ARE 57 |
| INCHES WIDE. THE PROPOSED OCCUPANT LOAD FOR THE ENTIRE |
| FLOOR IS 581 OCCUPANTS. 581 OCCUPANTS DIVIDE BY 3= 194 |
| OCCUPANTS PER STAIR. WHEN YOU DIVIDE THE 57 INCHES OF |
| STAIR WIDTH BY THE 0.3 = 190 OCCUPANTS. THE PLANS ARE |
| DEFICIENT BY 4 OCCUPANTS PER STAIRWELL. SEE FBC-B |
| 1005.3.1. THE CAPACITY, IN INCHES (MM), OF MEANS OF |
| EGRESS STAIRWAYS SHALL BE CALCULATED BY MULTIPLYING THE |
| OCCUPANT LOAD SERVED BY SUCH STAIRWAY BY A MEANS OF |
| EGRESS CAPACITY FACTOR OF 0.3 INCH (7.6 MM) PER |
| OCCUPANT. |
| 24B) SHEET A1.12 LIFE SAFETY 2ND FLOOR VS. A2.02 2ND |
| FLOOR PLAN SHOWS AN OCCUPANT LOAD OF 581 OCCUPANTS AND |
| TABLE 1021.1 REQUIRES 3 EXITS THERE IS AN ISSUE WITH |
| FBC-B SECTION 1028.2 FOR THE 2ND FLOOR PLEASE DEFINE |
| THE MAIN EXIT. 1028.2 ASSEMBLY MAIN EXIT. IN A |
| BUILDING, ROOM OR SPACE USED FOR ASSEMBLY PURPOSES THAT |
| HAS AN OCCUPANT LOAD OF GREATER THAN 300 AND IS |
| PROVIDED WITH A MAIN EXIT, THE MAIN EXIT SHALL BE OF |
| SUFFICIENT WIDTH TO ACCOMMODATE NOT LESS THAN ONE-HALF |
| OF THE OCCUPANT LOAD, BUT SUCH WIDTH SHALL NOT BE LESS |
| THAN THE TOTAL REQUIRED WIDTH OF ALL MEANS OF EGRESS |
| LEADING TO THE EXIT. WHERE THE BUILDING IS CLASSIFIED |
| AS A GROUP A OCCUPANCY, THE MAIN EXIT SHALL FRONT ON AT |
| LEAST ONE STREET OR AN UNOCCUPIED SPACE OF NOT LESS |
| THAN 10 FEET (3048 MM) IN WIDTH THAT ADJOINS A STREET |
| OR PUBLIC WAY. IN A BUILDING, ROOM OR SPACE USED FOR |
| ASSEMBLY PURPOSES WHERE THERE IS NO WELL-DEFINED MAIN |
| EXIT OR WHERE MULTIPLE MAIN EXITS ARE PROVIDED, EXITS |
| SHALL BE PERMITTED TO BE DISTRIBUTED AROUND THE |
| PERIMETER OF THE BUILDING PROVIDED THAT THE TOTAL WIDTH |
| OF EGRESS IS NOT LESS THAN 100 PERCENT OF THE REQUIRED |
| WIDTH. |
| THE ISSUE WITH THE 2 EXITS GROUPED ON THE WEST SIDE OF |
| THE BUILDING IF A FIRE BLOCKS THE 2 WEST EXITS 50% OF |
| THE OCCUPANT LOAD IS STILL SUPPOSED TO EXIT OUT OF THE |
| REMAINING EXITS. |
| 1028.3 ASSEMBLY OTHER EXITS. IN ADDITION TO HAVING |
| ACCESS TO A MAIN EXIT, EACH LEVEL IN A BUILDING USED |
| FOR ASSEMBLY PURPOSES HAVING AN OCCUPANT LOAD GREATER |
| THAN 300 AND PROVIDED WITH A MAIN EXIT, SHALL BE |
| PROVIDED WITH ADDITIONAL MEANS OF EGRESS THAT SHALL |
| PROVIDE AN EGRESS CAPACITY FOR AT LEAST ONE HALF OF THE |
| TOTAL OCCUPANT LOAD SERVED BY THAT LEVEL AND SHALL |
| COMPLY WITH SECTION 1015.2. IN A BUILDING USED FOR |
| ASSEMBLY PURPOSES WHERE THERE IS NO WELL-DEFINED MAIN |
| EXIT OR WHERE MULTIPLE MAIN EXITS ARE PROVIDED, EXITS |
| FOR EACH LEVEL SHALL BE PERMITTED TO BE DISTRIBUTED |
| AROUND THE PERIMETER OF THE BUILDING, PROVIDED THAT THE |
| TOTAL WIDTH OF EGRESS IS NOT LESS THAN 100 PERCENT OF |
| THE REQUIRED WIDTH. |
| 24C) PLEASE REVIEW THE MEETING ROOM # 3 THE ROOM HAS AN |
| OCCUPANT LOAD OF 107 OCCUPANTS THE PLEASE SEE SIDE WALL |
| BETWEEN ROOMS 220 & 221. THIS SECTION OF WALL HAS 2 |
| DOORS SWINGING IN OPPOSITE DIRECTIONS. THE REMAINDER OF |
| THE MEETING ROOMS (217, 218 & 219) ALSO HAVE AN |
| OCCUPANT LOAD GREATER THAN 50 REQUIRING A SECOND MEANS |
| OF EGRESS WITH THE DOOR SWINGING IN THE DIRECTION OF |
| TRAVEL. FBC-B 1008.1.2. |
| 24D) THERE IS A NOTE FOR S SMOKE PARTITION FOR THE 2 |
| STORY ATRIUM USING THE EXCEPTION #1 REQUIRING BOTH |
| REQUIREMENTS OF 404.6 EXCEPTION 1.1 & 1.2 BE MET. |
| PLEASE PROVIDE DETAILS FOR THE SPACING OF THE FIRE |
| SPRINKLERS AND COMPLIANCE WITH 1.2 1.2. THE GLASS WALL |
| SHALL BE INSTALLED IN A GASKETED FRAME IN A MANNER THAT |
| THE FRAMING SYSTEM DEFLECTS WITHOUT BREAKING (LOADING) |
| THE GLASS BEFORE THE SPRINKLER SYSTEM OPERATES. |
| 24E) THE DOOR SCHEDULE ON SHEET A8.02 INDICATES IN |
| STAIRWELL 3 AN ACCESS HATCH IDENTIFIED AS S3, NOT |
| IDENTIFIED ON THE FLOOR PLAN. FBC-B 1022.4. OPENINGS IN |
| INTERIOR EXIT STAIRWAYS OTHER THAN UNPROTECTED EXTERIOR |
| OPENINGS SHALL BE LIMITED TO THOSE NECESSARY FOR EXIT |
| ACCESS TO THE ENCLOSURE FROM NORMALLY OCCUPIED SPACES |
| AND FOR EGRESS FROM THE ENCLOSURE. |
| 25) SHEET A1.13 THE 3RD FLOOR PARKING & SHEET A2.03, |
| THESE SHEETS WILL BE COMMON COMMENTS FOR THE 3RD, |
| 4TH AND 5TH FLOORS. |
| |
| 25A) THIS WILL BE A COMMON COMMENT FOR ALL FLOORS. NONE |
| OF THE FLOORS SHOW THE FIRE SERVICE ACCESS ELEVATOR |
| LOBBY TO BE ENCLOSED BY A SMOKE BARRIER HAVING A FIRE |
| RESISTANCE RATING OF NOT LESS THAN 1 HOUR. SEE FBC-B |
| 3007.7.2. THE FIRE SERVICE ACCESS ELEVATOR LOBBY SHALL |
| BE ENCLOSED WITH A SMOKE BARRIER HAVING A |
| FIRE-RESISTANCE RATING OF NOT LESS THAN 1 HOUR, EXCEPT |
| THAT LOBBY DOORWAYS SHALL COMPLY WITH SECTION 3007.7.3. |
| 25B) COMMENT COMMON TO ALL FLOORS. THE FIRE SERVICE |
| ACCESS ELEVATOR LOBBY ENTRY DOORS IN THE DOOR |
| SCHEDULEA8.02 ARE NOT FIRE RATED. 3007.7.3 LOBBY |
| DOORWAYS. OTHER THAN THE DOOR TO THE HOIST WAY, EACH |
| DOORWAY TO A FIRE SERVICE ACCESS ELEVATOR LOBBY SHALL |
| BE PROVIDED WITH A 3/4-HOUR FIRE DOOR ASSEMBLY |
| COMPLYING WITH SECTION 716.5. THE FIRE DOOR ASSEMBLY |
| SHALL ALSO COMPLY WITH THE SMOKE AND DRAFT CONTROL DOOR |
| ASSEMBLY REQUIREMENTS OF SECTION 716.5.3.1 WITH THE UL |
| 1784 TEST CONDUCTED WITHOUT THE ARTIFICIAL BOTTOM SEAL. |
| 25C) COMMENT COMMON TO THE 3 PARKING GARAGE FLOORS. |
| DOOR 303A DOES NOT HAVE 18 INCHES FOR MANEUVERING |
| CLEARANCES ON THE LATCH SIDE OF THE DOOR. SEE |
| FBC-ACCESS. CODE 404.2.4. |
| 25D) NEITHER THE GENERATOR ROOM NOR THE DOOR TO THE |
| GENERATOR ROOM SHOW A FIRE RATING. 2014 FBC-B 403.4.8.1 |
| REQUIRES 2 HOUR FIRE RATED WALLS WITH 1 ? HOUR OPENING |
| PROTECTIVES. TABLE 716.5. |
| 25E) THIS COMMENT IS A COMMON FOR THE 3 PARKING FLOORS |
| AND THE 1ST FLOOR. THE PLANS INDICATE TO PROVIDE FALL |
| PROTECTION AT THE ENTRY OF THE AUTOMOBILE ELEVATOR. |
| PLEASE PROVIDE COMPLIANCE WITH 2014 FBC-B 1013.2 GUARDS |
| SHALL BE LOCATED ALONG OPEN-SIDED, EQUIPMENT PLATFORMS, |
| STAIRS, RAMPS AND LANDINGS THAT ARE LOCATED MORE THAN |
| 30 INCHES (762 MM) MEASURED VERTICALLY TO THE FLOOR OR |
| GRADE BELOW AT ANY POINT WITHIN 36 INCHES (914 MM) |
| HORIZONTALLY TO THE EDGE OF THE OPEN SIDE. GUARDS SHALL |
| BE ADEQUATE IN STRENGTH AND ATTACHMENT IN ACCORDANCE |
| WITH SECTION 1607.8. |
| |
| 25F) THIS IS A COMMON COMMENT FOR THE 3 GARAGE PARKING |
| FLOORS ALL EXTERIOR WALLS WHERE A VEHICLE COULD RUN |
| INTO THE WALL AND THE COMMON WALL BETWEEN THE PARKING |
| GARAGE AND ATRIUM WILL NEED TO SHOW COMPLIANCE WITH |
| 1607.8.3 VEHICLE BARRIERS. VEHICLE BARRIERS FOR |
| PASSENGER VEHICLES SHALL BE DESIGNED TO RESIST A |
| CONCENTRATED LOAD OF 6,000 POUNDS IN ACCORDANCE WITH |
| SECTION 4.5.3 OF ASCE 7. ASCE 7-10 SECTION 4.5.3 FOR |
| DESIGN OF THE SYSTEM, THE LOADS SHALL BE ASSUME TO ACT |
| BETWEEN 1FT. 6 INCHES AND 2 FT. 3 INCHES ABOVE THE |
| FINISH FLOOR SURFACE, LOCATED TO PRODUCE A MAXIMUM LOAD |
| EFFECTS. THE LOAD SHALL BE APPLIED ON AN AREA NOT TO |
| EXCEED 12 IN. BY 12 IN. |
| |
| 25G) SHEET A2.05 LIFE SAFETY PLAN INDICATES 2 |
| ACCESSIBLE PARKING STALLS WITH COLUMNS IN THE ACCESS |
| AISLE. PLEASE PROVIDE THE CLEAR WIDTH FROM THE COLUMN |
| TO THE ACCESSIBLE PARKING STALL. FBC-ACCESSIBILITY CODE |
| 502.3.1 WIDTH. ACCESS AISLES SERVING CAR AND VAN |
| PARKING SPACES SHALL BE 60 INCHES (1525 MM) WIDE |
| MINIMUM. |
| 26) SHEET A1.16 6TH FLOOR LIFE SAFETY PLAN & A7.05 & |
| A7.06 ENLARGED FLOOR PLAN 6TH FLOOR. |
| 26A) COMMON COMMENT ALL FLOORS. THERE IS A UNKNOWN WALL |
| TYPE NO SHOWN ON EITHER PLANS WITHIN THE LINEN SHOOT |
| ENCLOSURE, THE WALL IN COMMON WITH THE HOUSE KEEPING |
| ROOM IS NOT IDENTIFIED. THIS WALL SHOULD BE A 2 HOUR |
| FIRE RATED WALL, IT IS PART OF THE SHAFT ENCLOSURE. |
| FBC-B 713.4 FIRE-RESISTANCE RARING. |
| |
| 26B) COMMON COMMENT ALL FLOORS. THE DOOR TO GAIN ENTRY |
| INTO THE HOUSE KEEPING ROOM IS LABELED X23. |
| SHEET A8.02 THE DOOR SCHEDULE INDICATES UNDER NOTE 22 |
| THIS DOOR IS A ?DUTCH DOOR? THIS DOOR PROVIDE 2 LEAVES, |
| ONE ABOVE THE OTHER. PLEASE PROVIDE THE TESTED ASSEMBLY |
| FOR THIS TYPE OF CONFIGURATION, WHERE IS THE BREAK IN |
| THE DOOR TO OCCUR, WHERE WILL THE LOCK SET BE LOCATED, |
| WHAT ASSEMBLY IS TO HOLD THE DOOR TOGETHER, WILL THE |
| TOP AND BOTTOM PORTIONS OF THE DOOR BE ON SPRING TYPE |
| HINGES, WILL BOTH HALVES OF THE DOOR BE ON HOLD OPEN |
| DEVISES THAT WILL ACTIVATE UPON FIRE AND OR SMOKE |
| ALARM? NOTE 19 INDICATES A VIEW PANEL, HOW LARGE OF A |
| VIEW PANEL. MISSING INFORMATION 107.2.1.3. TABLE 716.5/ |
| 716.5.8 GLAZING MATERIAL. FIRE-PROTECTION-RATED GLAZING |
| CONFORMING TO THE OPENING PROTECTION REQUIREMENTS IN |
| SECTION 716.5 SHALL BE PERMITTED IN FIRE DOOR |
| ASSEMBLIES. |
| 716.5.8.1 SIZE LIMITATIONS. FIRE-PROTECTION-RATED |
| GLAZING SHALL COMPLY WITH THE SIZE LIMITATIONS OF NFPA |
| 80, AND AS PROVIDED IN SECTIONS 716.5.8.1.1 AND |
| 716.5.8.1.2. |
| |
| 26C) SHEET A6.13 LINEN CHUTE DETAIL SHEET. PLEASE NOTE |
| SECTION DETAILS OF THE LINEN CHUTE ARE MISSING 2 |
| DETAILS; |
| 26C)(1) THE DETAIL DOES NOT INCLUDE THE HOUSING OR NOTE |
| FOR THE REQUIREMENT OF FBC-B 903.2.11.2 RUBBISH AND |
| LINEN CHUTES. |
| AN AUTOMATIC SPRINKLER SYSTEM SHALL BE INSTALLED AT THE |
| TOP OF RUBBISH AND LINEN CHUTES AND IN THEIR TERMINAL |
| ROOMS. CHUTES SHALL HAVE ADDITIONAL SPRINKLER HEADS |
| INSTALLED AT ALTERNATE FLOORS AND AT THE LOWEST INTAKE. |
| WHERE A RUBBISH CHUTE EXTENDS THROUGH A BUILDING MORE |
| THAN ONE FLOOR BELOW THE LOWEST INTAKE, THE EXTENSION |
| SHALL HAVE SPRINKLERS INSTALLED THAT ARE RECESSED FROM |
| THE DROP AREA OF THE CHUTE AND PROTECTED FROM FREEZING |
| IN ACCORDANCE WITH SECTION 903.3.1.1. SUCH SPRINKLERS |
| SHALL BE INSTALLED AT ALTERNATE FLOORS, BEGINNING WITH |
| THE SECOND LEVEL BELOW THE LAST INTAKE AND ENDING WITH |
| THE FLOOR ABOVE THE DISCHARGE. CHUTE SPRINKLERS SHALL |
| BE ACCESSIBLE FOR SERVICING. ACCESS DOOR REQUIRED. |
| |
| 26C)(2) MISSING DETAIL FOR THE ACCESS DOOR INTO THE |
| CHUTE ITSELF AND NOTE FOR THE FIRE RATING OF THE |
| ASSEMBLY. FBC-B 713.13.1 REFUSE, RECYCLING AND LAUNDRY |
| CHUTE ENCLOSURES. OPENINGS INTO THE SHAFT, INCLUDING |
| THOSE FROM ACCESS ROOMS AND TERMINATION ROOMS, SHALL BE |
| PROTECTED IN ACCORDANCE WITH THIS SECTION AND SECTION |
| 716. OPENINGS INTO CHUTES SHALL NOT BE LOCATED IN |
| CORRIDORS. DOORS SHALL BE SELF- OR AUTOMATIC-CLOSING |
| UPON THE ACTUATION OF A SMOKE DETECTOR IN ACCORDANCE |
| WITH SECTION 716.5.9.3. |
| |
| 26D) COMMON COMMENT FOR 6-12 FLOORS THE 2 HOUR FIRE |
| RATED SHAFT BEHIND THE SERVICE ELEVATOR AND P1 ELEVATOR |
| DO NOT HAVE THE WALL IDENTIFICATION TAGS. 107.2.1.3. |
| ADDITIONAL INFORMATION REQUIRED. |
| |
| 26E) PLEASE PROVIDE IF THERE ARE ANY DWELLING UNITS |
| WITHIN THE FLOORS 6-12? DEFINITION: |
| DWELLING UNIT. A SINGLE UNIT PROVIDING COMPLETE, |
| INDEPENDENT LIVING FACILITIES FOR ONE OR MORE PERSONS, |
| INCLUDING PERMANENT PROVISIONS FOR LIVING, SLEEPING, |
| EATING, COOKING AND SANITATION. |
| |
| SLEEPING UNIT. A ROOM OR SPACE IN WHICH PEOPLE SLEEP, |
| WHICH CAN ALSO INCLUDE PERMANENT PROVISIONS FOR LIVING, |
| EATING, AND EITHER SANITATION OR KITCHEN FACILITIES BUT |
| NOT BOTH. SUCH ROOMS AND SPACES THAT ARE ALSO PART OF A |
| DWELLING UNIT ARE NOT SLEEPING UNITS. |
| |
| IF THERE ARE DWELLING UNITS THEN CODE REQUIREMENTS FOR |
| : |
| FBC-B 2010 1207.2 AIR-BORNE SOUND. |
| FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND. |
| FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2. FLOOR |
| INSULATION. INSULATION INSTALLED BETWEEN A |
| FINISHED FLOOR AND SOLID DECKING WITHOUT INTERVENING |
| AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME |
| SPREAD INDEX OF NOT MORE THAN 200. |
| |
| 26F) BUILDING PROVISO/ DEFERRED SUBMITTAL: OPEN AIR |
| TERRACE WATERPROOFING MATERIAL AND DETAILS. SHEET 5.11. |
| ADMINISTRATION 107.3.4 DESIGN PROFESSIONAL IN |
| RESPONSIBLE CHARGE. THE REGISTERED DESIGN |
| PROFESSIONAL IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE |
| FOR REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS |
| PREPARED BY OTHERS, INCLUDING PHASED AND DEFERRED |
| SUBMITTAL ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF |
| THE BUILDING. PRODUCTS SHALL BE REVIEWED AND APPROVED |
| IN WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL. |
| |
| 26G) BUILDING PROVISO/ DEFERRED SUBMITTALS: OPEN AIR |
| TERRACE VIVA BLADE GUARD RAIL SYSTEM. SHEET 5.11. |
| ADMINISTRATION 107.3.4 DESIGN PROFESSIONAL IN |
| RESPONSIBLE CHARGE. THE REGISTERED DESIGN |
| PROFESSIONAL IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE |
| FOR REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS |
| PREPARED BY OTHERS, INCLUDING PHASED AND DEFERRED |
| SUBMITTAL ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF |
| THE BUILDING. PRODUCTS SHALL BE REVIEWED AND APPROVED |
| IN WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL. |
| |
| 26H) ** COMMON COMMENT FOR ALL FLOORS (6-12) WHERE THE |
| ALLOWABLE COMMON PATH OF TRAVEL IS EXCEEDED. EXAMPLE: |
| ROOMS 604 & 605 FROM THE MOST REMOTE POINT IN THE SUITE |
| TO THE NEAREST VERTICAL EXIT IS OVER THE ALLOWABLE 75 |
| FT. TO ACHIEVE THE ALLOWABLE 75 FT. A RATED WALL IS |
| INSTALLED IN THE EXIT ACCESS CORRIDOR, ON THE DOOR |
| SCHEDULE THIS DOOR IS NOT FIRE RATED. PLEASE PROVIDE A |
| CODE SECTION WHERE THIS IS ALLOWED TO BE CONSIDERED |
| CODE COMPLIANT. 2014 FBC-B TABLE 1014.3. DEFINITION: |
| COMMON PATH OF EGRESS TRAVEL. THAT PORTION OF EXIT |
| ACCESS WHICH THE OCCUPANTS ARE REQUIRED TO TRAVERSE |
| BEFORE TWO SEPARATE AND DISTINCT PATHS OF EGRESS TRAVEL |
| TO TWO EXITS ARE AVAILABLE. PATHS THAT MERGE ARE COMMON |
| PATHS OF TRAVEL. COMMON PATHS OF EGRESS TRAVEL SHALL BE |
| INCLUDED WITHIN THE PERMITTED TRAVEL DISTANCE. |
| |
| 27) SHEET A1.18 & A7.09 & A7.10. THE 8TH, 10TH & 12TH |
| FLOORS. THIS COMMENT FOR THE ROOMS 818,819,1018, |
| 1019,1218 & 1219 ALL EXCEED THE ALLOWABLE 75 FT. |
| ALLOWABLE COMMON PATH OF TRAVEL OF 75 FT. 2014 FBC-B |
| TABLE 1014.3 |
| |
| 28) SHEET A2.08A THE INTERSTITIAL SPACE FLOOR PLAN. IN |
| BOTH VERTICAL EXIT STAIR TOWERS 1 & 2 THERE IS A NOTE |
| OF A DOOR LABELED S3 AND NOTE TO THE SIDE TO PROVIDE A |
| 3 FT. X 4 FT. ACCESS HATCH. THIS DOOR/ ACCESS HATCH IS |
| WITHIN THE VERTICAL EXIT AND LEADS TO THE INTERSTITIAL |
| SPACE BETWEEN FLOORS. PLEASE FIND ANOTHER WAY TO ACCESS |
| THE INTERSTITIAL SPACE BETWEEN FLOORS. CODE COMPLIANCE |
| FOR THE VERTICAL EXIT STAIRS CANNOT BE MET WITH THIS |
| OPENING WITHIN THE STAIRS. PLEASE SEE THE 2014 FBC-B |
| SECTION 1022.4 OPENINGS. |
| INTERIOR EXIT STAIRWAY AND RAMP OPENING PROTECTIVES |
| SHALL BE IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION |
| 716. OPENINGS IN INTERIOR EXIT STAIRWAYS AND RAMPS |
| OTHER THAN UNPROTECTED EXTERIOR OPENINGS SHALL BE |
| LIMITED TO THOSE NECESSARY FOR EXIT ACCESS TO THE |
| ENCLOSURE FROM NORMALLY OCCUPIED SPACES AND FOR EGRESS |
| FROM THE ENCLOSURE. |
| |
| 29) SHEET A2.09 & A7.41 13TH FLOOR ROOFTOP GARDEN: |
| 29A) THIS SHEET INDICATES A SECTION FOR RESTROOM 1321 & |
| 1322, PAGE A7.41 SECTION 04. PLEASE SEE ON THIS SHEET |
| THE DETAIL IS MISSING. 107.2.1.3. ADDITIONAL |
| INFORMATION IS REQUIRED. |
| |
| 29B) DOORS 1322, 1323,1324, 1325 & 1326 ARE MISSING |
| FROM THE DOOR SCHEDULE FOUND ON SHEET A8.02, CANNOT BE |
| CHECKED FOR SIZE, TYPE NOR FIRE RATING. 2014 FBC-B |
| 1008.1.1, TABLE 716.5. |
| |
| 29C) DOORS NOT NUMBERS, THE DOOR ALL THE WAY TO THE |
| LEFT OF THE PAGE SEPARATING AREAS 1313 & 1314 SWINGS |
| AGAINST THE DIRECTION OF EGRESS TRAVEL WHERE SERVING A |
| ROOM OR AREA CONTAINING AN OCCUPANT LOAD OF 50 OR MORE |
| PERSONS OR A GROUP H OCCUPANCY. FBC-B 1008.1.2. |
| 29D) BARS 1311 AND 1312 WILL NEED TO SHOW COMPLIANCE |
| WITH; 2014 FBC-ACCESS. CODE 902.3 HEIGHT. THE TOPS OF |
| DINING SURFACES SHALL BE 28 INCHES MINIMUM AND 34 |
| INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| 29E) THE AREAS ROOF LOUNGE AND LOBBY, 1313 & 1314 MAY |
| NEED TO COMPLY WITH ACCESS. CODE 902.3 IF THERE ARE |
| TABLES PRESENT. THIS PLAN DOES NOT SHOW A SEATING |
| ARRANGEMENT IN THE ROOF LOUNGE 1314. |
| |
| 29F) STAIRWELL # 1 SHOWS A LADDER TO GAIN ACCESS TO THE |
| ROOF TOP EQUIPMENT. PLEASE REVIEW : |
| 2014 FBC-B SECTION 1022.4 OPENINGS. INTERIOR EXIT |
| STAIRWAY AND RAMP OPENING PROTECTIVES SHALL BE IN |
| ACCORDANCE WITH THE REQUIREMENTS OF SECTION 716. |
| OPENINGS IN INTERIOR EXIT STAIRWAYS AND RAMPS OTHER |
| THAN UNPROTECTED EXTERIOR OPENINGS SHALL BE LIMITED TO |
| THOSE NECESSARY FOR EXIT ACCESS TO THE ENCLOSURE FROM |
| NORMALLY OCCUPIED SPACES AND FOR EGRESS FROM THE |
| ENCLOSURE. |
| FBC-B 1022.5 PENETRATIONS. PENETRATIONS INTO AND |
| OPENINGS THROUGH INTERIOR EXIT STAIRWAYS AND RAMPS ARE |
| PROHIBITED EXCEPT FOR REQUIRED EXIT DOORS, EQUIPMENT |
| AND DUCTWORK NECESSARY FOR INDEPENDENT VENTILATION OR |
| PRESSURIZATION, SPRINKLER PIPING, STANDPIPES, |
| ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION |
| SYSTEMS AND ELECTRICAL RACEWAY SERVING THE INTERIOR |
| EXIT STAIRWAY AND RAMP AND TERMINATING AT A STEEL BOX |
| NOT EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH |
| PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE WITH |
| SECTION 714. |
| |
| 30) POOL AND JACUZZI ARE NOT PART OF THIS PERMIT, WILL |
| REQUIRE A SEPARATE PERMIT, REVIEW AND ASSOCIATED FEES. |
| |
| 31) FENCING AND GATES AROUND THE POOL WILL REQUIRE A |
| SEPARATE PERMIT, REVIEW AND ASSOCIATED FEES. |
| |
| 32) SHEET A2.10 SHOWS AS HIDDEN LINES VARIOUS ROOF TOP |
| EQUIPMENT. SHEET M2.10 SHOWS GENERIC ROOF TOP EQUIPMENT |
| TIE DOWNS. DETAILS WILL NEED TO BE SPECIFIC FOR EACH |
| TYPE AND SIZE OF ROOF TOP EQUIPMENT. FOR ALL ROOF TOP |
| EQUIPMENT, CURBS OR A/C STANDS, DETAILED ATTACHMENT TO |
| THE ROOF FRAMING & DECK AS WELL AS FROM THE CURB OR |
| ROOF STAND TO THE EQUIPMENT ABOVE. |
| |
| 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL |
| MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY |
| METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT |
| EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY |
| AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. |
| EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE |
| OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| LOADS? |
| 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL |
| EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO |
| WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND |
| PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 33) SHEET A2.10 PLEASE SHOW COMPLIANCE WITH: FBC-B 2014 |
| 1509.6 MECHANICAL EQUIPMENT SCREENS. |
| MECHANICAL EQUIPMENT SCREENS SHALL BE CONSTRUCTED OF |
| THE MATERIALS SPECIFIED FOR THE EXTERIOR WALLS IN |
| ACCORDANCE WITH THE TYPE OF CONSTRUCTION OF THE |
| BUILDING. WHERE THE FIRE SEPARATION DISTANCE IS GREATER |
| THAN 5 FEET (1524 MM), MECHANICAL EQUIPMENT SCREENS |
| SHALL NOT BE REQUIRED TO COMPLY WITH THE |
| FIRE-RESISTANCE RATING REQUIREMENTS. |
| |
| 34) A.600 SERIES DRAWINGS FOR STAIRWELL 1, 2 & 3. |
| PLEASE PROVIDE COMPLIANCE WITH THE 2014 FBC-ACCESS. |
| CODE SECTION 307.4 AND VIEW FIGURE 307.4 FOR VERTICAL |
| CLEARANCES. |
| |
| 35) BUILDING PROVISO: DEFERRED SUBMITTAL. SHEETS A6.02 |
| & A6.03 STAIR GUARDRAIL/ HANDRAILS . ADMINISTRATION |
| 107.3.4 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE. THE |
| REGISTERED DESIGN |
| PROFESSIONAL IN RESPONSIBLE CHARGE SHALL BE RESPONSIBLE |
| FOR REVIEWING AND COORDINATING SUBMITTAL DOCUMENTS |
| PREPARED BY OTHERS, INCLUDING PHASED AND DEFERRED |
| SUBMITTAL ITEMS, FOR COMPATIBILITY WITH THE DESIGN OF |
| THE BUILDING. |
| FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL |
| FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE |
| ENGINEER OF RECORD FOR REVIEW. |
| 36) SHEET A4.01 SHOWS A NORTH ELEVATION WITH A NOTE FOR |
| CONCRETE CANOPY WITH WOOD COMPOSITE UNDERNEATH FINISH. |
| THE STRUCTURAL SHEET S5.21 DETAIL PROVIDES STRUCTURAL |
| DETAILS AS TO THE THICKNESS OF THIS CANOPY, AND THE |
| PLACEMENT OF REINFORCEMENT. THERE ARE 2 AREAS OF |
| CONCERN: |
| |
| 36A) THE NOTE FOUND ON A4.01 INDICATES THE UNDERNEATH |
| SIDE OF THE CANOPY IS TO BE FINISHED WITH A WOOD |
| COMPOSITE MATERIAL. WE FIND THIS SAME NOTE AT AROUND |
| THE 155 FT. & 173.5 FT. ELEVATION. PLEASE PROVIDE |
| PRODUCT LITERATURE ON THIS PRODUCT TO SEE HOW THIS |
| MATERIAL WAS TESTED, TO WHAT STANDARD? DOES IT MEET THE |
| DEFINITION OF A COMPOSITE MATERIAL. |
| |
| DEFINITION OF COMPOSITE MATERIAL: 703.5.2 COMPOSITE |
| MATERIALS. MATERIALS HAVING A STRUCTURAL BASE OF |
| NONCOMBUSTIBLE MATERIAL AS DETERMINED IN ACCORDANCE |
| WITH SECTION 703.5.1 WITH A SURFACING NOT MORE THAN |
| 0.125 INCH (3.18 MM) THICK THAT HAS A FLAME SPREAD |
| INDEX NOT GREATER THAN 50 WHEN TESTED IN ACCORDANCE |
| WITH ASTM E 84 OR UL 723 SHALL BE ACCEPTABLE AS |
| NONCOMBUSTIBLE MATERIALS. |
| |
| 2014 FBC-B 1406.2.1 TYPE I, II, III AND IV |
| CONSTRUCTION. ON BUILDINGS OF TYPE I, II, III AND IV |
| CONSTRUCTION, EXTERIOR WALL COVERINGS SHALL BE |
| PERMITTED TO BE CONSTRUCTED OF COMBUSTIBLE MATERIALS, |
| COMPLYING WITH THE FOLLOWING LIMITATIONS: |
| 1. COMBUSTIBLE EXTERIOR WALL COVERINGS SHALL NOT EXCEED |
| 10 PERCENT OF AN EXTERIOR WALL SURFACE AREA WHERE THE |
| FIRE SEPARATION DISTANCE IS 5 FEET (1524 MM) OR LESS. |
| 2. COMBUSTIBLE EXTERIOR WALL COVERINGS SHALL BE LIMITED |
| TO 40 FEET (12 192 MM) IN HEIGHT ABOVE GRADE PLANE. |
| 3. COMBUSTIBLE EXTERIOR WALL COVERINGS CONSTRUCTED OF |
| FIRE-RETARDANT-TREATED WOOD COMPLYING WITH SECTION |
| 2303.2 FOR EXTERIOR INSTALLATION SHALL NOT BE LIMITED |
| IN WALL SURFACE AREA WHERE THE FIRE SEPARATION DISTANCE |
| IS 5 FEET (1524 MM) OR LESS AND SHALL BE PERMITTED UP |
| TO 60 FEET (18 288 MM) IN HEIGHT ABOVE GRADE PLANE |
| REGARDLESS OF THE FIRE SEPARATION DISTANCE. |
| 4. WOOD VENEERS SHALL COMPLY WITH SECTION 1405.5. |
| 1406.2.1.1.2 FIRE SEPARATION GREATER THAN 5 FEET. FOR |
| FIRE SEPARATION DISTANCES GREATER THAN 5 FEET (1524 |
| MM), ANY EXTERIOR WALL COVERING SHALL BE PERMITTED THAT |
| HAS BEEN EXPOSED TO A REDUCED LEVEL OF INCIDENT RADIANT |
| HEAT FLUX IN ACCORDANCE WITH THE NFPA 268 TEST METHOD |
| WITHOUT EXHIBITING SUSTAINED FLAMING. THE MINIMUM FIRE |
| SEPARATION DISTANCE REQUIRED FOR THE EXTERIOR WALL |
| COVERING SHALL BE DETERMINED FROM TABLE 1406.2.1.1.2 |
| BASED ON THE MAXIMUM TOLERABLE LEVEL OF INCIDENT |
| RADIANT HEAT FLUX THAT DOES NOT CAUSE SUSTAINED FLAMING |
| OF THE EXTERIOR WALL COVERING. |
| |
| 36B) THE WOOD COMPOSITE MATERIAL, PLEASE PROVIDE HOW |
| THIS MATERIAL WILL BE ATTACHED TO THE SUB-STRUCTURE, |
| ADHERED, PINNED? 107.2.1.3 ADDITIONAL INFORMATION |
| REQUIRED. |
| |
| 36C) ON THE TOP OF THE 8 FT. CONCRETE CANOPY WHAT |
| PRODUCT WILL BE USED TO KEEP MOISTURE FROM SEEPING INTO |
| THE CONCRETE SLAB AND REINFORCEMENT? |
| |
| 37) SHEET A4.01 THE NORTH WALL ELEVATION ON THE GARAGE |
| LEVELS 3-5 THE PLANS SHOW PERFORATED ALUMINUM PANEL |
| SYSTEM. PLEASE PROVIDE PRODUCT LITERATURE, AND |
| ENGINEERING ANALYSIS OF THE SYSTEM, WITH THE WIND |
| DESIGN CRITERIA AND ANCHORING SYSTEMS REVIEWED BY THE |
| ENGINEER OF RECORD. FL 61G-15-30.006 (3) THE DELEGATED |
| ENGINEER SHALL FORWARD THE DELEGATED ENGINEERING |
| DOCUMENTS TO THE ENGINEER OF RECORD FOR REVIEW. 2014 |
| FBC-B 1503.1 ROOF DECKS SHALL BE COVERED WITH APPROVED |
| ROOF COVERINGS SECURED TO THE BUILDING OR STRUCTURE IN |
| ACCORDANCE WITH THE PROVISIONS OF THIS CHAPTER. ROOF |
| COVERINGS SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE |
| WITH THIS CODE AND THE APPROVED MANUFACTURER?S |
| INSTRUCTIONS SUCH THAT THE ROOF COVERING SHALL SERVE TO |
| PROTECT THE BUILDING OR STRUCTURE. |
| 38) SHEET A1.11 AND A2.01 BOTH SHOW THE 1ST FLOOR, BUT |
| THERE ARE NO DIMENSIONS FOR SIZING OF THE FIRE COMMAND |
| CENTER. THE FIRE COMMAND ROOM IS FOUND ON THIS FLOOR. |
| FBC-B403.4.6 FIRE COMMAND. A FIRE COMMAND CENTER |
| COMPLYING WITH SECTION 911 SHALL BE PROVIDED IN A |
| LOCATION APPROVED BY THE FIRE DEPARTMENT. |
| 38A) PLEASE SHOW COMPLIANCE WITH FBC-B 911.1.4. LAYOUT |
| APPROVAL. A LAYOUT OF THE FIRE COMMAND CENTER AND ALL |
| FEATURES REQUIRED BY THIS SECTION TO BE CONTAINED |
| THEREIN SHALL BE SUBMITTED FOR APPROVAL PRIOR TO |
| INSTALLATION. |
| 38B) 911.1.5 REQUIRED FEATURES. |
| THE FIRE COMMAND CENTER SHALL COMPLY WITH NFPA 72 AND |
| SHALL CONTAIN THE FOLLOWING FEATURES: |
| |
| 1. THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM |
| CONTROL UNIT. |
| |
| 2. THE FIRE DEPARTMENT COMMUNICATIONS SYSTEM. |
| |
| 3. FIRE DETECTION AND ALARM SYSTEM ANNUNCIATOR. |
| |
| 4. ANNUNCIATOR UNIT VISUALLY INDICATING THE LOCATION OF |
| THE ELEVATORS AND WHETHER THEY ARE OPERATIONAL. |
| |
| 5. STATUS INDICATORS AND CONTROLS FOR AIR DISTRIBUTION |
| SYSTEMS. |
| |
| 6. THE FIRE-FIGHTER?S CONTROL PANEL REQUIRED BY SECTION |
| 909.16 FOR SMOKE CONTROL SYSTEMS INSTALLED IN THE |
| BUILDING. |
| |
| 7. CONTROLS FOR UNLOCKING STAIRWAY DOORS |
| SIMULTANEOUSLY. |
| |
| 8. SPRINKLER VALVE AND WATERFLOW DETECTOR DISPLAY |
| PANELS. |
| |
| 9. EMERGENCY AND STANDBY POWER STATUS INDICATORS. |
| |
| 10. A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED |
| ACCESS TO THE PUBLIC TELEPHONE SYSTEM. |
| |
| 11. FIRE PUMP STATUS INDICATORS. |
| |
| 12. SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL |
| FLOOR PLAN AND DETAILING THE BUILDING CORE, MEANS OF |
| EGRESS, FIRE PROTECTION SYSTEMS, FIRE-FIGHTING |
| EQUIPMENT AND FIRE DEPARTMENT ACCESS AND THE LOCATION |
| OF FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE |
| BARRIERS AND SMOKE PARTITIONS. |
| |
| 13. AN APPROVED BUILDING INFORMATION CARD THAT |
| CONTAINS, BUT IS NOT LIMITED TO, THE FOLLOWING |
| INFORMATION: |
| |
| 13.1. GENERAL BUILDING INFORMATION THAT INCLUDES: |
| PROPERTY NAME, ADDRESS, THE NUMBER OF FLOORS IN THE |
| BUILDING (ABOVE AND BELOW GRADE), USE AND OCCUPANCY |
| CLASSIFICATION (FOR MIXED USES, IDENTIFY THE DIFFERENT |
| TYPES OF OCCUPANCIES ON EACH FLOOR), ESTIMATED BUILDING |
| POPULATION (I.E., DAY, NIGHT, WEEKEND); |
| |
| 13.2. BUILDING EMERGENCY CONTACT INFORMATION THAT |
| INCLUDES: A LIST OF THE BUILDING?S EMERGENCY CONTACTS |
| (E.G., BUILDING MANAGER, BUILDING ENGINEER, ETC.) AND |
| THEIR RESPECTIVE WORK PHONE NUMBER, CELL PHONE NUMBER, |
| EMAIL ADDRESS; |
| |
| 13.3. BUILDING CONSTRUCTION INFORMATION THAT INCLUDES: |
| THE TYPE OF BUILDING CONSTRUCTION (E.G., FLOORS, WALLS, |
| COLUMNS, AND ROOF ASSEMBLY); |
| |
| 13.4. EXIT STAIR INFORMATION THAT INCLUDES: NUMBER OF |
| EXIT STAIRS IN BUILDING, EACH EXIT STAIR DESIGNATION |
| AND FLOORS SERVED, LOCATION WHERE EACH EXIT STAIR |
| DISCHARGES, EXIT STAIRS THAT ARE PRESSURIZED, EXIT |
| STAIRS PROVIDED WITH EMERGENCY LIGHTING, EACH EXIT |
| STAIR THAT ALLOWS REENTRY, EXIT STAIRS PROVIDING ROOF |
| ACCESS; ELEVATOR INFORMATION THAT INCLUDES: NUMBER OF |
| ELEVATOR BANKS, ELEVATOR BANK DESIGNATION, ELEVATOR CAR |
| NUMBERS AND RESPECTIVE FLOORS THAT THEY SERVE, LOCATION |
| OF ELEVATOR MACHINE ROOMS, LOCATION OF SKY LOBBY, |
| LOCATION OF FREIGHT ELEVATOR BANKS; |
| |
| 13.5. BUILDING SERVICES AND SYSTEM INFORMATION THAT |
| INCLUDES: LOCATION OF MECHANICAL ROOMS, LOCATION OF |
| BUILDING MANAGEMENT SYSTEM, LOCATION AND CAPACITY OF |
| ALL FUEL OIL TANKS, LOCATION OF EMERGENCY GENERATOR, |
| LOCATION OF NATURAL GAS SERVICE; |
| |
| 13.6. FIRE PROTECTION SYSTEM INFORMATION THAT INCLUDES: |
| LOCATIONS OF STANDPIPES, LOCATION OF FIRE PUMP ROOM, |
| LOCATION OF FIRE DEPARTMENT CONNECTIONS, FLOORS |
| PROTECTED BY AUTOMATIC SPRINKLERS, LOCATION OF |
| DIFFERENT TYPES OF SPRINKLER SYSTEMS INSTALLED (E.G., |
| DRY, WET, PRE-ACTION, ETC.); AND |
| |
| 13.7 HAZARDOUS MATERIAL INFORMATION THAT INCLUDES: |
| LOCATION OF HAZARDOUS MATERIAL, QUANTITY OF HAZARDOUS |
| MATERIAL. |
| |
| 14. WORK TABLE. |
| |
| 15. GENERATOR SUPERVISION DEVICES, MANUAL START AND |
| TRANSFER FEATURES. |
| |
| 16. PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED |
| BY OTHER SECTIONS OF THIS CODE. |
| |
| 17. ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME |
| A17.1. |
| |
| 18. ELEVATOR EMERGENCY OR STANDBY POWER SELECTOR |
| SWITCH(ES), WHERE EMERGENCY OR STANDBY POWER IS |
| PROVIDED. |
| |
| 39) 2014 FBC-B 403.5.3 STAIRWAY DOOR OPERATION. |
| STAIRWAY DOORS OTHER THAN THE EXIT DISCHARGE DOORS |
| SHALL BE PERMITTED TO BE LOCKED FROM THE STAIRWAY SIDE. |
| STAIRWAY DOORS THAT ARE LOCKED FROM THE STAIRWAY SIDE |
| SHALL BE CAPABLE OF BEING UNLOCKED SIMULTANEOUSLY |
| WITHOUT UNLATCHING UPON A SIGNAL FROM THE FIRE COMMAND |
| CENTER. |
| |
| 40) PLEASE SUBMIT DOCUMENTATION FOR THE FOLLOWING: |
| FBC-B 403.4.7 SMOKE REMOVAL./ 909.4 ANALYSIS. |
| A RATIONAL ANALYSIS SUPPORTING THE TYPES OF SMOKE |
| CONTROL SYSTEMS TO BE EMPLOYED, THEIR METHODS OF |
| OPERATION, THE SYSTEMS SUPPORTING THEM AND THE METHODS |
| OF CONSTRUCTION TO BE UTILIZED SHALL ACCOMPANY THE |
| SUBMITTED CONSTRUCTION DOCUMENTS AND SHALL INCLUDE, BUT |
| NOT BE LIMITED TO, THE ITEMS INDICATED IN SECTIONS |
| 909.4.1 THROUGH 909.4.6. |
| |
| 41) PLEASE SHOW HOW COMPLIANCE WITH FBC-B 403.5.5 |
| LUMINOUS EGRESS PATH MARKINGS. |
| LUMINOUS EGRESS PATH MARKINGS SHALL BE PROVIDED IN |
| ACCORDANCE WITH SECTION 1024. FBC-B 1024.1 APPROVED |
| LUMINOUS EGRESS PATH MARKINGS DELINEATING THE EXIT PATH |
| SHALL BE PROVIDED IN HIGH-RISE BUILDINGS OF GROUP A, B, |
| E, I, M, AND R-1 OCCUPANCIES IN ACCORDANCE WITH |
| SECTIONS 1024.1 THROUGH 1024.5. |
| |
| 42) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| 43) FOR THE RESUBMISSION OF PLANS, PLEASE BREAK THE |
| PLAN SETS DOWN TO SMALLER MANAGEABLE ROLLS. BUILDING |
| AND ID DRAWINGS TOGETHER, STRUCTURAL BY ITSELF AND MEP |
| TOGETHER. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION |
| DEVELOPMENT SERVICES DEPARTMENT |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |