2017-01-27 11:02:053RD REVIEW FBC-2014 MECHANICAL
 PERMIT #16061439
 1/27/17
  
 1) THE REVISED PLANS AND ENERGYGAUGE COMPLIANCE FORM
 EACH REQUIRE DIGITAL SIGNATURES.
  
 2) REVISE SHEETS M4.02 & M4.07 IN ACCORDANCE WITH THE
 FAN CHANGES AND PRESSURIZATION METHOD FOR STAIRWELL #2.
  
 3) PROVIDE A SUBMITTAL FOR THE NEW PRESSURIZATION FANS
 SPF-1-1 & SPF 6-1.
  
 4) THE FOLLOWING LIST OF REVISED APARTMENT PLANS APPEAR
 TO SHOW DRYER EXHAUST DUCTS RUNNING THROUGH RETURN AIR
 PLENUMS WHICH IS PROHIBITED PER SECTION 504.4.: SHEETS
 M3-1-1, 3-2-1, 3-3-1, 3-10-1, 3-14-1, & 3-15-1.
  
 5) THE SUBMITTED REVISION NARRATIVE DID NOT COMPLETELY
 LIST ALL THE CHANGES SHOWN IN THE REVISED PLANS. PLEASE
 PROVIDE A COMPLETE NARRATIVE WITH THE RESUBMITTED
 PLANS.
  