2017-01-27 11:02:05 | 3RD REVIEW FBC-2014 MECHANICAL | | PERMIT #16061439 | | 1/27/17 | | | | 1) THE REVISED PLANS AND ENERGYGAUGE COMPLIANCE FORM | | EACH REQUIRE DIGITAL SIGNATURES. | | | | 2) REVISE SHEETS M4.02 & M4.07 IN ACCORDANCE WITH THE | | FAN CHANGES AND PRESSURIZATION METHOD FOR STAIRWELL #2. | | | | 3) PROVIDE A SUBMITTAL FOR THE NEW PRESSURIZATION FANS | | SPF-1-1 & SPF 6-1. | | | | 4) THE FOLLOWING LIST OF REVISED APARTMENT PLANS APPEAR | | TO SHOW DRYER EXHAUST DUCTS RUNNING THROUGH RETURN AIR | | PLENUMS WHICH IS PROHIBITED PER SECTION 504.4.: SHEETS | | M3-1-1, 3-2-1, 3-3-1, 3-10-1, 3-14-1, & 3-15-1. | | | | 5) THE SUBMITTED REVISION NARRATIVE DID NOT COMPLETELY | | LIST ALL THE CHANGES SHOWN IN THE REVISED PLANS. PLEASE | | PROVIDE A COMPLETE NARRATIVE WITH THE RESUBMITTED | | PLANS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|