Plan Review Notes
Plan Review Notes For Permit 16061439
Permit Number 16061439
Review Stop M
Sequence Number 2
Notes
Date Text
2016-10-26 14:28:502ND REVIEW FBC-2010 MECHANICAL
 PERMIT #16061439
 10/25/16
  
 1) SHEET M-2-6-1: THE EXHAUST FROM EF-2 SHALL DISCHARGE
 TO THE OUTDOORS PER SECTION 501.2 FBC-10 MECHANICAL
 (CORRECTION OF COMMENT #2 FROM THE 1ST REVIEW).
  
 2) M-2-6-1: PLEASE PROVIDE DOCUMENTATION FROM CARRIER
 INDICATING THE EXTERIOR CONDENSER UNITS MAY BE
 INSTALLED INDOORS AND ARE COMPLIANT WITH MANUFACTURER'S
 SPECIFICATIONS.
  
 3) A2.6.2: PLEASE TAG THE WALLS ENCLOSING THE NEW MECH
 RM AND INCLUDE THE WALLS IN THE LEGEND. REFER TO
 SECTION 304.6 EXCEPTION AND VERIFY COMPLIANCE FOR
 VEHICULAR IMPACT PROTECTION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  