Plan Review Notes For Permit 16061439 |
Permit Number |
16061439 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2016-10-26 14:28:50 | 2ND REVIEW FBC-2010 MECHANICAL | | PERMIT #16061439 | | 10/25/16 | | | | 1) SHEET M-2-6-1: THE EXHAUST FROM EF-2 SHALL DISCHARGE | | TO THE OUTDOORS PER SECTION 501.2 FBC-10 MECHANICAL | | (CORRECTION OF COMMENT #2 FROM THE 1ST REVIEW). | | | | 2) M-2-6-1: PLEASE PROVIDE DOCUMENTATION FROM CARRIER | | INDICATING THE EXTERIOR CONDENSER UNITS MAY BE | | INSTALLED INDOORS AND ARE COMPLIANT WITH MANUFACTURER'S | | SPECIFICATIONS. | | | | 3) A2.6.2: PLEASE TAG THE WALLS ENCLOSING THE NEW MECH | | RM AND INCLUDE THE WALLS IN THE LEGEND. REFER TO | | SECTION 304.6 EXCEPTION AND VERIFY COMPLIANCE FOR | | VEHICULAR IMPACT PROTECTION. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|