Plan Review Notes
Plan Review Notes For Permit 16061439
Permit Number 16061439
Review Stop M
Sequence Number 1
Notes
Date Text
2016-07-26 08:48:331ST REVIEW MECHANICAL
 REVISION #16061439
 MASTER #15031312
 7/16/16
  
 1) SHEETS M2-3-1, 4-1, 5-1, 6-1: INDICATE THE TYPE OF
 DUCTWORK TO BE INSTALLED IN THE GARAGE AND THE
 CLEARANCE HEIGHTS FROM FINISHED FLOOR TO BOTTOM OF THE
 DUCTS. REFER TO SMACNA DUCT CONSTRUCTION STANDARDS-
 2005, AND SECTION 304.6 FBC-14 MECHANICAL.
  
 2) M2-6-1: THE EXHAUST FROM EF-2 SHALL DISCHARGE TO THE
 OUTDOORS- SEE SECTION 501.3 AND REVISE THE PLAN.
  
 3 ) M2-6-1: PROVIDE AN EXHAUST VENTILATION CALCULATION
 FOR GEF-6-2, PROVIDE A SEQUENCE OF OPERATION FOR THE
 FAN, AND SHOW HOW MAKEUP AIR IS BEING PROVIDED FOR THE
 EXHAUST.
  
 4) M2-6-1: REFER TO SECTION 1104.2 AND INDICATE THE
 TYPE AND AMOUNT OF REFRIGERANT IN THE SYSTEMS CONTAINED
 IN THE NEW MECHANICAL ROOM. PLEASE NOTE A FIRE-RATED
 MACHINERY ROOM MAY BE REQUIRED, AND ADDITIONAL
 REQUIREMENTS PER SECTIONS 1104 AND 1105 MAY BE
 APPLICABLE TO THE INSTALLATION. SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE CONDENSERS- THE UNITS SHALL BE
 INSTALLED IN ACCORDANCE WITH THEIR LISTING OR PER
 MANUFACTURER'S INSTRUCTIONS.
  
 5) M2-6-1 SHOWS THE 8 CONDENSER UNITS TO BE RELOCATED
 ARE CU TYPES 3, 4A, AND 5A, HOWEVER SHEET M2.91 SHOWS
 THE UNIT TYPES RELOCATED WERE CU'S 2 & 3.
  
 6) M2-1-1 & M4.00: THE TRASH ROOM AC HAS BEEN CHANGED
 TO A 1.5 TON SYSTEM, HOWEVER THE AC AND ENERGY
 CALCULATIONS INDICATE A 5TON SYSTEM.
  
 7) M3.1.1: THE 32X6 AND 16X12 RETURN AIR TRANSFERS FROM
 BEDROOM 301.04 ARE UNDERSIZED PER SECTION 601.5
 EXCEPTIONS 2 & 3. A) THE 36X12 TRANSFER AT THE MAIN AC
 PLENUM IS ALSO UNDERSIZED PER 601.5 EXCEPTION 2.
  
 8) M3.2.1: INDICATE HOW THE SUPPLY AIR FOR THE AC-3
 SYSTEMS IS BEING RETURNED TO THE UNITS IN THE CLOSETS-
 SEE SECTION 602.1 FOR PLENUM REQUIREMENTS AND
 LIMITATIONS.
  
 9) M3.3.1: SEE COMMENT #8 ABOVE AS IT PERTAINS TO
 AC-4A.
  
 10) ADVISORY: PLEASE REVIEW THE RETURN AIR SYSTEMS FOR
 THE APARTMENTS SHOWN ON MASTER PLAN SHEETS M3.10.1,
 M3.14.01, M.3.15.1 AND M3.16.1- PERMIT #15031312. IT
 APPEARS THAT SOME OF THE RETURN AIR AND TRANSFER GRILLS
 SHOWN ARE UNDERSIZED PER SECTION 601.5. PLEASE REVIEW
 AND REVISE
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  