2016-07-26 08:48:33 | 1ST REVIEW MECHANICAL |
| REVISION #16061439 |
| MASTER #15031312 |
| 7/16/16 |
| |
| 1) SHEETS M2-3-1, 4-1, 5-1, 6-1: INDICATE THE TYPE OF |
| DUCTWORK TO BE INSTALLED IN THE GARAGE AND THE |
| CLEARANCE HEIGHTS FROM FINISHED FLOOR TO BOTTOM OF THE |
| DUCTS. REFER TO SMACNA DUCT CONSTRUCTION STANDARDS- |
| 2005, AND SECTION 304.6 FBC-14 MECHANICAL. |
| |
| 2) M2-6-1: THE EXHAUST FROM EF-2 SHALL DISCHARGE TO THE |
| OUTDOORS- SEE SECTION 501.3 AND REVISE THE PLAN. |
| |
| 3 ) M2-6-1: PROVIDE AN EXHAUST VENTILATION CALCULATION |
| FOR GEF-6-2, PROVIDE A SEQUENCE OF OPERATION FOR THE |
| FAN, AND SHOW HOW MAKEUP AIR IS BEING PROVIDED FOR THE |
| EXHAUST. |
| |
| 4) M2-6-1: REFER TO SECTION 1104.2 AND INDICATE THE |
| TYPE AND AMOUNT OF REFRIGERANT IN THE SYSTEMS CONTAINED |
| IN THE NEW MECHANICAL ROOM. PLEASE NOTE A FIRE-RATED |
| MACHINERY ROOM MAY BE REQUIRED, AND ADDITIONAL |
| REQUIREMENTS PER SECTIONS 1104 AND 1105 MAY BE |
| APPLICABLE TO THE INSTALLATION. SUBMIT MANUFACTURER'S |
| SPECIFICATIONS FOR THE CONDENSERS- THE UNITS SHALL BE |
| INSTALLED IN ACCORDANCE WITH THEIR LISTING OR PER |
| MANUFACTURER'S INSTRUCTIONS. |
| |
| 5) M2-6-1 SHOWS THE 8 CONDENSER UNITS TO BE RELOCATED |
| ARE CU TYPES 3, 4A, AND 5A, HOWEVER SHEET M2.91 SHOWS |
| THE UNIT TYPES RELOCATED WERE CU'S 2 & 3. |
| |
| 6) M2-1-1 & M4.00: THE TRASH ROOM AC HAS BEEN CHANGED |
| TO A 1.5 TON SYSTEM, HOWEVER THE AC AND ENERGY |
| CALCULATIONS INDICATE A 5TON SYSTEM. |
| |
| 7) M3.1.1: THE 32X6 AND 16X12 RETURN AIR TRANSFERS FROM |
| BEDROOM 301.04 ARE UNDERSIZED PER SECTION 601.5 |
| EXCEPTIONS 2 & 3. A) THE 36X12 TRANSFER AT THE MAIN AC |
| PLENUM IS ALSO UNDERSIZED PER 601.5 EXCEPTION 2. |
| |
| 8) M3.2.1: INDICATE HOW THE SUPPLY AIR FOR THE AC-3 |
| SYSTEMS IS BEING RETURNED TO THE UNITS IN THE CLOSETS- |
| SEE SECTION 602.1 FOR PLENUM REQUIREMENTS AND |
| LIMITATIONS. |
| |
| 9) M3.3.1: SEE COMMENT #8 ABOVE AS IT PERTAINS TO |
| AC-4A. |
| |
| 10) ADVISORY: PLEASE REVIEW THE RETURN AIR SYSTEMS FOR |
| THE APARTMENTS SHOWN ON MASTER PLAN SHEETS M3.10.1, |
| M3.14.01, M.3.15.1 AND M3.16.1- PERMIT #15031312. IT |
| APPEARS THAT SOME OF THE RETURN AIR AND TRANSFER GRILLS |
| SHOWN ARE UNDERSIZED PER SECTION 601.5. PLEASE REVIEW |
| AND REVISE |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |