2016-07-01 14:42:59 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC 2010 |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) THE APPROVED PLANS WERE SIGNED AND SEALED BY A |
| FLORIDA LICENSED ARCHITECT (MIGUEL F. SANCHEZ), WHO IS |
| THE DESIGNER OF RECORD. THE REVISED PLANS NEED TO BE |
| SIGNED AND SEALED BY THE ARCHITECT THAT IS THE DESIGNER |
| OF RECORD. FS 481 THE OTHER OPTION IS TO HAVE THE NEW |
| PLANS REVIEWED AND APPROVED BY THE ARCHITECT AND |
| STAMPED WITH HIS SHOP DRAWING REVIEW STAMP. |
| |
| 2) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. |
| ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| THE PERSON RESPONSIBLE FOR THE DESIGN. |
| |
| 3) THE PLANS THAT WERE SUBMITTED ARE MISSING |
| INFORMATION, SUCH AS THE CONDENSER PAD AND ANCHORING |
| INFORMATION. THE INFORMATION ON THE BATHROOM EXHAUST |
| FANS MODEL AND CFMS IS MISSING. FBC 107.2.1, |
| FBCR-M1301.1, FBCR-M1305.1.4.1 |
| |
| 4) THE TRANSFER DUCT AT THE MASTER BEDROOM SUITE IS |
| REQUIRED TO BE 10" AND THE PLANS HAVE 9". ALL SUPPLY |
| AIR INTO THE MASTER SUITE INCLUDING THE MASTER BATHROOM |
| IS REQUIRED TO BE CONSIDERED FOR BALANCED RETURN AIR. |
| FBCR-M1602.04 |
| |
| 5) SOME OF THE SUPPLY DROPS DO NOT HAVE THE CFMS |
| SPECIFIED. FBC 107.2.1 |
| |
| 6) IT IS NOT CLEAR ON THE DRAWINGS HOW THE SUPPLY AIR |
| TO THE FIRST FLOOR IS BEING ROUTED. THERE APPEARS TO BE |
| A 16" X 10 " DISTRIBUTION BOX OFF THE AIR HANDLER WITH |
| A 14" DIAMETER FLEX DUCT DOWN TO THE FIRST FLOOR. THE |
| FIRST FLOOR PLANS DO NOT SHOW THE 14" DIA. SUPPLY FROM |
| THE SECOND FLOOR AND THERE ARE TWO DISTRIBUTION BOXES |
| THAT ARE NOT CONNECTED TO EACH OTHER SHOWN. THE |
| DUCTWORK HAS A DARK SHADING ON THEM THAT MAKES IT |
| ILLEGIBLE. FBC 107.2.1 |