Plan Review Notes For Permit 16061385 |
Permit Number |
16061385 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-07-02 08:48:27 | 1ST REVIEW | | | | | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER LL | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES | | BUILDING DIVISION | | 561-805-6711 | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | 1. PROVIDE DIMENSION OF DRINKING WATER SPOUT ON | | CLASSROOM SINK FROM FRONT EDGE TO SPOUT SHALL COMPLY | | WITH FBC AC 602.2 EXCEPTION: A PARALLEL APPROACH | | COMPLYING WITH 305 SHALL BE PERMITTED AT UNITS FOR | | CHILDREN?S USE WHERE THE SPOUT IS 30 INCHES (760 MM) | | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND AND IS 31/2 | | INCHES (90 MM) MAXIMUM FROM THE FRONT EDGE OF THE UNIT, | | INCLUDING BUMPERS. | | | | 2. PROVIDE DETAIL FOR HANGING WATER HEATER IT WILL | | WEIGH ABOUT 700LB. PER WPB AMEND. TO FBC 107.2.1 | | | | COMPLY WITH PROVISO FROM ORIGINAL PLAN: | | | | 4 OF THE 9 DRINKING FOUNTAINS SHALL COMPLY WITH FBC | | ACC. SEC. 602.7 DRINKING FOUNTAINS FOR STANDING | | PERSONS. | | SPOUT OUTLETS OF DRINKING FOUNTAINS FOR STANDING | | PERSONS SHALL BE 38 INCHES (965 MM) MINIMUM AND 43 | | INCHES (1090 MM) MAXIMUM ABOVE THE FINISH FLOOR OR | | GROUND. | | TO MEET THE REQUIREMENTS OF FBC ACC. SEC. | | 211.3 MORE THAN MINIMUM NUMBER. | | WHERE MORE THAN THE MINIMUM NUMBER OF DRINKING | | FOUNTAINS SPECIFIED IN 211.2 ARE PROVIDED, 50 PERCENT | | OF THE TOTAL NUMBER OF DRINKING FOUNTAINS PROVIDED | | SHALL COMPLY WITH 602.1 THROUGH 602.6, AND 50 PERCENT | | OF THE TOTAL NUMBER OF DRINKING FOUNTAINS PROVIDED | | SHALL COMPLY WITH 602.7. |
|