Plan Review Notes
Plan Review Notes For Permit 16061385
Permit Number 16061385
Review Stop P
Sequence Number 1
Notes
Date Text
2016-07-02 08:48:271ST REVIEW
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
 PLUMBING COMMENTS:
  
 1. PROVIDE DIMENSION OF DRINKING WATER SPOUT ON
 CLASSROOM SINK FROM FRONT EDGE TO SPOUT SHALL COMPLY
 WITH FBC AC 602.2 EXCEPTION: A PARALLEL APPROACH
 COMPLYING WITH 305 SHALL BE PERMITTED AT UNITS FOR
 CHILDREN?S USE WHERE THE SPOUT IS 30 INCHES (760 MM)
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND AND IS 31/2
 INCHES (90 MM) MAXIMUM FROM THE FRONT EDGE OF THE UNIT,
 INCLUDING BUMPERS.
  
 2. PROVIDE DETAIL FOR HANGING WATER HEATER IT WILL
 WEIGH ABOUT 700LB. PER WPB AMEND. TO FBC 107.2.1
  
 COMPLY WITH PROVISO FROM ORIGINAL PLAN:
  
 4 OF THE 9 DRINKING FOUNTAINS SHALL COMPLY WITH FBC
 ACC. SEC. 602.7 DRINKING FOUNTAINS FOR STANDING
 PERSONS.
 SPOUT OUTLETS OF DRINKING FOUNTAINS FOR STANDING
 PERSONS SHALL BE 38 INCHES (965 MM) MINIMUM AND 43
 INCHES (1090 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
 TO MEET THE REQUIREMENTS OF FBC ACC. SEC.
 211.3 MORE THAN MINIMUM NUMBER.
 WHERE MORE THAN THE MINIMUM NUMBER OF DRINKING
 FOUNTAINS SPECIFIED IN 211.2 ARE PROVIDED, 50 PERCENT
 OF THE TOTAL NUMBER OF DRINKING FOUNTAINS PROVIDED
 SHALL COMPLY WITH 602.1 THROUGH 602.6, AND 50 PERCENT
 OF THE TOTAL NUMBER OF DRINKING FOUNTAINS PROVIDED
 SHALL COMPLY WITH 602.7.