Date |
Text |
2016-07-06 07:00:12 | BUILDING PLAN REVIEW |
| W. P. B. REVISION: 16061385 |
| W. P. B. PERMIT: 16041215 |
| ADD: 2001 S. DIXIE HWY. |
| CONT: MAC ENTERPRISES |
| TEL: 561-236-3627 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WED. JULY 06/ 2016 |
| ACTION: DENIED |
| |
| 1) SHEET A201 THE SOUTH ELEVATION THE NEW WINDOWS(206) |
| ON THE 2ND FLOOR, THE WINDOW THAT IS WITHIN 10 FEET OF |
| THE 2ND FLOOR LANDING REQUIRES 45 MINUTE FIRE RATED |
| UNIT. SHEET 610 WINDOW SCHEDULE DOES NOT INDICATE A 45 |
| MIN. FIRE RATED UNIT. 2014 FBC-B 1026.6. |
| |
| |
| 2) THE STRUCTURAL SHEETS HAVE NOT BEEN UPDATED FOR NEW |
| COLUMNS AT EACH SIDE OF THE WINDOWS NOR BEAM OR LINTEL |
| SCHEDULE FOR THE NEW OPENINGS. |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION 107.2.1.3 107.3.5 MINIMUM |
| 107.3.5.1 COMMERCIAL BUILDINGS: |
| WIND REQUIREMENTS PRESSURES / NEW OPENINGS |
| BUILDING ENVELOPE/ PRODUCT APPROVALS |
| STRUCTURAL ELEMENTS, COLUMNS. BEAMS AND OR LINTELS. |
| |
| 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION |
| DEVELOPMENT SERVICES DEPARTMENT |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |