2016-07-12 11:37:23 | 1ST ELECTRICAL REVIEW NOTES |
| REVIEWED FOR COMPLIANCE WITH: |
| 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| |
| 1. SECTION 107.2.1 OF THE WPB CITY AMENDMENTS REQUIRE |
| THAT THE CONSTRUCTION DOCUMENTS BE OF SUFFICIENT |
| CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| THE PROPOSED WORK AND SHOW IN DETAIL THAT IT WILL |
| CONFORM TO CODE REQUIREMENTS SUCH DRAWINGS SHALL |
| INDICATE THE APPLICABLE DESIGN CODE, AND FURTHERMORE, |
| THE DRAWINGS SHALL BEAR THE NAME AND SIGNATURE OF THE |
| PERSON RESPONSIBLE FOR THE DESIGN. (YOUR NAME AND |
| SIGNATURE SHALL APPEAR ON ALL DOCUMENTS). PROVIDE A |
| FLOORPLAN TO A MINIMUM 1/8? SCALE OF THE PROPOSED WORK. |
| SHOW LOCATION OF ELECTRICAL PANELS. |
| 2. NEC 408.4(A) REQUIRES THAT YOU PROVIDE A PANEL |
| SCHEDULE OR CIRCUIT DIRECTORY LEGIBLY INDICATING THE |
| SPECIFIC PURPOSE OF EVERY CIRCUIT PROVIDE SPECS FOR THE |
| PROPOSED RANGE HOOD AND INDICATE IF IT IS TO BE |
| CONNECTED INTO A FIRE ALARM SYSTEM. |
| 3. INCLUDE THE CONNECTIONS TO THE DISH WASHER AND |
| DISPOSAL IN YOUR SCOPE OF WORK. |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| THANK YOU, |
| MIKE ALBARRAN |
| ELECTRICAL PLANS EXAMINER |
| PH: 561-805-6746 |
| EMAIL: [email protected] |
| |