 PLUMBING COMMENTS:
  
 1. SHT A-1.0 CODE RESEARCH INDICATES THE TENANT SPACES
 TO BE MERCANTILE OCCUPANCIES. UNDER THE HEADING OF
 MEANS OF EGRESS THERE ARE (2) DISCREPANCIES, (1) THE
 OCCUPANCY TYPE IS LISTED AS BUSINESS, THE (2) ISSUE IS
 OCCUPANT LOAD IS FIGURED AT 60 SQ. FT. / OCCUPANT
 PLEASE REVIEW THE 2014 FBC-B TABLE 1004.1.2 WHERE
 EITHER AT BASEMENT OR GRADE FLOOR LEVEL THE OCCUPANT
 LOAD IS TAKEN AT 30 SQ. FT./ OCCUPANT. CLARIFICATION OF
 THIS AFFECTS THE NUMBER OF BATHROOMS REQUIRED. IF IT IS
 A MERCANTILE ONLY 1 IS REQUIRED BUT IF IT IS BUSINESS
 SEPARATE FACILITIES ARE REQUIRED FOR MEN AND WOMEN
 WHICH IS 2 BATHROOMS PER UNIT. 2014 FBC PL SEC 403.2
  
  
  
  
  
  
  