2016-07-05 07:48:211ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16061353
 7/5/16
  
 1) SHEET M1.1: DUCT SMOKE DETECTORS ARE REQUIRED IN THE
 RETURN AIR SYSTEMS OF AC SYSTEMS 1 & 2- SECTION
 606.2.1. PLEASE NOTE THAT MANUFACTURER'S SPECIFICATIONS
 TYPICALLY INDICATE THAT 5-TON SYSTEMS HAVE CAPACITIES
 EXCEEDING 2000 CFMS.
  
 2) M1.1: PROVIDE THE CLEARANCE DISTANCES FOR THE O/A
 INTAKES AS REQUIRED BY SECTION 401.4, ITEMS 1-4.
  
 3) M5.1: PROVIDE THE WIND LOAD DESIGN CRITERIA FOR
 INSTALLATION OF THE EXTERIOR CONDENSERS, AND COMPLETE
 DETAILS FOR ANCHORING THE UNITS TO THE CONCRETE PADS-
 LENGTH OF THE 1/4" BOLT, AND TYPE AND SIZE OF CLIP
 FASTENERS- SECTION 301.15.
  
 4) A-1.1 & M0.1: DOORS A101 & B101 MUST BE
 NON-COMBUSTIBLE- SECTION C403.2.7.2 FBC-14 ENERGY
 CONSERVATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER