Date |
Text |
2016-07-08 06:58:16 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16061352 |
| ADD: 1905 S. DIXIE HWY. SUITE # ??????? |
| CONT: SISCA |
| TEL: 561-228-7503 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: FRI. JULY 08/2016 |
| ACTION: DENIED |
| |
| 1) THE PERMIT APPLICATION DOES NOT INCLUDE THE SUITES |
| TO BE INCLUDED IN THE SCOPE OF WORK TO BE COVERED UNDER |
| THIS PERMIT. THE TITLE BLOCK ALSO JUST SAYS 1905 S. |
| DIXIE HWY. IT WOULD APPEAR THE SCOPE OF WORK TO BE |
| COVERED UNDER THIS PERMIT IS BOTH SUITES 100A & 100B? |
| 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. 107.2.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS.CONSTRUCTION |
| DOCUMENTS SHALL BE OF SUFFICIENTCLARITY TO INDICATE THE |
| LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED. |
| |
| 2) SHEET A-1.0: |
| 2A) CODE RESEACH OCCUPANCY CLASSIFICATION IS INDICATED |
| AS MERCANTILE BUT ALSO LIST NON-SEPARATED USE. IS THERE |
| ANOTHER OCCUPANCY TYPE NOT DECLARED WHERE NON-SEPARATED |
| USE COMES INTO PLAY IN A MIXED USE BUILDING ? 2014 |
| FBC-B 508.3 NONSEPARATED OCCUPANCIES. BUILDINGS OR |
| PORTIONS OF BUILDINGS THAT COMPLY WITH THE PROVISIONS |
| OF THIS SECTION SHALL BE CONSIDERED AS NONSEPARATED |
| OCCUPANCIES. |
| |
| 2B) CODE RESEARCH INDICATES THE TENANT SPACES TO BE |
| MERCANTILE OCCUPANCIES. UNDER THE HEADING OF MEANS OF |
| EGRESS THERE ARE (2) DISCREPANCIES, (1) THE OCCUPANCY |
| TYPE IS LISTED AS BUSINESS AND THE OCCUPANT LOAD IS |
| TAKEN AT 100 SQ. FT/ OCCUPANT, THE (2) ISSUE IS |
| OCCUPANT LOAD IS FIGURED AT 60 SQ. FT. / OCCUPANT |
| PLEASE REVIEW THE 2014 FBC-B TABLE 1004.1.2 WHERE |
| EITHER AT BASEMENT OR GRADE FLOOR LEVEL THE OCCUPANT |
| LOAD IS TAKEN AT 30 SQ. FT./ OCCUPANT. |
| |
| 3) SHEET A-2.0: |
| 3A) PLEASE REVIEW THE ALLOWABLE CENTERS FOR AN |
| ACCESSIBLE WATER CLOSET IN THE 2014 FBC-ACCESSIBILITY |
| CODE THE WATER CLOSET IS TO BE LOCATED BETWEEN 16 |
| INCHES TO 18 INCHES FROM THE SIDE WALL. SEE ACCESS. |
| CODE 604.2. THE OTHER ISSUE THE PLANS DO NOT SHOW AN |
| OVER ALL MEASUREMENT OF THE RESTROOMSTHE MINIMUM |
| MEASUREMENT WOULD BE 7 FEET 1 INCH. THE PLANS CENTER |
| THE WATER CLOSET AT 16 3/4 INCHES OFF THE WALL AND THE |
| LAV IS CENTERED AT 15 3/4 INCHES OFF THE OPPOSITE SIDE |
| WALL. THE "CLEARANCES" FROM THE SIDE WALL OVER THE |
| WATER CLOSET TO THE CLOSET EDGE OF THE LAV IS 60 |
| INCHES, THE CENTERLINE DISTANCE OFF THE WALL FOR THE |
| LAV AT 15 3/4 INCHES WILL INCREASE THE OVERALL DISTANCE |
| OR THE ROOM BY 3/4 INCHES. |
| |
| 3B) THE DETAILS FOR THE GRAB BARS ALL SHOW THE DISTANCE |
| 36 INCHES FROM THE FINISH FLOOR TO CENTERLINE, PLEASE |
| NOTE THE 2014 FBC-ACCESSIBILITY CODE SECTION 609.4 |
| REQUIRES THE MEASUREMENT TO BE TAKEN FROM THE TOP OF |
| THE GRIPPING SURFACE. |
| |
| 3C) THERE ARE NO DETAILS SHOWN HOW CODE COMPLIANCE FOR |
| BACKING FOR GRAB BARS. 2014 FBC-ACCESS. CODE 609.8 |
| STRUCTURAL STRENGTH. |
| |
| 3D) THE PLANS DO NOT SHOW ACCESSIBLE SGINAGE. SHOW |
| COMPLIANCE WITH ACCESS. CODE 703.1 GENERAL. |
| SIGNS SHALL COMPLY WITH 703. WHERE BOTH VISUAL AND |
| TACTILE CHARACTERS ARE REQUIRED, EITHER ONE SIGN WITH |
| BOTH VISUAL AND TACTILE CHARACTERS, OR TWO SEPARATE |
| SIGNS, ONE WITH VISUAL, AND ONE WITH TACTILE |
| CHARACTERS, SHALL BE PROVIDED. |
| |
| 703.2 RAISED CHARACTERS. |
| RAISED CHARACTERS SHALL COMPLY WITH 703.2 AND SHALL BE |
| DUPLICATED IN BRAILLE COMPLYING WITH 703.3. RAISED |
| CHARACTERS SHALL BE INSTALLED IN ACCORDANCE WITH 703.4. |
| |
| 3E) THE PLANS DO NOT INDICATE IF THE 2 MEANS OF EGRESS |
| ARE ACCESSIBLE MEANS OF EGRESS. 2014 FBC-ACCESSIBILITY |
| CODE 207.1 ACCESSIBLE MEANS OF EGRESS SHALL COMPLY WITH |
| THE 2003 IBC SECTION 1007. 2003 IBC-B 1007.1. WHERE 2 |
| OR MORE MEANS OF EGRESS IS REQUIRED BY SECTION 1014.1 |
| OR 1018.1 FROM ANY ACCESSIBLE PORTION OF THE SPACE |
| SHALL BE SERVED BY NOT LESS THAN TWO ACCESSIBLE MEANS |
| OF EGRESS. |
| |
| 3F) PLEASE PROVIDE A LETTER SHOWING A ITEMIZED LIST OF |
| ELEMNTS WHERE UP TO 20% OF THE CONTRACT VALUE HAS |
| BROUGHT THESE ELEMENTS UP TO MEET THE CURRENT 2014 |
| ACCESSIBLITY CODE. 202.4.1 DISPROPORTIONATE COST. |
| ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF |
| TRAVEL TO THE ALTERED AREA WILL BE DEEMED |
| DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE |
| COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE |
| PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS |
| EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF |
| TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING |
| AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE |
| ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING |
| RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS, |
| ENLARGING TOILET STALLS, INSULATING PIPES, OR |
| INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS |
| ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH |
| AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT, |
| INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT |
| TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING |
| AN INACCESSIBLE DRINKING FOUNTAIN. |
| |
| 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION |
| DEVELOPMENT SERVICES DEPARTMENT |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| DEVELOPMENT SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |
| |
| |
| |
| |
| |