2016-06-29 16:43:35****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 SAME INSTALLATION SCHEDULE WAS SUBMITTED.
  
 1. FBC 5TH EDITION RESIDENTIAL 301, SUBSTRATE FOR ALL
 OPENINGS IS CONCRETE PER THE INSTALLATION SCHEDULE. HOW
 HAS THIS BEEN DETERMINED? A FILLED CELL IS NOT
 CONSIDERED "CONCRETE"; THE "HOLLOW BLOCK" CHART SHOULD
 BE USED. FOR A TYPICAL CBS STRUCTURE, THE TOP IS
 CONCRETE, SIDES AND BOTTOM ARE FILLED CELLS.
  
 EITHER PROVIDE EVIDENCE THAT SIDES AND BOTTOM ARE
 CONCRETE, OR REVISE THE INSTALLATION SCHEDULE
 ACCORDINGLY.
  
  