Plan Review Notes For Permit 16061332 |
Permit Number |
16061332 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-06-25 13:10:22 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. FBC 5TH EDITION RESIDENTIAL 301, SUBSTRATE FOR ALL | | OPENINGS IS CONCRETE PER THE INSTALLATION SCHEDULE. HOW | | HAS THIS BEEN DETERMINED? A FILLED CELL IS NOT | | CONSIDERED "CONCRETE"; THE "HOLLOW BLOCK" CHART SHOULD | | BE USED. FOR A TYPICAL CBS STRUCTURE, THE TOP IS | | CONCRETE, SIDES AND BOTTOM ARE FILLED CELLS. | | | | EITHER PROVIDE EVIDENCE THAT SIDES AND BOTTOM ARE | | CONCRETE, OR REVISE THE INSTALLATION SCHEDULE | | ACCORDINGLY. | | | | |
|