 GAS COMMENTS;
  
  
 1. GAS RISER DOES NOT CLEARLY SHOW EXISTING POOL HEATER
 SHOW LOCATION OF EXISTING POOL HEATER ON RISER. PER WPB
 AMEND. TO FBC SEC. 107.2.1
  
 2. CLEARLY INDICATE PRESSURE OF SYSTEM.PER FBC-2014
 FUEL GAS SEC. 402.2.
  
 3. THE EXISTING 3/4 FROM METER TI FIRST TEE NEEDS TO BE
 INCREASED TO 1IN. PER FBC FUEL GAS TABLE TABLE 402.4(1)
  
 4. INDICATE WHAT SIZING TABLES YOU ARE USING. PER WPB
 AMEND. TO FBC SEC. 107.2.1