Plan Review Notes
Plan Review Notes For Permit 16061282
Permit Number 16061282
Review Stop B
Sequence Number 8
Notes
Date Text
2018-06-05 15:21:37RESIDENTIAL (R3) REVISION, 8TH BUILDING REVIEW
 CHECKLIST.
 CODE: 2010 FBC.
  
 ORIGINAL COMMENT:
 1- GAF FLAT ROOF NOA 13-1022.15 SPECIFIED ON DRAWING
 S-2 AND SELECTED INSULATED ASSEMBLY ON PAGE 6 OF 16:
 PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7 TO MEET THE DESIGN
 PRESSURES OF SEC. R301.1 AT PERIMETER AND CORNER AREAS.
 FBC-RESIDENTIAL 2010.
 NOTE: SEE GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 SUBMITTED FOR RAS 117 CALCULATIONS REQUIREMENTS.
  
 RESPONSE:
 A) INFORMATION IN RAS 117 CALCULATIONS SUBMITTED DON'T
 MATCH ENGINEER OF RECORD DRAWINGS SUBMITTED UNDER
 REVISION #16061282. ENGINEER SELECTED ASSEMBLY WITH THE
 MAXIMUM DESIGN PRESSURES OF -52.5 . ENGINEER DOING THE
 RAS 117 CALCULATIONS IS USING ASSEMBLY WITH A MAXIMUM
 DESIGN PRESSURE OF -45PSF. IN ADDITION, THE FASTENER
 USED FOR THE ASSEMBLY WITH A MAXIMUM DESIGN PRESSURE OF
 -45PSF IS DIFFERENT THAN THE ONE SPECIFIED BY THE
 ENGINEER DOING THE RAS 117 CALCULATIONS. FASTENERS ON
 THE APPROVED ASSEMBLIES CAN NOT BE INTERCHANGED. REVISE
 AS REQUIRED TO MATCH. COORDINATE ALL THE INFORMATION TO
 AVOID MORE CONFLICTS AND UN-NECESSARY DELAYS. SEC.
 R301.1 FBC-RESIDENTIAL 2010.
  
 B) THIS PROJECT WAS REVIEWED UNDER THE 2010 FBC
 RESIDENTIAL NOT 2017. REVISE AS REQUIRED. CHAPTER 553
 F.S.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  