Plan Review Notes
Plan Review Notes For Permit 16061282
Permit Number 16061282
Review Stop B
Sequence Number 6
Notes
Date Text
2017-11-01 18:13:29 
 RESIDENTIAL (R3) REVISION, SIXTH BUILDING REVIEW
 CHECKLIST.
 CODE: 2010 FBC.
  
 NOTE:
 CONTRACTOR OWES $154.50 FOR PREVIOUS REVISION FEES. NO
 MORE REVIEWS WILL BE DONE UNTIL THESE FEES ARE PAID.
 FEES FOR CURRENT SUBMITTAL WILL BE ASSESSED ONCE LATEST
 SUBMITTAL IS CLARIFIED.
  
  
 1- NO CLEAR WHAT THE CONTRACTOR IS DOING. CONTRACTOR TO
 CLARIFY WHY LATEST DRAWINGS S-2 AND S-3 THAT WERE
 SIGNED BY ENGINEER OF RECORD ON 08/10/17 WERE VOIDED.
 WHY SUBMITTING OLD DRAWINGS THAT WERE SIGNED AND SEALED
 BY THE ENGINEER OF RECORD ON 06/29/16. NO SURE WHAT ARE
 THE REVISIONS FOR THIS JOB. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 2- NONE OF THE COMMENTS FROM PREVIOUS CHECKLIST WERE
 ADDRESSED. NO CLEAR WHAT THE CONTRACTOR IS DOING. SEC.
 107.2.1 CITY AMENDMENTS.
  
 3- I WANT TO REQUEST A MEETING WITH THE CONTRACTOR AND
 MY SUPERVISOR TO GET THIS JOB BACK IN TRACK.
  
  
 NOTE:
 BELOW IS THE COPY OF PREVIOUS CHECKLIST. NOTHING WAS
 ADDRESSED:
  
 1- FLAT ROOF FL11946-R7 SUBMITTED:
 A) CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO
 BE INSTALLED TO VERIFY COMPLIANCE WIT THE DESIGN
 PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL, 5TH EDITION
 (2014).
 REPEAT COMMENT. NOT ADDRESSED.
  
 B) NONE OF THE ASSEMBLIES FROM FLORIDA PRODUCT APPROVAL
 FL11946-R7 SUBMITTED MEETS THE DESIGN PRESSURES FOR ALL
 ROOF ZONES. NEED TO PROVIDE SIGNED AND SEALED RAS 117
 CALCULATIONS FOR PERIMETER AND CORNER AREAS AS REQUIRED
 BY LIMITATION #5.7 OF FLORIDA PRODUCT APPROVAL
 SUBMITTED. NEED THE CALCULATIONS TO MEET THE DESIGN
 PRESSURES REQUIRED BY SEC. R301.1 FBC-RESIDENTIAL.
 REPEAT COMMENT. NOT ADDRESSED.
  
 2- CONTRACTOR TO PROVIDE THE ADDITIONAL VALUE TO USE
 STEEL BEAMS INSTEAD OF WOOD. INCLUDE THE DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS.
 REPEAT COMMENT. NOT ADDRESSED.
  
 3- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 WOOD RAILING BY THE SPECIALTY ENGINEER AS SPECIFIED ON
 DETAILS ON SHEET S-3.
 SEC. R301.1 FBC 2010. NOTE: THIS INFORMATION NEED TO BE
 PROVIDED FOR REVIEW PRIOR TO INSPECTIONS TO AVOID
 CONFLICTS OR DELAYS.
 REPEAT COMMENT. NOT ADDRESSED.
 NOTE: THIS WAS ALSO REQUESTED ON PROVISO DATED 10/20/15
 AND NOT INFORMATION WAS PROVIDED.
  