Date |
Text |
2017-11-01 18:13:29 | |
| RESIDENTIAL (R3) REVISION, SIXTH BUILDING REVIEW |
| CHECKLIST. |
| CODE: 2010 FBC. |
| |
| NOTE: |
| CONTRACTOR OWES $154.50 FOR PREVIOUS REVISION FEES. NO |
| MORE REVIEWS WILL BE DONE UNTIL THESE FEES ARE PAID. |
| FEES FOR CURRENT SUBMITTAL WILL BE ASSESSED ONCE LATEST |
| SUBMITTAL IS CLARIFIED. |
| |
| |
| 1- NO CLEAR WHAT THE CONTRACTOR IS DOING. CONTRACTOR TO |
| CLARIFY WHY LATEST DRAWINGS S-2 AND S-3 THAT WERE |
| SIGNED BY ENGINEER OF RECORD ON 08/10/17 WERE VOIDED. |
| WHY SUBMITTING OLD DRAWINGS THAT WERE SIGNED AND SEALED |
| BY THE ENGINEER OF RECORD ON 06/29/16. NO SURE WHAT ARE |
| THE REVISIONS FOR THIS JOB. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| 2- NONE OF THE COMMENTS FROM PREVIOUS CHECKLIST WERE |
| ADDRESSED. NO CLEAR WHAT THE CONTRACTOR IS DOING. SEC. |
| 107.2.1 CITY AMENDMENTS. |
| |
| 3- I WANT TO REQUEST A MEETING WITH THE CONTRACTOR AND |
| MY SUPERVISOR TO GET THIS JOB BACK IN TRACK. |
| |
| |
| NOTE: |
| BELOW IS THE COPY OF PREVIOUS CHECKLIST. NOTHING WAS |
| ADDRESSED: |
| |
| 1- FLAT ROOF FL11946-R7 SUBMITTED: |
| A) CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO |
| BE INSTALLED TO VERIFY COMPLIANCE WIT THE DESIGN |
| PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL, 5TH EDITION |
| (2014). |
| REPEAT COMMENT. NOT ADDRESSED. |
| |
| B) NONE OF THE ASSEMBLIES FROM FLORIDA PRODUCT APPROVAL |
| FL11946-R7 SUBMITTED MEETS THE DESIGN PRESSURES FOR ALL |
| ROOF ZONES. NEED TO PROVIDE SIGNED AND SEALED RAS 117 |
| CALCULATIONS FOR PERIMETER AND CORNER AREAS AS REQUIRED |
| BY LIMITATION #5.7 OF FLORIDA PRODUCT APPROVAL |
| SUBMITTED. NEED THE CALCULATIONS TO MEET THE DESIGN |
| PRESSURES REQUIRED BY SEC. R301.1 FBC-RESIDENTIAL. |
| REPEAT COMMENT. NOT ADDRESSED. |
| |
| 2- CONTRACTOR TO PROVIDE THE ADDITIONAL VALUE TO USE |
| STEEL BEAMS INSTEAD OF WOOD. INCLUDE THE DESIGN |
| PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY |
| AMENDMENTS. |
| REPEAT COMMENT. NOT ADDRESSED. |
| |
| 3- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| WOOD RAILING BY THE SPECIALTY ENGINEER AS SPECIFIED ON |
| DETAILS ON SHEET S-3. |
| SEC. R301.1 FBC 2010. NOTE: THIS INFORMATION NEED TO BE |
| PROVIDED FOR REVIEW PRIOR TO INSPECTIONS TO AVOID |
| CONFLICTS OR DELAYS. |
| REPEAT COMMENT. NOT ADDRESSED. |
| NOTE: THIS WAS ALSO REQUESTED ON PROVISO DATED 10/20/15 |
| AND NOT INFORMATION WAS PROVIDED. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| (561)805-6712 |
| [email protected] |
| |
| |