2017-08-16 12:34:30 | RESIDENTIAL (R3) REVISION, FIFTH BUILDING REVIEW |
| CHECKLIST. |
| CODE: 2010 FBC. |
| |
| ****NOTE: |
| REVISION FEES WERE ADDED FOR THE THREE DRAWINGS |
| SUBMITTED (S1, S2 AND S3 SIGNED AND SEALED BY THE |
| ENGINEER ON 08/10/17). CONTRACTOR OWES $154.50 FOR |
| REVISION FEES. |
| |
| |
| 1- FLAT ROOF FL11946-R7 SUBMITTED: |
| A) CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO |
| BE INSTALLED TO VERIFY COMPLIANCE WIT THE DESIGN |
| PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL, 5TH EDITION |
| (2014). |
| REPEAT COMMENT. NOT ADDRESSED. |
| |
| B) NONE OF THE ASSEMBLIES FROM FLORIDA PRODUCT APPROVAL |
| FL11946-R7 SUBMITTED MEETS THE DESIGN PRESSURES FOR ALL |
| ROOF ZONES. NEED TO PROVIDE SIGNED AND SEALED RAS 117 |
| CALCULATIONS FOR PERIMETER AND CORNER AREAS AS REQUIRED |
| BY LIMITATION #5.7 OF FLORIDA PRODUCT APPROVAL |
| SUBMITTED. NEED THE CALCULATIONS TO MEET THE DESIGN |
| PRESSURES REQUIRED BY SEC. R301.1 FBC-RESIDENTIAL. |
| REPEAT COMMENT. NOT ADDRESSED. |
| |
| 2- CONTRACTOR TO PROVIDE THE ADDITIONAL VALUE TO USE |
| STEEL BEAMS INSTEAD OF WOOD. INCLUDE THE DESIGN |
| PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY |
| AMENDMENTS. |
| REPEAT COMMENT. NOT ADDRESSED. |
| |
| 3- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| WOOD RAILING BY THE SPECIALTY ENGINEER AS SPECIFIED ON |
| DETAILS ON SHEET S-3. |
| SEC. R301.1 FBC 2010. NOTE: THIS INFORMATION NEED TO BE |
| PROVIDED FOR REVIEW PRIOR TO INSPECTIONS TO AVOID |
| CONFLICTS OR DELAYS. |
| REPEAT COMMENT. NOT ADDRESSED. |
| NOTE: THIS WAS ALSO REQUESTED ON PROVISO DATED 10/20/15 |
| AND NOT INFORMATION WAS PROVIDED. |
| |