Plan Review Notes
Plan Review Notes For Permit 16061282
Permit Number 16061282
Review Stop B
Sequence Number 4
Notes
Date Text
2017-02-10 10:16:59RESIDENTIAL (R3) REVISION, FOURTH BUILDING REVIEW
 CHECKLIST.
 CODE: 2010 FBC.
  
 1- FLAT ROOF FL11946-R7 SUBMITTED:
 A) CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO
 BE INSTALLED TO VERIFY COMPLIANCE WIT THE DESIGN
 PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL, 5TH EDITION
 (2014).
 REPEAT COMMENT. NOT ADDRESSED.
  
 B) NONE OF THE ASSEMBLIES FROM FLORIDA PRODUCT APPROVAL
 FL11946-R7 SUBMITTED MEETS THE DESIGN PRESSURES FOR ALL
 ROOF ZONES. NEED TO PROVIDE SIGNED AND SEALED RAS 117
 CALCULATIONS FOR PERIMETER AND CORNER AREAS AS REQUIRED
 BY LIMITATION #5.7 OF FLORIDA PRODUCT APPROVAL
 SUBMITTED. NEED THE CALCULATIONS TO MEET THE DESIGN
 PRESSURES REQUIRED BY SEC. R301.1 FBC-RESIDENTIAL.
 REPEAT COMMENT. NOT ADDRESSED.
  
 2- CONTRACTOR TO PROVIDE THE ADDITIONAL VALUE TO USE
 STEEL BEAMS INSTEAD OF WOOD. INCLUDE THE DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS.
 REPEAT COMMENT. NOT ADDRESSED.
  
 3- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 WOOD RAILING BY THE SPECIALTY ENGINEER AS SPECIFIED ON
 DETAILS ON SHEET S-3.
 SEC. R301.1 FBC 2010. NOTE: THIS INFORMATION NEED TO BE
 PROVIDED FOR REVIEW PRIOR TO INSPECTIONS TO AVOID
 CONFLICTS OR DELAYS.
 REPEAT COMMENT. NOT ADDRESSED.
 NOTE: THIS WAS ALSO REQUESTED ON PROVISO DATED 10/20/15
 AND NOT INFORMATION WAS PROVIDED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved