Plan Review Notes
Plan Review Notes For Permit 16061282
Permit Number 16061282
Review Stop B
Sequence Number 1
Notes
Date Text
2016-06-24 15:41:02RESIDENTIAL (R3) REVISION, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- ORIGINAL APPROVED PLANS DON'T INCLUDE FLAT ROOF
 SYSTEMS. ENGINEER OF RECORD NEEDS TO REVISE PLANS
 SPECIFYING THE PROPOSED FLAT ROOF.
 PROVIDE TWO SIGNED AND SEALED DRAWINGS SHOWING THE
 REVISION. SEC. R301 OF 2010 FBC-RESIDENTIAL. .
  
 2- FLAT ROOF NOA 11-0601.10 SUBMITTED IS NOT DESIGNED
 FOR FLAT ROOF. THIS NOA IS AN UNDERLAYMENT FOR PITCHED.
 ROOFS. REVISE AS REQUIRED.
 (A) PROVIDE PRODUCT APPROVAL (2 COPIES) FOR FLAT ROOF
 SYSTEM THAT IS DESIGNED FOR THE ROOF DECK FINISH AS
 SPECIFIED ON PLANS.
 FAC 61G20-3.002(33).
  
 (B) CLEARLY IDENTIFY APPROVED ASSEMBLY TO BE USED FROM
 THE PRODUCT APPROVAL RE-SUBMITTED TO VERIFY COMPLIANCE
 WITH THE DESIGN PRESSURES OF SEC. R301 OF 2010
 FBC-RESIDENTIAL.
  
 (C) IF THE SELECTED ASSEMBLY DOESN'T MEET THE
 CALCULATED DESIGN PRESSURES, THEN SIGNED AND SEALED RAS
 117 CALCULATIONS ARE REQUIRED. SEE PRODUCT APPROVAL
 SUBMITTED. SEC. R301 OF 2010 FBC-RESIDENTIAL.
  
 (D) ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) FLAT ROOF PRODUCT APPROVAL AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 3- THIS FLAT ROOF SYSTEM WAS NOT PART OF THE APPROVED
 PLANS. SPECIFY THE ADDITIONAL VALUE FOR THE NEW FLAT
 ROOF AS REQUIRED BY SEC. 109.3 CITY AMENDMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  
  