Plan Review Notes
Plan Review Notes For Permit 16061269
Permit Number 16061269
Review Stop G
Sequence Number 2
Notes
Date Text
2016-10-17 05:39:351) WHAT HAPPENED TO THE EXISTING GAS RANGE WITH A LOAD
 OF 100,000 BTU'S? THIS NEEDS TO BE ADDED INTO THE TOTAL
 BTU LOAD OF THE SYSTEM.
 2) THE MINIMUM SIZE OF THE SCH. 40 PIPE AT THE METER
 SHALL BE A MIN. OF 1 1/2 INCH PIPE PER TABLE 402.4 (2).
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  