2016-10-17 05:39:35 | 1) WHAT HAPPENED TO THE EXISTING GAS RANGE WITH A LOAD | | OF 100,000 BTU'S? THIS NEEDS TO BE ADDED INTO THE TOTAL | | BTU LOAD OF THE SYSTEM. | | 2) THE MINIMUM SIZE OF THE SCH. 40 PIPE AT THE METER | | SHALL BE A MIN. OF 1 1/2 INCH PIPE PER TABLE 402.4 (2). | | | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | |
|