Plan Review Notes
Plan Review Notes For Permit 16061264
Permit Number 16061264
Review Stop P
Sequence Number 1
Notes
Date Text
2016-06-24 17:11:391ST REVIEW
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
 PLUMBING COMMENTS:
  
  
 1. WATER FOUNTAIN REQUIRED FOR CHANGE OF OCCUPANCY
 SHALL COMPLY WITH FBC PL [B] 410.2 MINIMUM NUMBER.
 WHERE DRINKING FOUNTAINS ARE REQUIRED, NOT FEWER THAN
 TWO DRINKING FOUNTAINS SHALL BE PROVIDED. ONE DRINKING
 FOUNTAIN SHALL COMPLY WITH THE REQUIREMENTS FOR PEOPLE
 WHO USE A WHEELCHAIR AND ONE DRINKING FOUNTAIN SHALL
 COMPLY WITH THE REQUIREMENTS FOR STANDING PERSONS.
 FBC PL TABLE 403.1/ A DRINKING FOUNTAIN COMPILING WITH
 FBC ACC 211.2 MINIMUM NUMBER.
 NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
  
 2. A SERVICE SINK IS REQUIRED FOR CHANGE OF OCCUPANCY
 SHALL COMPLY WITH FBC PL TABLE 403.1
  
 3. PLEASE PROVIDE WATER RISER DIAGRAM .PER WPB AMEND TO
 FBC 107.2.1
  
 4. PLEASE SHOW THE CLEAR FLOOR SPACE FOR THE WATER
 CLOSET SHALL COMPLY WITHE FBC ACC 604.3.1 SIZE.
 CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL.
  
 4. PLEASE SHOW THE CLEAR FLOOR SPACE FOR THE LAVATORY'S
 SHALL COMPLY WITHE FBC ACC 606.2 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR
 A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 5. PLEASE SHOW THE CLEAR FLOOR SPACE FOR THE WATER
 FOUNTAIN SHALL COMPLY WITHE FBC ACC 602.2 CLEAR FLOOR
 SPACE.
 UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE
 COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH
 AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 6. THE DOOR TO BATHROOM SHALL COMPLY WITH FBC ACC
 603.2.3 DOOR SWING.
 DOORS SHALL NOT SWING INTO THE CLEAR FLOOR SPACE OR
 CLEARANCE REQUIRED FOR ANY FIXTURE. DOORS SHALL BE
 PERMITTED TO SWING INTO THE REQUIRED TURNING SPACE.
  
 EXCEPTIONS:
  
 1. DOORS TO A TOILET ROOM OR BATHING ROOM FOR A SINGLE
 OCCUPANT ACCESSED ONLY THROUGH A PRIVATE OFFICE AND NOT
 FOR COMMON USE OR PUBLIC USE SHALL BE PERMITTED TO
 SWING INTO THE CLEAR FLOOR SPACE OR CLEARANCE PROVIDED
 THE SWING OF THE DOOR CAN BE REVERSED TO COMPLY WITH
 603.2.3.
  
 2. WHERE THE TOILET ROOM OR BATHING ROOM IS FOR
 INDIVIDUAL USE AND A CLEAR FLOOR SPACE COMPLYING WITH
 305.3 IS PROVIDED WITHIN THE ROOM BEYOND THE ARC OF THE
 DOOR SWING, DOORS SHALL BE PERMITTED TO SWING INTO THE
 CLEAR FLOOR SPACE OR CLEARANCE REQUIRED FOR ANY
 FIXTURE.
  
 7. TOILET SHALL COMPLY WITH FBC ACC 604.2 LOCATION.
 THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM
 TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR
 PARTITION,
 604.4 SEATS.
 THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES
 (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS
 SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION.
  
 8. GRAB BARS SHALL COMPLY WITH FBC ACC 609.4 POSITION
 OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE,
  
  
  
  
  
  
  
 DISREGARD COMMENTS BELOW
2016-06-24 09:59:59NEED TO CORRECT DRAWING OF VENTING FOR FIXTURES NEED TO
 HAVE BETWEEN W/C AND LAV. NEED TO HAVE SIZE OF VENTS ON
 DRAWING