Plan Review Notes
Plan Review Notes For Permit 16061264
Permit Number 16061264
Review Stop B
Sequence Number 1
Notes
Date Text
2016-06-29 07:07:34BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16061264
 ADD: 420 6TH ST.
 CONT: TRI GENERAL CONTRACTORS
 TEL: 561-324-6944
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON.JULY 05/ 2016
 ACTION: DENIED
  
 1) PLEASE PROVIDE A COMPLETE SET OF FLOOR PLANS SHOWING
 THE 1ST FLOOR AND WHAT EITHER APPEARS TO BE A MEZANINE
 OR A 2ND FLOOR. PLEASE PROVIDE THE SQUARE FOOT FLOOR
 AREA OF THE MEZANINE/ 2ND FLOOR AS WELL AS THE OPEN
 AREA OF THE 1ST FLOOR TO DETERMINE THE FLOOR AREA AND
 USAGE.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS. THE EXAMINATION OF THE DOCUMENTS BY THE
 BUILDING OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM
 CRITERIA AND DOCUMENTS: A FLOOR PLAN; SITE
 PLAN.
  
 107.3.5.1.1 COMMERCIAL BUILDINGS:BUILDING
 1. SITE REQUIREMENTS:
 PARKING
 FIRE ACCESS
 2. OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED
 (SEE TABLE 503).
 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL
 INCLUDE THE FOLLOWING COMPONENTS:
 FIRE-RESISTANT SEPARATIONS
 FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION
 PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS
 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 SCHEMATIC FIRE SPRINKLERS, REQUIRED OR NOT
 7. OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
 8. STRUCTURAL REQUIREMENTS SHALL INCLUDE:
 DESIGN LOADS: STAIR & 2ND FLOOR LOADS
 WIND REQUIREMENTS IF WINDOWS AND DOORS ARE BEING ADDED
 OR ALTERED
 10. ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE
 FOLLOWING:
 SITE REQUIREMENTS
 ACCESSIBLE ROUTE
 VERTICAL ACCESSIBILITY
 TOILET AND BATHING FACILITIES
 DRINKING FOUNTAINS
 EQUIPMENT
  
 2) THE LAST KNOWN USE FOR THIS SPACE WAS AN WAREHOUSE
 AND ACCESSORY OFFICE OCCUPANCY PERMIT # 08040438.
 PLEASE SEE THE 2014 FBC-EXISITNG BUILDING CODE
 SECTION 1001.3 CHANGE OF OCCUPANCY CLASSIFICATION.
 WHERE THE OCCUPANCY CLASSIFICATION OF A BUILDING
 CHANGES, THE PROVISIONS OF SECTIONS 1002 THROUGH 1012
 SHALL APPLY. THE APPLICATION, PLANS NOR THE TITLE BLOCK
 INDICATE THERE IS A CHANGE IN OCCUPANCY.
  
 3) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 4) A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 2) EXST. BLDG. CODE SECTION 1005 MEANS OF EGRESS.
 1005.1 GENERAL. MEANS OF EGRESS IN PORTIONS OF
 BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY
 CLASSIFICATION SHALL COMPLY WITH SECTION 1012.
  