2016-06-24 17:56:17RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- FLAT ROOF FLORIDA PRODUCT APPROVAL FL1654-R19
 SUBMITTED:
 THE MAXIMUM DESIGN PRESSURE FOR THE W-138 SELECTED
 ASSEMBLY IS -90 PSF. BONDED ASSEMBLIES DON'T ALLOW
 RATIONAL ANALYSIS TO ENHANCE THE DESIGN PRESSURE. SEE
 NOTE #9 ON PAGE 2 OF 45. ACCORDING TO SEC. R301.2.1.4.3
 FBC-RESIDENTIAL, 5TH EDITION (2014) THIS BUILDING LOOKS
 LIKE IS LOCATED IN EXPOSURE "C". THE DESIGN PRESSURE
 FOR ZONE #3 IS HIGHER THAN -90 PSF. THEREFORE, THIS
 ASSEMBLY CAN NOT BE USED. THE DESIGN PRESSURE FOR ZONE
 #3 IN EXPOSURE "C" IS +/- 95.7 PSF. PROVIDE ANOTHER
 ASSEMBLY THAT MEETS OR EXCEEDS THE DESIGN PRESSURE FOR
 ALL ROOF ZONES.
 NOTE: IF SELECTING ANOTHER ASSEMBLY THAT IS
 MECHANICALLY FASTENED AND THAT ALLOWS NAIL ENHANCING,
 THEN PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS
 REQUIRED.
  