Plan Review Notes For Permit 16061249 |
Permit Number |
16061249 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-06-24 17:56:17 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW COMMENTS. | | CODE: FBC 5TH EDITION (2014). | | | | 1- FLAT ROOF FLORIDA PRODUCT APPROVAL FL1654-R19 | | SUBMITTED: | | THE MAXIMUM DESIGN PRESSURE FOR THE W-138 SELECTED | | ASSEMBLY IS -90 PSF. BONDED ASSEMBLIES DON'T ALLOW | | RATIONAL ANALYSIS TO ENHANCE THE DESIGN PRESSURE. SEE | | NOTE #9 ON PAGE 2 OF 45. ACCORDING TO SEC. R301.2.1.4.3 | | FBC-RESIDENTIAL, 5TH EDITION (2014) THIS BUILDING LOOKS | | LIKE IS LOCATED IN EXPOSURE "C". THE DESIGN PRESSURE | | FOR ZONE #3 IS HIGHER THAN -90 PSF. THEREFORE, THIS | | ASSEMBLY CAN NOT BE USED. THE DESIGN PRESSURE FOR ZONE | | #3 IN EXPOSURE "C" IS +/- 95.7 PSF. PROVIDE ANOTHER | | ASSEMBLY THAT MEETS OR EXCEEDS THE DESIGN PRESSURE FOR | | ALL ROOF ZONES. | | NOTE: IF SELECTING ANOTHER ASSEMBLY THAT IS | | MECHANICALLY FASTENED AND THAT ALLOWS NAIL ENHANCING, | | THEN PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS | | REQUIRED. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 | | [email protected] | | | | |
|